Plan Review Details - Permit 08060116
Plan Review Stops For Permit 08060116
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-05-15 Cont ID  
Sent By jwitmer Date 2009-05-15 Time 09:04 Rev Time 0.77
Received By jwitmer Date 2009-05-14 Time 14:38 Sent To  
Notes
2009-05-15 09:05:23REVISION SHEET G3,G4 & G8

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-08-11 Cont ID  
Sent By jwitmer Date 2008-08-11 Time 15:35 Rev Time 0.55
Received By jwitmer Date 2008-08-11 Time 15:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-30 Cont ID  
Sent By jwitmer Date 2008-06-30 Time 14:11 Rev Time 1.22
Received By jwitmer Date 2008-06-30 Time 14:10 Sent To  
Notes
2008-06-30 14:18:57BUILDING PLAN REVIEW
 PERMIT: 08060116
 ADD: 1541 BELVEDERE RD
 CONT: GUARIDIAN FUELING TECH
 TEL: (904)680--0860
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1B)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) PLANS FAIL TO INDICATE WIND LOAD INFORMATION AND HOW
 THE NEW PUMPS ARE GOING TO BE ATTACHED TO RESIST THE
 MOMENT OF OVERTURNING.
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1.BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
 2.WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3.
 WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4.THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5.COMPONENTS AND CLADDING. THE DESIGN WIND
 PRESSURES IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE
 SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS
 NOT SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
 1609.
 1609.1.3 ANCHORAGE TO RESIST THE MOMENT OF
 OVER-TURNING, UPLIFT AND SLIPPAGE.
  
 3) SHEET G-6 PLEASE INDICATE COMPLIANCE WITH REACH
 RANGESFOR THE DESPENSER DETAIL. 11-4.27.3- 11-4.27.4.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2009-07-04 Cont ID  
Sent By dpalmer Date 2009-07-04 Time 14:25 Rev Time 0.00
Received By dpalmer Date 2009-07-04 Time 14:25 Sent To PC
Notes
2009-07-04 14:25:36E-1, E-2

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2009-06-15 Cont ID  
Sent By dpalmer Date 2009-06-15 Time 14:37 Rev Time 0.00
Received By dpalmer Date 2009-06-15 Time 14:37 Sent To PC
Notes
2009-06-15 14:37:50 
  
  
  
 ** DENIED REVISIONS *
  
 1) NOTE: E-3 SUBMITTED AS REVISED YET THERE ARE NO
 REVISIONS FROM THE RECORD SET OF PLANS. THE LAST
 REVISED SHEET NOTED IN THE TITLE BLOCK IS FROM
 7/13/2008. THE NEW SHEET E-3 SUBMITTED HAS THE SAME
 REVISION DATED 7/13/2008.
 ** PLEASE ONLY SUBMIT SHEETS WHICH ARE INDEED BEING
 REVISED.
  
 2) NOTE: PLEASE SEE E-1. NOTE ON THE SCOPE OF WORK HAS
 BEEN REVISED WITH THE REV #2, HOWEVER IT IS UNCLEAR
 WHAT THE REVISION IS? THE SENTENCE IN THIS NOTE STATES:
 * CONNECT NEW TANKS TO*. WHAT ARE THE NEW TANKS BEING
 CONNECTED TO? PLEASE COMPLETE NOTES FOR REVIEW AND
 COORDINATION FOR CODE COMPLIANCE.
 NEC 514 AND FBC 106.5, 106.1.1 FOR CLARITY AND
 COORDINATION OF PLANS.
  
 3) NOTE: PLEASE COORDINATE PLANS. THE PLANS FOR E-2 NOW
 INDICATE THAT THE EXISTING PANEL G WHICH WAS BEING
 REPLACED IS NOW GOING TO REMAIN. HOWEVER THE RISER
 STILL INDICATES THE PANEL G AS A 20 CIRCUIT MLO YET THE
 REVISED PANEL HAS NOW GONE FROM THE QO 24 ON RECORD
 PLANS TO A QO16.
 WHICH ONE WILL IT BE? THE NEW REVISED PANEL SCHEDULE
 SHOWS 16, BUT THIS IS IN CONFLICT WITH THE RISER NOTES.
  
 4) NOTE: PLEASE PROVIDE MORE INFORMATION ON STP RELAYS.
 THE RISER HAS NOW BEEN REVISED TO REMOVE ALL STP RELAYS
 HOWEVER THE PANEL SCHEDULE STILL LISTS FOUR. THE ONLY
 ONE REVISED WAS FOR *FUTURE DIESEL STP*.
 PLEASE COORDINATE.
 NEC 514, AND FBC 106.5, 106.1.1 FOR CLARITY AND
 COORDINATION OF RECORD PLANS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-05-15 Cont ID  
Sent By dpalmer Date 2009-05-15 Time 13:46 Rev Time 0.00
Received By dpalmer Date 2009-05-15 Time 13:46 Sent To  
Notes
2009-05-15 13:46:30**DENIED REVIEW/ PASSED REVIEW**
  
 1) NOTE: SHEET E-1 IS THE ONLY SHEET WITH REVISIONS
 INDICATED ON PLANS WHICH COORDINATE WITH THE TITLE
 BLOCKS. IN FACT SHEET E-2 FOR EXAMPLE IS A COMPLETELY
 DIFFERENT SHEET FROM RECORD SET WITH NO REVISIONS
 INDICATED.
 ONLY SHEET E-1 WAS STAMPED. OTHER SHEETS AS NOTED ARE
 FAILED. PLEASE SUBMIT ALL REVISED ITEMS AND COORDINATE
 TITLE BLOCKS WITH CLOUDED REVISIONS ON PLANS.
 FBC 106.1.1,106.1.2,106.5
 IT IS UNCLEAR WHY SHEETS WITH NO REVISIONS WERE
 SUBMITTED. IT IS ALSO UNCLEAR SHEET E-2 IS NOW
 COMPLETELY DIFFERENT FROM PREVIOUS SHEETS E-2.
  
 ** PLEASE DO NOT SUBMIT THE JOB-SITE PLANS. THESE
 SHOULD BE LOCATED ON-SITE AT ALL TIMES.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-07-29 Cont ID  
Sent By dpalmer Date 2008-07-29 Time 12:43 Rev Time 0.00
Received By dpalmer Date 2008-07-29 Time 12:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-01 Cont ID  
Sent By dpalmer Date 2008-07-01 Time 15:31 Rev Time 0.00
Received By dpalmer Date 2008-07-01 Time 15:31 Sent To  
Notes
2008-07-01 15:31:44 
 ** DENIED **
  
  
  
 1) NOTE: PLEASE BE SURE THE CURRENT ADOPTED CODES ARE
 REQUIRED TO BE STATED ON PLANS PER FS553.73.
 PLEASE SEE THE SHEET E-0 WAS NOT STAMPED DUE TO THE
 NEED FOR REVISED CODES NEEDED.
 PLEASE KNOW THE *CALIFORNIA CODE OF REGULATIONS* WHICH
 WAS NOTE DON E-3 HAS BEEN REDLINED/CROSSED OUT.
 PLEASE INCLUDE THE 2005 NFPA-70, 2003 NFPA-30, 2004 FBC
 W/2007 REVISIONS.
 PLEASE REVISE ON SHEET E-0.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-05-21 Cont ID  
Sent By mawillia Date 2009-05-21 Time 12:32 Rev Time 0.00
Received By mawillia Date 2009-05-21 Time 12:06 Sent To  
Notes
2009-05-21 12:33:53*****REVISION APPROVED*****
  
 THE COVER SHEET FOR THE SET OF PLANS WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-08-12 Cont ID  
Sent By mwennerg Date 2008-08-12 Time 15:09 Rev Time 0.00
Received By mwennerg Date 2008-08-12 Time 15:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-07-02 Cont ID  
Sent By mwennerg Date 2008-07-02 Time 14:49 Rev Time 0.00
Received By mwennerg Date 2008-07-02 Time 14:49 Sent To  
Notes
2008-07-02 14:52:27STAMPED, SIGNED AND DATED SHEET G-1.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-07-01 Cont ID  
Sent By kstevens Date 2009-07-01 Time 09:46 Rev Time 0.00
Received By kstevens Date 2009-07-01 Time 09:46 Sent To  
Notes
2009-07-01 09:46:30TO DVP

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-06-03 Cont ID  
Sent By jgomez Date 2009-06-03 Time 14:44 Rev Time 0.00
Received By jgomez Date 2009-06-03 Time 14:43 Sent To  
Notes
2009-06-03 14:44:38SENT TO DEWEY PALMER'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-05-06 Cont ID  
Sent By shill Date 2009-05-06 Time 16:51 Rev Time 0.00
Received By shill Date 2009-05-06 Time 16:51 Sent To  
Notes
2009-05-06 16:52:27COMM BOARD #6
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-17 Cont ID  
Sent By adarroug Date 2008-07-17 Time 15:23 Rev Time 0.00
Received By adarroug Date 2008-07-17 Time 15:23 Sent To  
Notes
2008-07-17 15:28:00TO "COMM" BD#18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-02 Cont ID  
Sent By mwennerg Date 2008-07-02 Time 14:55 Rev Time 0.00
Received By mwennerg Date 2008-06-05 Time 14:30 Sent To  
Notes
2008-06-05 14:30:32TO "COMM" BD#17

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-05-15 Cont ID  
Sent By rregueir Date 2009-05-15 Time 11:39 Rev Time 0.00
Received By rregueir Date 2009-05-15 Time 11:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-06-30 Cont ID  
Sent By tgordon Date 2008-06-30 Time 09:04 Rev Time 0.30
Received By tgordon Date 2008-06-30 Time 09:04 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status N Date 2009-05-11 Cont ID  
Sent By kdfreema Date 2009-05-11 Time 11:53 Rev Time 0.00
Received By kdfreema Date 2009-05-11 Time 11:53 Sent To  
Notes
2009-05-11 11:54:39***PROVISO***
  
 ALL LANDSCAPING DAMAGED DURING PROPOSED CONSTRUCTION
 SHALL BE REPLACED.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 WITH QUESTIONS.

Review Stop Z ZONING
Rev No 2 Status P Date 2008-07-22 Cont ID  
Sent By kdfreema Date 2008-07-22 Time 09:19 Rev Time 0.00
Received By kdfreema Date 2008-07-22 Time 09:19 Sent To  
Notes
2008-07-22 09:20:30***PROVISO***
  
 ALL LANDSCAPING DAMAGED DURING PROPOSED WORK SHALL BE
 REPLACED.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 WITH QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status P Date 2008-06-12 Cont ID  
Sent By choops Date 2008-06-12 Time 14:12 Rev Time 0.00
Received By choops Date 2008-06-12 Time 14:12 Sent To  
Notes
2008-06-12 14:16:21***APPROVED***
  
 PROVISO:LOCATION OF REPLACED EQUIPMENT/CONCRETE TO
 MATCH EXISTING AS SHOWN.ALL REMOVED/DAMAGED
 LANDSCAPING SHALL BE REPLACED.