Plan Review Details - Permit 08060213
Plan Review Stops For Permit 08060213
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-09-17 Cont ID  
Sent By jwitmer Date 2008-09-11 Time 13:50 Rev Time 1.33
Received By jwitmer Date 2008-09-11 Time 13:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-08-12 Cont ID  
Sent By jwitmer Date 2008-08-12 Time 12:16 Rev Time 0.77
Received By jwitmer Date 2008-08-12 Time 12:16 Sent To  
Notes
2008-08-12 12:19:44BUILDING PLAN REVIEW
 PERMIT: 08060213
 ADD: 1401 NORTHPOINTE PARKWAY SUITE #
 CONT: CARRICK
 TEL: (561)718-9090
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1A) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACEANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) COMPLIED.
  
 3) 2ND REQUEST, SEE ATTACHED AREIAL, IT APPEARS THIS
 BUILDING COVERS THREE INDIVDUAL LOTS, LOT NUMBER 0251,
 0252 AND 0242. UNITY OF TITLE. THE PROPOSED BUILDING
 STRUCTURE TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE
 LOTS WHICH COMBINE TO FORM 'THE SITE'.A 'UNITY OF
 TITLE' SHALL BE RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF OF TITLE'
 DOCUMENT SO THAT FBC TABLE 601 BOUNDARY LINE
 REQUIREMENTS MAY BE DEEMED NOT APPLICABLE. FORMS ARE
 AVALIBLE AT CITY HALL 5TH FLOOR ZONING DEPARTMENT.
  
 4) -8) COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-30 Cont ID  
Sent By jwitmer Date 2008-06-30 Time 16:38 Rev Time 3.33
Received By jwitmer Date 2008-06-30 Time 16:38 Sent To  
Notes
2008-06-30 16:56:45BUILDING PLAN REVIEW
 PERMIT: 08060213
 ADD: 1401 NORTHPOINTE PARKWAY SUITE #
 CONT: CARRICK
 TEL: (561)718-9090
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) THE INFORMATION REQUESTED BELOW WILL PROVIDE FOR AN
 ACCURATE REVIEW OF YOUR PROJECT AND CREATE LESS
 QUESTIONS IN REGARDS TO THE TYPE OF CONSTRUCTION.
 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT
 IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED E)
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 F ) NUMBER OF FLOORS
  
 3) SEE ATTACHED AREIAL, IT APPEARS THIS BUILDING COVERS
 THREE INDIVDUAL LOTS, LOT NUMBER 0251, 0252 AND 0242.
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'.A 'UNITY OF TITLE'
 SHALL BE RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A
 COPY OF THE RECORDED 'UNITY OF OF TITLE' DOCUMENT SO
 THAT FBC TABLE 601 BOUNDARY LINE REQUIREMENTS MAY BE
 DEEMED NOT APPLICABLE. FORMS ARE AVALIBLE AT CITY HALL
 5TH FLOOR ZONING DEPARTMENT.
  
 4) OFFICE 100A NORTH WALL IS THE COMMON WALL TO THE
 STAIRWELL AND EXIT PASSAGEWAY THIS WALL IS NOT
 DESIGNATED AS A RATED WALLPLEASE SEE 707.4.
  
 5)IT ROOM # 107 IF THIS ROOM IS CONSIDERED A TRUE IT
 ROOM, THEN THE WALLS WILL NEED TO BE RATED SEE NEC
 645.2, ALSO SEE ELECTRICAL COMMENTS.
  
 6)LS1 THE PLAN INDICATES A NEW EXIT LIGHT IN THE
 WAREHOUSE AT DOOR# 5 VESTIBULE, BUT THE SIGHT LINE IS
 BLOCKED FROM THE IT ROOM. SEE 1006.3.1 EXIT LIGHTS
 SHALL BE MARKED AND READILY VISIBLE FROM ANY DIRECTION
 OF EXIT ACCESS. PLEASE CORRECT OR ADJUST FIXTURES.
  
 7) LS1 PLANAS ALSO INDICATE A NEW EXIT LIGHT AT DOOR#
 14 LEAVING THE BUSSINESS OCCUPANCY IN TO THE WAREHOUSE
 OCCUPANCY, THE EXISTING BUILDING CODE TABLE 812.4.1
 HAZARD CATEGORIES INDICATES BUSINESSAND S1 OCCUPANCY
 ARE OF THE SAME HAZARD CATEGORY ALLOWING EXITING
 THROUGH THE WAREHOUSE. PLEASE PROVIDE A EGRESS PATH FOR
 THE WAREHOUSE AREA.PLANS INDICATE A FENCED IN AREA AND
 GATE TO THE EGRESS DOOR. FORTHIS DOOR TO BE USED AS A
 MEANS OF EGRESS THIS GATE CAN NOT BE
 LOCKED.1013.2.ADDITIONAL EXIT LIGHTS MAY BE REQUIRED IN
 THE WAREHOUSE AREA DUE TO RACK STORAGE.1006.3.1.
  
 8) LS1 AND A-3 BOTH INDICATE IN HALL 127 CONSIDERED A
 EXIT PASSAGEWAY A FIRE EXTINGHISHER PLEASE PROVIDE
 ADDTIONAL INFORMATION ON THE DIMENSIONS OF THIS UNIT.
 1003.3.3 HORIZONTAL PROJECTIONS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-09-03 Cont ID  
Sent By btrobaug Date 2008-09-03 Time 14:54 Rev Time 0.00
Received By btrobaug Date 2008-09-03 Time 14:51 Sent To  
Notes
2008-09-03 14:55:32SAME SHEETS RESUBMITTED FROM 8/15/08 REVIEW./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-08-15 Cont ID  
Sent By btrobaug Date 2008-08-15 Time 16:59 Rev Time 0.00
Received By btrobaug Date 2008-08-15 Time 16:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-02 Cont ID  
Sent By btrobaug Date 2008-07-02 Time 16:51 Rev Time 0.00
Received By btrobaug Date 2008-07-02 Time 14:22 Sent To  
Notes
2008-07-02 16:44:21 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} LOCATE PANEL "P2" ON THE ELECTRICALPLAN SO THAT
 CLEARANCE REQUIREMENTS CAN BE REVIEWED PER 110.26.
  
 2} PER 301.1 DECLARE THE OCCUPANCY TYPE FOR THE AREA
 UNDER ALTERATION.
  
 3} SHEET E1 ENERGY CALCULATIONSFOR LIGHTING DENSITIES
 ARE ALL CALCULATED AT 1.1WATT/ SQ FT. APPARENTLY USING
 THE USING THE BUILDING AREA METHOD TABLE 13-415.2.C.1.
 INDICATE WHAT BUILDING TYPE WAS USED, SEE COMMENT #2.
  
 4} SEE ARTICLE 645 NEC AND NFPA-75 REGARDING
 REQUIREMENTS FOR THIS ROOM. LOCATE THE DISCONNECTING
 MEANS PER 645.10 ON THE PLANS.
  
 NOTE: A SEPARATE LOW VOLTAGE PERMIT IS REQUIRED PRIOR
 TO INSTALLING THE ACCESS CONTROL SYSTEM
  
 PLEASE REMOVE OLD SHEETS, INSERT NEW ONES, SUBMIT OLD
 SHEETS TO EXPEDITE AND SUBMIT WRITTEN RESPONSE TO THE
 COMMENTS MADE IN THIS REVIEW.
  
 PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE
 SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED. AN
 ELECTRICAL CONTRACTOR MUST REMOVE ALL WIRING IN
 AFFECTED AREAS FOR DEMOLITION AND MAKE SAVE SAME. ALL
 TEMPORARY WIRING FOR THIS DEMOLITION SHALL COMPLY WITH
 ARTICLE 590 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-09-17 Cont ID  
Sent By mwennerg Date 2008-09-17 Time 10:39 Rev Time 0.00
Received By mwennerg Date 2008-09-17 Time 10:39 Sent To B
Notes
2008-09-17 10:40:08PLANS WERE PASSED BY FIRE REVIEW ON 8/22/08. NEW SHEET
 LS-1 WAS STAMPED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-08-22 Cont ID  
Sent By mwennerg Date 2008-08-22 Time 10:17 Rev Time 0.00
Received By mwennerg Date 2008-08-22 Time 10:17 Sent To  
Notes
2008-08-22 10:26:44***PROVISO***
  
 COMMENTS FROM FIRST FIRE REVIEW HAVE BEEN ADDRESSED.
 PLEASE MAKE NOTE THAT IN ADDITION TO SEPARATE SHOP
 DRAWINGS AND PERMITS FOR FIRE SPRINKLER AND FIRE ALARM
 SYSTEMS, EQUIPMENT LAYOUT IS REQUIRED ON BASE PLANS AT
 TIME OF PERMIT APPLICATION PER FBC 106.3.5.1 AND FS
 553.79(2).
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-07-14 Cont ID  
Sent By mawillia Date 2008-07-14 Time 16:02 Rev Time 0.00
Received By mawillia Date 2008-07-14 Time 14:54 Sent To  
Notes
2008-07-14 16:01:56*****DENIED*****
  
  
 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 2.ON SHEET LS-1, IT APPEARS THAT THE NEW EXIT LIGHT
 IN THE CONVERTER CONTROL ROOM [124] DIRECTS PERSONS TO
 THE WAREHOUSE WHICH IS CONSIDERED A MORE HAZARDOUS
 AREA..PLEASE EXPLAIN.
  
 3.ON SHEET E-2, PLEASE EXPLAIN THE CARD READERS IN
 RELATION TO PERSON/PERSONS BEING ABLE TO EGRESS THROUGH
 EXIT DOOR(S) AS PER NFPA 101 - 7.2.1.6.2
  
 4.PLEASE PROVIDE LAYOUT OF THE FIRE SPRINKLER HEADS
 AND FIRE ALARM DEVICES FOR THIS REMODEL.IT IS
 UNDERSTOOD THAT SEPARATE PLANS AND PERMIT WILL BE
 PROVIDED ONCE THE MASTER PERMIT IS PRINTED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-10-21 Cont ID  
Sent By adarroug Date 2008-10-21 Time 11:23 Rev Time 0.00
Received By adarroug Date 2008-10-21 Time 11:23 Sent To M
Notes
2008-10-21 11:23:45TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-09-02 Cont ID  
Sent By adarroug Date 2008-09-02 Time 12:00 Rev Time 0.00
Received By adarroug Date 2008-09-02 Time 12:00 Sent To  
Notes
2008-09-02 12:00:21TO "COMM" BD#13

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-01 Cont ID  
Sent By adarroug Date 2008-08-01 Time 10:55 Rev Time 0.00
Received By adarroug Date 2008-08-01 Time 10:55 Sent To  
Notes
2008-08-01 10:55:45TO "COMM" BD#13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-01 Cont ID  
Sent By mawillia Date 2008-07-14 Time 14:54 Rev Time 0.00
Received By adarroug Date 2008-06-09 Time 14:32 Sent To  
Notes
2008-06-09 14:33:07TO "COMM" BD#23

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-12-10 Cont ID  
Sent By hmoser Date 2008-12-10 Time 07:53 Rev Time 0.00
Received By hmoser Date 2008-12-10 Time 07:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-11-08 Cont ID  
Sent By rregueir Date 2008-11-08 Time 15:33 Rev Time 0.00
Received By rregueir Date 2008-11-08 Time 15:33 Sent To PC
Notes
2008-11-08 15:33:43REV.1 PAGE M-1.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-09-09 Cont ID  
Sent By rregueir Date 2008-09-09 Time 11:21 Rev Time 0.00
Received By rregueir Date 2008-09-09 Time 10:17 Sent To  
Notes
2008-09-09 11:23:39A/C SUB-PERMIT APPLICATION WAS INSIDE THE RESUBMITTAL
 PACKAGE AND NOT PROCESSED AT TIME OF RESUBMITTAL. A SUB
 PERMIT # HAS BEEN GENERATED. HOWEVER, THE SUB-PERMIT
 FEE MUST BE PAID PRIOR TO ISSUANCE OF MASTER AND THIS
 SUB-PERMIT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-08-21 Cont ID  
Sent By rregueir Date 2008-08-21 Time 11:27 Rev Time 0.00
Received By rregueir Date 2008-08-21 Time 11:22 Sent To  
Notes
2008-08-21 11:27:37REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 SEE PREVIOUS REVIEW COMMENTS (ATTACHED FOR REFERENCE).
 ALTMAN BROTHERS HAS STILL NOT SUBMITTED AN APPLICATION
 FOR PERMIT TO PERFORM THIS WORK. REVIEW STATUS WILL
 REMAIN IN FAIL STATUS PENDING RECEIPT OF SUCH
 APPLICATION FOR MECHANICAL PERMIT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-07-01 Cont ID  
Sent By rregueir Date 2008-07-01 Time 13:28 Rev Time 0.00
Received By rregueir Date 2008-07-01 Time 08:50 Sent To  
Notes
2008-07-01 13:28:29REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 MECHANICAL PLANS HAVE BEEN REVIEWED FOR CODE COMPLIANCE
 AND STAMPED. REVIEW WILL REMAIN IN FAIL STATUS PENDING
 APPLICATION FOR PERMIT FROM THE A/C CONTRACTOR. ALTMAN
 BROTHERS HAS ACTED AS THE DESIGNER UNDER THE PROVISIONS
 OF FS 489. AS SUCH, ALTMAN BROTHERS MUST ALSO BE THE
 INSTALLING CONTRACTOR. ONCE ALTMAN BORTHERS APPLIES FOR
 A PERMIT TO PERFORM THE WORK PROPOSED FOR THIS PROJECT,
 THE REVIEW STATUS WILL BE CHANGED TO PASS STATUS AND
 THE PERMIT MAY BE ISSUED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-09-04 Cont ID  
Sent By kstevens Date 2008-09-04 Time 10:08 Rev Time 0.00
Received By kstevens Date 2008-09-04 Time 10:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-08-11 Cont ID  
Sent By kstevens Date 2008-08-11 Time 07:35 Rev Time 0.00
Received By kstevens Date 2008-08-08 Time 16:58 Sent To  
Notes
2008-08-11 08:05:12DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SUBMIT A SANITARY RISER DIAGRAM FOR THE NEW SERVICE
 SINK ADDED. PER SECTION 909.1 THE SINK SHALL DISCHARGE
 DOWNSTREAM OF THE HORIZONTAL WET VENT FOR THE TOILET
 ROOM FIXTURES. PLEASE SHOW THE CONNECTION FOR THE NEW
 SINK. SECTION 106.3.5.1.3.
  
 2. PLEASE REMOVE ALL OLD SHEETS THAT ARE REPLACED AND
 SUBMIT ONE COPY SEPARATELY FOR COMPAIRSON.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-07-07 Cont ID  
Sent By mperson Date 2008-07-07 Time 14:58 Rev Time 0.00
Received By mperson Date 2008-07-07 Time 14:58 Sent To  
Notes
2008-07-07 15:07:43PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 1. PLEASE PROVIDE THE TYPE OF OCCUPANCY AND NUMBER OF
 OCCUPANTS PER FBC- PLUMBING SECTION, 403.1 MINIMUM
 NUMBER OF FIXTURES. PLUMBING FIXTURES SHALL BE PROVIDED
 FOR THE TYPE OF OCCUPANCY AND IN THE MINIMUM NUMBER
 SHOWN IN TABLE 403.1 . TYPES OF OCCUPANCIES NOT SHOWN
 IN TABLE 403.1 SHALL BE CONSIDERED INDIVIDUALLY BY THE
 CODE OFFICIAL. THE NUMBER OF OCCUPANTS SHALL BE
 DETERMINED BY THE FLORIDA BUILDING CODE, BUILDING.
 OCCUPANCY CLASSIFICATION SHALL BE DETERMINED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2008-06-11 Cont ID  
Sent By choops Date 2008-06-11 Time 13:48 Rev Time 0.00
Received By choops Date 2008-06-11 Time 13:48 Sent To  
Notes
2008-06-11 13:49:28***APPROVED - ADDITION OF SIDEWALK CONNECTION***