Plan Review Details - Permit 08060141
Plan Review Stops For Permit 08060141
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2008-08-08 Cont ID  
Sent By lursu Date 2008-08-08 Time 11:56 Rev Time 0.00
Received By lursu Date 2008-08-08 Time 11:56 Sent To  
Notes
2008-08-08 11:58:37NEW ADDRESSES ARE ASSIGNED TO THE NEW CONSTRUCTIONS.
  
 QUESTIONS/COMMENTS:
  
 LACRAMIOARA URSU, MA ,GISP
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2008-06-09 Cont ID  
Sent By lursu Date 2008-06-09 Time 08:52 Rev Time 0.00
Received By lursu Date 2008-06-09 Time 08:52 Sent To  
Notes
2008-06-09 08:52:19***FAILED***
  
 THE NEW STREET NAMES WERE NOT APPROVED BY THIS
 DEPARTMENT .CONTACT WAS MADE USING E-MAILS WITH THE
 OWNER 'S REPRESENTATIVE AND THE FINAL STREET NAMES ARE
 UNDER DISCUSSION .
 NO NEW SITE ADDRESSES WERE ISSUED FOR THE NEW
 BUILDINGS.
  
 QUESTIONS/COMMENTS:
 LACRAMIOARA URSU, MA ,GISP
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-25 Cont ID  
Sent By rmcdouga Date 2008-07-25 Time 16:28 Rev Time 0.00
Received By rmcdouga Date 2008-07-25 Time 16:28 Sent To  
Notes
2008-07-25 16:24:452004 FBC W/2007 REVISIONS
 6 UNIT TOWN HOUSE
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3)FBC R401.4AREA OF QUESTIONABLE
 SOIL.SUBMIT TWO COPIES OF A SIGNED AND SEALED
 GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 4) SUBMIT TWO COPIES OF SIGNED AND SEALED TRUSS
 DRAWINGS AND TRUSS LAYOUT DRAWINGS, THAT HAVE BEEN
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD FOR THE PROJECT. R802.1.6
  
 5) SPECIFY CARBON MONOXIDE DETECTORS ON THE PLANS AS
 REQUIRED BY DCA RULE 9B-3.0472.
  
 6) ON SHEET A1 UNDER THE GARAGE NOTES PLEASE REVISE TO
 SPECIFY THE APPLICABLE SECTIONS OF THE FBC RESIDENTIAL
 CODE. SEE R309.1, R 309.1.1 AND R309.2.
  
 7) PLEASE PROVIDE TWO SETS OF PLANS AND DOCUMENTS AS
 REQUIRED BY FBC 106.1* CITY AMENDMENTS.
  
 8) SUBMIT TWO COPIES OF A SITE PLAN SPECIFYING THE
 SEPARATION DISTANCES BETWEEN BUILDINGS AS WELL AS
 DISTANCES TO PROPERTY LINES. FBC R 302.1.
  
 9) FOR THE WATER HEATER ENCLOSURE UNDER THE STAIRS,
 SHOW COMPLIANCE WITH R311.2.2 UNDER STAIR PROTECTION.
 ENCLOSED ACCESSIBLE SPACE UNDER STAIRS SHALL HAVE
 WALLS, UNDER STAIR SURFACE AND ANY SOFFITS PROTECTED ON
 THE ENCLOSED SIDE WITH 1/2-INCH (12.7 MM) GYPSUM
 BOARD.
  
 10) SHOW COMPLIANCE WITH R602.1.2 FOR FIREBLOCKING OF
 THE CONCEALED SPACE BETWEEN STAIR STRINGERS AT THE TOP
 AND BOTTOM OF THE RUN.
  
 11) WINDOWS A-D IN THE BATHROOMS ARE REQUIRED TO BE
 SAFETY GLAZING IF THEY ARE LESS THAN 60" ABOVE THE
 FLOOR OR WALKING SURFACE. SEE FBC R308.4. (UNIT A)
  
 12) ON SHEET S2, MARK F IN THE ROOF ANCHOR SCHEDULE
 LISTS THE MAXIMUM DESIGN UPLIFT AS 2000 LBS. AND THE
 ALLOWABLE UPLIFT LOAD FOR THE ANCHOR IS 1215 LBS.
 PLEASE CORRECT. FBC R802.1.6.5
  
 13) FBC R803.2.3.1 REQUIRES ROOF SHEATHING TO BE
 FASTENED WITH 8D RING SHANK NAILS AND 10D COMMON NAILS
 ARE SPECIFIED. PLEASE REVISE.
  
 14) ON SHEET S4 A HEAD WALL FIRESTOPPING DETAIL FROM 3M
 HW-D-0075 MODIFIED BY JUDGEMENT # 518786 IS SPECIFIED.
 PLEASE SUBMIT TWO SIGNED AND SEALED COPIES OF THE
 JUDGEMENT FROM THE MANUFACTURER'S ENGINEER.
  
 15) PROVIDE CALCULATIONS FOR ROOF VENTILATION SHOWING
 COMPLIANCE WITH R806.2 MINIMUM AREA.
 THE TOTAL NET FREE VENTILATING AREA SHALL NOT BE LESS
 THAN 1 TO 150 OF THE AREA OF THE SPACE VENTILATED
 EXCEPT THAT THE TOTAL AREA IS PERMITTED TO BE REDUCED
 TO 1 TO 300, PROVIDED AT LEAST 50 PERCENT AND NOT MORE
 THAN 80 PERCENT OF THE REQUIRED VENTILATING AREA IS
 PROVIDED BY VENTILATORS LOCATED IN THE UPPER PORTION OF
 THE SPACE TO BE VENTILATED AT LEAST 3 FEET (914 MM)
 ABOVE EAVE OR CORNICE VENTS WITH THE BALANCE OF THE
 REQUIRED VENTILATION PROVIDED BY EAVE OR CORNICE VENTS.
 AS AN ALTERNATIVE, THE NET FREE CROSS-VENTILATION AREA
 MAY BE REDUCED TO 1 TO 300 WHEN A VAPOR BARRIER HAVING
 A TRANSMISSION RATE NOT EXCEEDING 1 PERM IS INSTALLED
 ON THE WARM SIDE OF THE CEILING.
  
 16) SUBMIT TWO COPIES OF THE ENERGY CALCULATION FORMS
 SIGNED BY THE OWNER/AGENT. USE WORST CASE CALCULATIONS
 OR THEY WILL NEED TO BE DIFFERENT DEPENDING ON THE
 ORIENTATION OF THE BUILDING. ALSO MAKE CORRECTIONS
 NOTED IN COMMENTS FROM OTHER TRADES. FBC CHAPTER 13.
  
 17) PLEASE COMPLY WITH FBC 106.3* CITY AMENDMENTS
 PRODUCT APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 18) SUBMIT TWO COPIES OF PRODUCT APPROVALS AS REQUIRED
 BY DCA RULE 9B-72 FOR THE FOLLOWING ITEMS: WINDOW
 MULLIONS, CONCRETE LINTELS, SIMPSON AND USP
 CONNECTORS.
  
 19) SUBMIT TWO COPIES OF A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY THE CONNECTION
 TYPE, EDGE DISTANCE, SPAN, ANCHOR TYPE AND ANCHOR
 SPACING. FBC R 301.2.1.2.
  
 20) THE NOA THAT WAS SUBMITTED FOR THE LAWSON FIXED
 WINDOW EXPIRED ON MAY 08, 2008. SUBMIT CURRENT NOA NO.
 08-0409.03.
  
 21) THE 1/8" ANNEALED GLASS LISTED IN THE LAWSON HS
 WINDOW NOA DOES NOT HAVE ADEQUATE DESIGN PRESSURES FOR
 THE 6' X 4' XO OR OX HS WINDOWS. HOWEVER, THE OTHERS DO
 HAVE ADEQUATE DESIGN PRESSURES. PLEASE SPECIFY THE
 GLAZING OPTION THAT WILL BE USED IN THE NOA. R301.2.1
  
 22) THE NOA FOR THE AMARR GARAGE DOOR EXPIRES ON
 SEPTEMBER 4, 2008. ANY PERMITS APPLIED FOR AFTER THAT
 DATE WILL REQUIRE A CURRENT NOA. DCA RULE 9B-72
  
 23) THE VALUE OF THE STRUCTURE HAS BEEN DETERMINED TO
 BE $183,756.07 USING ICC BUILDING VALUATION DATA.
 ADDITIONAL FEES OF $278.72ARE DUE.
  
 24) AN ADDRESS IS REQUIRED TO BE ASSIGNED TO THE UNIT
 BY THE CITY BEFORE A PERMIT CAN BE ISSUED. PLEASE
 CONTACT LACRAMIOARA URSU @ 561-822-1239.
  
 NOTE: THE PLANS SPECIFY EXPOSURE CATEGORY B WHICH IS
 CORRECT FOR MOST OF THE BUILDINGS. HOWEVER,THE 8 UNIT
 BUILDINGS NUMBERS 1, 4, 9 AND 14 ARE EXPOSURE CATEGORY
 C. SEE FBC R 301.2.1.4.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-02 Cont ID  
Sent By dpalmer Date 2008-07-02 Time 14:55 Rev Time 0.00
Received By dpalmer Date 2008-07-02 Time 14:55 Sent To  
Notes
2008-07-02 14:56:04 
  
 ** DENIED REVIEW **
  
 THE FOLLOWING IS FOR THE REVIEW OF ALL UNITS *A*,*B*
 AND*C*.
  
 1) NOTE: PLEASE KNOW BASED ON PERMIT APPLICATION AND
 PLANS IT IS UNCLEAR SHOW THESE UNITS WILL ACTUALLY BE
 APPLIED. SOME ITEMS ON PLANS LEND TO A MULTI-FAMILY
 BUILDING AS THERE ARE REFERENCES TO ONE SERVICE,
 DE-RATING OF LOADS FOR MULTIPLE UNITS AND ALL AS
 APPLIED UNDER ONE ADDRESS.
 IF THESE ARE EACH A FEE SIMPLE TOWN HOUSE WITH PROPERTY
 LINES SEPARATING UNITS THIS WILL AFFECT PLANS AND
 REVIEWS.
 IF ONE BUILDING AND DONE AS A CONDO OR MULTI-FAMILY
 BUILDING THEN THE REVIEW COMMENTS WILL ALSO BE
 DIFFERENT.
  
 ** PLEASE COORDINATE APPLICATIONS, TYPES OF BUILDINGS
 ETC. PLEASE SEE COMMENTS BELOW AS THIS WILL AFFECT HOW
 THE REVIEWS/DESIGN IS CORRECTED.
  
 2) NOTE: PLEASE SEE THE APPLIED ADDRESS FOR EACH
 LOCATION ON THE TITLE BLOCKS ON PLANS NEEDS TO BE
 ACCURATE ONCE DETERMINED.
 PLEASE BE SURE TO SEE COMMENTS FROM OTHER TRADES SUCH
 AS FIRE, BUILDING AND THE ADDRESSING REVIEWER.
 PLEASE ADJUST TITLE BLOCKS FOR CORRECT ADDRESS. THIS IS
 REQUIRED FOR ALL SHEETS AND FOR ALL TRADES WHETHER OR
 NOT COMMENT IS MADE BY OTHER REVIEWERS.
 FAC 61G1-16.004, 61G15-23.002
 FBC 106.1.1, 106.5 FOR ADDITIONAL CLARITY AND RECORD
 PLANS.
  
 3) NOTE: PLEASE BE SURE THE FOLLOWING CODE IS REFLECTED
 ON PLANS. THE STATE IS CURRENTLY UNDER THE 2002
 NFPA-72. PLEASE ADJUST.
 PLEASE ALSO KNOW CODE SECTIONS SUCH AS THE NOTE ON E
 SHEETS WHICH REFERENCE SMOKE DETECTION DEVICES PER
 CHAPTER 8 ARE NO LONGER CORRECT AS THE CHAPTER UNDER
 THE CURRENT NFPA-72 HAS CHANGED.
 PLEASE SEE THE FOLLOWING COMMENTS.
 ** PLEASE KEEP IN MIND APPLICATION DATE AFFECT THE
 CODES AND CODE CHANGES WILL BE COMING THIS YEAR IN THE
 STATE OF FLORIDA.
 FS 553.73
 FBC 106.1.1, 106.5
  
 4) NOTE: PLEASE SEE NFPA-72 DEFINITIONS AS THE PLANS
 STATE THERE WILL BE SMOKE DETECTORS INSTALLED HOWEVER
 NO FIRE ALARM PANEL, HORN ETC ARE SHOWN.
 PLEASE KNOW THAT *SMOKE DETECTORS* ARE DEVICES WHICH
 ONLY *DETECT* AND DO NOT SOUND AN ALARM. SMOKE ALARMS
 ARE DEVICES WHICH DETECT AND SOUND. PLEASE VERIFY WHICH
 DEVICES ARE ACTUALLY GOING TO BE INSTALLED.
 IF THESE ARE GOING TO INDEED BE SMOKE ALARMS, PLEASE BE
 SURE TO ADJUST ALL NOTES ON PLANS WHICH INDICATE SMOKE
 DETECTORS.
 PLEASE SEE NFPA72 11.5.1.1, 11.8.3
  
 5) NOTE: PLANS MISSING REQUIRED LIGHT FIXTURE OF SOME
 SORT ON UNITS A AND B AT THE COVERED PATIO.
 PLEASE ALSO SEE THE GREAT ROOMS IN ALL THREE UNITS WILL
 REQUIRE A LIGHT FIXTURE OF SOME SORT ON THE J-BOXES
 SHOWN OR HALF SWITCHED RECEPTACLES IN SAID ROOM.
 PLEASE ALSO SEE MISSING LIGHT FIXTURE OF SOME SORT
 INSIDE UNIT *A* LAUNDRY ROOM.
 210.70
 LS101 7.8
  
 6) NOTE: PLEASE SEE THE SERVICE CALCULATIONS INDICATE A
 600AMP MAIN YET PLANS DO NOT CONTAIN ANY OTHER
 INFORMATION ON THE INDICATED SERVICE.
 230.70, 215.5, 230.76, 230.72, 230.79 ETC
  
 7) NOTE: PLEASE SEE LOAD CALCULATIONS INDICATE
 DE-RATING FOR 8 UNITS HOWEVER THE BUILDING DOES NOT
 CONTAIN 8 UNITS.
 PLEASE SEE OTHER COMMENTS LIKE #1 AND #6 AS THE LOAD
 CALCULATIONS INFORMATION ALONG WITH SERVICE DOES NOT
 COORDINATE.
 PLEASE SEE NEC 220 WHEN ACTUAL FINAL SERVICE IS
 DETERMINED.
 PLEASE COORDINATE ALL PLANS, RISER, EQUIPMENT AND LOAD
 CALCULATIONS.
 FBC 106.1.1, 106.1.2 FOR CLARITY AND ADDITIONAL
 INFORMATION.
  
 8) NOTE: PLANS INDICATE A MAIN DISCONNECT OUTSIDE OF
 EACH UNIT HOWEVER THE RISER SUBMITTED IS MISSING THE
 MAIN DISCONNECT.
 230.70, 230.71, 230.76 230.79 ETC
  
 9) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR AFTER THE FIRST MEANS OF DISCONNECT PER
 250.122, 250.24, 250.110 ETC IF MAIN IS OUTSIDE AS
 SHOWN.
  
 10) NOTE: PLEASE BE SURE TO INDICATE THE REQUIRED
 *FOOTER STEEL* AS PART OF THE GROUND ELECTRODE SYSTEM.
 THE RISER SHOWS BUILDING STEEL HOWEVER MANY TIMES AND
 PER DEFINITIONS BUILDING STEEL IS NOT FOOTER STEEL.
 PLEASE ALSO CLARIFY COLD WATER SYSTEMS IN BUILDING. IF
 METALLIC, THEN PLEASE INCLUDE ON THE RISER.
 250.50
  
 11) NOTE: PLEASE SEE 210.52B1 FOR CIRCUITING OF DINING
 ROOMS/AREAS AND OTHER AREAS OF THE LIKE.
 PLEASE SEE UNIT *A* AS THE AREA OFF KITCHEN WHICH
 APPEARS AS BREAKFAST/BAR AREA DOES FALL UNDER THE AREAS
 LISTED IN 210.52B1.
 PLEASE ADJUST PLANS AND ANY CALCULATIONS ACCORDINGLY TO
 210.11C1, 220.52
  
 12) NOTE: PLEASE SEE UNIT *A* WHICH SHOWS THE WASHER
 CIRCUITED ON WITH LIGHTS AND GARAGE RECEPTACLES WHICH
 IS NOT PERMITTED.
 PLEASE SEE 210.11C2, 220.52B
  
 13) NOTE: PLEASE SEE ALL WATER HEATER LOCATIONS PER
 422.30, 422.31 REQUIRE DISCONNECTING MEANS. A
 RECEPTACLE IS NOT PERMITTED AS SHOWN ON PLANS. THIS
 CHANGED MANY CODE CYCLES AGO IN WHICH A CORD AND PLUG
 IS NOT PERMITTED ON WATER HEATERS.
 PLEASE ADJUST PLANS FOR ALL UNITS.
  
 14) NOTE: PLEASE SEE 422.13 AS WATER HEATERS ARE NOW
 CONSIDERED A CONTINUOUS LOAD UNDER THE 2005 NEC WHICH
 REQUIRES LOADS TO BE FIGURED AT 125%.
  
 15) NOTE: PLEASE KNOW ANY ITEMS WHICH ARE SHOWN ON
 PANELS OR PLANS AS *OPTIONAL* WILL BE REQUIRED TO BE
 REVISED ON EACH AND EVERY UNIT BEFORE ROUGH ELECTRICAL
 INSPECTION ON WHETHER OR NOT THAT UNIT WILL ACTUALLY
 RECEIVE THAT OPTION.
 ** THIS IS NOTED FOR INFORMATION AT THIS TIME AS THIS
 MAY HELP WITH THE DECISION OF EACH UNIT BEFORE
 APPLICATION IS MADE.
 NEC 408.4, 310.16, 220 ETC
 FBC 106.1.1, 106.5 FOR CLARITY AND RECORD PLANS
 COORDINATION.
  
 16) NOTE: PLEASE SEE KITCHEN WALL IN UNIT *B* WHICH IS
 MISSING WALL RECEPTACLE PER 210.52
  
 17) NOTE: PLEASE INDICATEAIC RATINGS FOR ALL SERVICE
 EQUIPMENT.110.9
 PLEASE COMPLETE INFORMATION ON ELECTRICAL PANELS.
 INFORMATION ON PANELS ARE VERY VAGUE AT THIS TIME.
 110.9, 110.3, 90.7
 FBC 106.1.1, 106.1.2 FOR CLARITY AND ADDITIONAL
 INFORMATION.
  
 18) NOTE: IT IS IMPORTANT TO UNDERSTAND COMPLETION OF
 THE BUILDING NEEDS TO TAKE PLACE FOR WALLS ETC ON
 ENERGYCALCULATIONS. PLEASE SEE NOTES FROM OTHER
 TRADES AS THIS WILL AFFECT THE ENTIRE APPLICATION
 PROCESS.
 ** IT IS ALSO IMPORTANT TO UNDERSTAND AS THE RISER,
 PLANS, CALCULATIONS ETC FOR ACTUAL TYPE OF BUILDING IS
 NOT CLEAR AND THERE IS INFORMATION NOT YET SUBMITTED OR
 SHOWN IN DESIGN FOR REVIEW THERE MAY VERY WELL BE NEW
 COMMENTS ON THE FOLLOWING REVIEW. THERE MAY BE SOME
 COMMENTS WHICH COULD NOT POSSIBLY BE MADE AT THIS
 TIME.
  
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2008-06-27 Cont ID  
Sent By rchokshi Date 2008-06-27 Time 16:33 Rev Time 0.00
Received By rchokshi Date 2008-06-27 Time 16:33 Sent To  
Notes
2008-06-27 16:33:52ENG REVIEW REQUIRED FOR THE ENTIRE SITE PERMIT ONLY.
 ENG REVIEW IS NOT REQUIRED FOR EACH INDIVIDUAL UNIT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-07-16 Cont ID  
Sent By mwennerg Date 2008-07-16 Time 10:39 Rev Time 0.00
Received By mwennerg Date 2008-07-16 Time 10:39 Sent To  
Notes
2008-07-16 10:40:09***DENIED***
  
 1) BUILDING ADDRESSING TO BE APPROVED AND FINALIZED.
 THE CORRECT ADDRESS TO BE DISPLAYED IN TITLE BLOCK OF
 EACH SHEET.
  
 2) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY SHALL COMPLY WITH NFPA 101, 2003 EDITION. PLEASE
 ADD NOTE TO PLANS.
  
 3) THE ADDRESS ON EACH BUILDING AND LIVING UNIT SHALL
 MEET THE REQUIREMENTS PER CITY OF WEST PALM BEACH CODE
 FOR MULTIPLE RESIDENTIAL UNITS.
  
 4) EACH LIVING UNIT IS REQUIRED TO BE PROVIDED WITH
 MINIMUM 2A-10B,C RATED FIRE EXTINGUISHER.
  
 5) BUILDING ACCESS TO COMPLY WITH REQUIREMENTS OF NFPA
 1, 2003 EDITION CHAPTER 18.
  
 6) INDICATE LOCATIONS OF NEW AND OR EXISTING FIRE
 HYDRANTS. NEW INSTALLATIONS SHALL BE FULLY OPERATIONAL
 PRIOR TO, DURING AND AFTER CONSTRUCTION.
  
 7) PLEASE PROVIDE GUARDRAIL DETAIL WITH STAIR SECTION.
 MINIMUM STRENGTH REQUIREMENTS HAVE BEEN PROVIDED ON
 PLANS.
  
 8) HARD WIRED SMOKE ALARMS SHALL BE MINIMUM OF (3')
 FROM AC DIFFUSERS. REMOVE TERM SMOKE DETECTORS IF NOT
 APPLICABLE AND REPLACE WITH SMOKE ALARMS.
  
 9) IN ADDITION TO THE FBC, PLEASE PROVIDE OCCUPANCY
 CLAASIFICATION FOR BUILDING AS PER NFPA 101, 2003
 EDITION.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-25 Cont ID  
Sent By rmcdouga Date 2008-07-25 Time 16:28 Rev Time 0.00
Received By rmcdouga Date 2008-06-05 Time 15:58 Sent To  
Notes
2008-06-05 15:59:04TO "COMM" BD#36

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-07-01 Cont ID  
Sent By tgordon Date 2008-07-01 Time 14:51 Rev Time 1.30
Received By tgordon Date 2008-07-01 Time 14:51 Sent To  
Notes
2008-07-01 14:55:14PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW,
 PLEASE SUBMIT MECHANICAL PLANS PER 2004 WPB AMEND.
 106.3.5.4 (10).
  
 2) THE ENERGY CALCULATIONS HAVE MANY ERRORS ON THEM,
 PLEASE HAVE THE ENERGY CALCULATIONS RE-DONE, PER 2004
 FBC 13-103.3
  
 ** SOME OF THE CORRECTIONS TO THE ENERGY CALCULATIONS
 ARE. **
  
 3) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R, PER
 2004 FBC 13-600.3.A, (12-8-06 REVISION).
  
 4) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-103.3.
  
 5) E-CAL'S LINE 8C NEED TO SHOW ALL RAISED FLOORS FOR
 MASTER BATH OVER COVERED PATIO, BEDROOM #2 OVER GARAGE,
 AND BEDROOM #3 OVER COVERED ENTRY, PLEASE READ 2004 FBC
 13-605.2.A.1.1.
  
 6) E-CAL'S LINE 9, PER 2004 FBC 13-602.2.A.1.3 COMMON
 WALLS SEPARATING CONDITIONED TENANCIES SHALL NOT BE
 INCLUDED IN THE AS-BUILT HOUSE ENVELOPE CALCULATION.
  
 7) PLEASE SHOW ON PLANS COMPLIANCE WITH 2004 FBC
 13-602.1.ABC.1.1 COMMON WALLS. WALLS COMMON TO TWO
 SEPARATE CONDITIONED TENANCIES SHALL BE INSULATED TO A
 MINIMUM OF R-11 FOR FRAME WALLS, AND TO R-3 ON BOTH
 SIDES OF COMMON MASONRY WALLS.
  
 8) THE COOLING LOAD CALCULATIONS WILL NEED TO BE
 RE-DONE WITH THE REVISED ENERGY CALCULATIONS, PER 2004
 FBC 13-607.1.ABC.1.
  
 9) PLEASE SHOW COMPLIANCE WITH F.S. 553.885 (1)CARBON
 MONOXIDE ALARM REQUIRED. EVERY BUILDING FOR WHICH A
 BUILDING PERMIT IS ISSUED FOR NEW CONSTRUCTION ON OR
 AFTER JULY 1, 2008, AND HAVING A FOSSIL-FUEL-BURNING
 HEATER OR APPLIANCE, A FIREPLACE, OR AN ATTACHED GARAGE
 SHALL HAVE AN APPROVED OPERATIONAL CARBON MONOXIDE
 ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM USED FOR
 SLEEPING PURPOSES.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-07-07 Cont ID  
Sent By mperson Date 2008-07-07 Time 13:51 Rev Time 0.00
Received By mperson Date 2008-07-07 Time 13:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-06-12 Cont ID  
Sent By kdfreema Date 2008-06-12 Time 08:45 Rev Time 0.00
Received By kdfreema Date 2008-06-12 Time 08:45 Sent To  
Notes
2008-06-12 08:45:20***FAILED***
  
 1. THE PROPERTY MUST BE PLATTED PRIOR TO THE
 COMMENCEMENT OF ANY CONSTRUCTION ACTIVITY.
  
 2. NO LANDSCAPE PLANS WERE SUBMITTED, LANDSCAPE PLANS
 ARE REQUIRED TO BE SUBMITTED WITH EACH PERMIT.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT
 [email protected] OR 561-822-1435 WITH QUESTIONS.