2008-12-01 15:03:17BUILDING PLAN REVIEW
 PERMIT: 08060051
 ADD: 300 N DIXIE HWY
 CONT: KNIGHT ELECTRIC
 TEL: (561)689- 3500
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) 2ND REQUEST, FEUL STORAGE TANK IS BEING LOCATED TO
 THE EXTERIOR OF THE BUILDING AS PER M-1,( OPEN PARKING
 GARAGE) PLEASE PROVIDE ATTACHMENT FOR MOMENT OF
 OVERTURNING, UPLIFT AND SLIPPAGE. 1609.3.1.
 VISITED JOBSITE PARKING GAGARE CONSIDERED OPEN!
  
 3 )2ND REQUEST, PLEASE PROVIDE WIND INFORMATION:
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3.
 WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 4) 2ND REQUEST, SHEET E-3 GENERATOR DETAIL INDICATES TO
 SEE STRUCTURAL SHEET FOR SLAB DETAILS, ALSO INCLUDE
 ANCHOR DETAILS FOR THE NEW GENERATOR. 1609.3.1
 ANCHORAGE AGAINST OVERTURNING, UPLIFT AND SLIDDING.
 MISSING ARCHITECURAL AND STRUCTURAL SHEETS.
  
 5-6) COMPLIED.
  
 7) NEW COMMENT, VISITED JOBSITE AND THE SOUTH WALL OF
 THE PARKING GARAGE IS OPEN TO TTHE WEATHER, A WING WALL
 APPROXIMATELY 42" TALL. SHEET M-1 NEW GENERATOR AREA
 INDICATES A LOUVER IN THE WALL, IS THERE GOING TO BE A
 NEW WALL INSTALLED BETWEEN COLUMNS?
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-30 Cont ID  
Sent By jwitmer Date 2008-06-30 Time 15:01 Rev Time 1.11
Received By jwitmer Date 2008-06-30 Time 15:01 Sent To  
Notes
2008-06-30 15:31:17BUILDING PLAN REVIEW
 PERMIT: 08060051
 ADD: 300 N DIXIE HWY
 CONT: KNIGHT ELECTRIC
 TEL: (561)689- 3500
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) FEUL STORAGE TANK IS BEING LOCATED TO THE EXTERIOR
 OF THE BUILDING AS PER M-1, PLEASE PROVIDE ATTACHMENT
 FOR MOMENT OF OVERTURNING, UPLIFT AND SLIPPAGE.
 1609.3.1.
  
 3) PLEASE PROVIDE WIND INFORMATION: 1603.1.4 WIND
 DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3.
 WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 4) SHEET E-3 GENERATOR DETAIL INDICATES TO SEE
 STRUCTURAL SHEET FOR SLAB DETAILS, ALSO INCLUDE ANCHOR
 DETAILS FOR THE NEW GENERATOR. 1609.3.1 ANCHORAGE
 AGAINST OVERTURNING, UPLIFT AND SLIDDING.
 MISSING ARCHITECURAL AND STRUCTURAL SHEETS.
  
 5) E-SHEETS ENGINEER MELQUIADES GARCIA IS MISSING IN
 THIER TITLEBLOCK:
 61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED & SEALED
 BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE:
 NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR,
 THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
 6) P-1 SHEET ENGINEER ROBERTO BETANCOURT ALSO IS
 MISSING INFORMATION IN THEIR TITLE BLOCK:
 61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED & SEALED
 BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE:
 NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR,
 THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-12-04 Cont ID  
Sent By btrobaug Date 2008-12-04 Time 12:11 Rev Time 0.00
Received By btrobaug Date 2008-12-04 Time 10:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-02 Cont ID  
Sent By btrobaug Date 2008-07-02 Time 13:34 Rev Time 0.00
Received By btrobaug Date 2008-07-02 Time 10:33 Sent To  
Notes
2008-07-02 13:04:13 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, NFPA-37, 2004 FBC
 CHAPTER 1 AS AMENDED AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 SHEET E-4:
  
 1} PROVIDE PANEL SCHEDULES FOR "EML" AND "EMP".
  
 2} CIRCUIT #3 IN PANEL "EDP" INCORRECTLY LISTS PANEL
 "EMP" AS A FEED, IT FEEDS PANEL "EML" ON THE RISER
 DIAGRAM.
  
 3} TRANSFORMER "PEG" MUST HAVE PRIMARY AND SECONDARY
 OVERCURRENT PROTECTION PER 450.3(B).
  
 4} INDICATE THE INPUT AND OUTPUT VOLTAGES FOR
 TRANSFORMER "PEG".
  
 5} INDICATE THE EMERGENCY FEED FOR PANEL "EGP",
 TRANSFORMER "T-2" AND PANEL "EGR". HOW ARE THE GARAGE
 EMERGENCY LIGHTS BEING FED?
  
 6} VERIFY THAT XFMR "PEG" AT 15KVA WILL FEED THE 28KVA
 LOAD ON "EMP".
  
 7} PER NFPA-37.4.1.2.3ENGINE ROOMS LOCATED WITHIN
 STRUCTURES SHALL HAVE INTERIOR WALLS, FLOORS, AND
 CEILINGS OF AT LEAST 1-HOUR FIRE RESISTANCE RATING.
 SHEET E-3 INDICATES A METALLIC FENCE ENCLOSING THE
 GENERATOR.
  
 PROVIDE A WRITTEN RESPONSE, REMOVE OLD AND VOIDED
 SHEETS AND PROVIDE ONE COPY OF THE OLD PLANS WHEN
 RESUBMITTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-12-08 Cont ID  
Sent By mawillia Date 2008-12-08 Time 14:29 Rev Time 0.00
Received By mawillia Date 2008-12-08 Time 14:06 Sent To  
Notes
2008-12-08 14:26:13*****APPROVED*****
  
  
 PLAN SHEETS E-1 AND P-1 WERE STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-07-03 Cont ID  
Sent By mwennerg Date 2008-07-03 Time 10:04 Rev Time 0.00
Received By mwennerg Date 2008-07-03 Time 10:04 Sent To  
Notes
2008-07-03 10:12:17***DENIED***
  
 1) TITLE BLOCK SHOWS AN ADDRESS OF 215 OLIVE AVE. AND
 PERMIT APPLICATION INDICATES 300 N. DIXIE HIGHWAY.
 PLEASE CORRELATE AND IF ADDRESS IS ON OLIVE AVE,
 INDICATE NORTH OR SOUTH.
  
 2) INDICATE ADOPTED EDITIONS UNDER CODES AND STANDARDS.
 IN ADDITION, NFPA 110 STANDARD FOR EMERGENCY AND
 STANDBY POWER SYSTEMS SHALL BE REFERENCED.
  
 3) PROVIDE MANUFACTURER SPECIFICATION SHEETS FOR
 GENERATOR AND ASSOCIATED EQUIPMENT.
  
 4) ILLUSTRATE BUILDING OPENINGS IN RELATION TO THE
 EXHAUST TERMINUS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status P Date 2008-11-22 Cont ID  
Sent By rregueir Date 2008-11-22 Time 16:50 Rev Time 0.00
Received By rregueir Date 2008-11-22 Time 16:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-04-28 Cont ID  
Sent By dpalmer Date 2009-04-28 Time 16:47 Rev Time 0.00
Received By dpalmer Date 2009-04-28 Time 16:47 Sent To  
Notes
2009-04-28 16:48:07TO JW'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-04-29 Cont ID  
Sent By jwitmer Date 2009-04-29 Time 13:56 Rev Time 0.00
Received By jwitmer Date 2009-04-20 Time 16:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-13 Cont ID  
Sent By adarroug Date 2008-11-13 Time 11:19 Rev Time 0.00
Received By adarroug Date 2008-11-13 Time 11:19 Sent To  
Notes
2008-11-13 11:20:04TO "BOB"#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-03 Cont ID  
Sent By mwennerg Date 2008-07-03 Time 10:22 Rev Time 0.00
Received By mwennerg Date 2008-06-04 Time 16:34 Sent To  
Notes
2008-06-04 16:51:36TO "COMM" BD#20

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-11-22 Cont ID  
Sent By rregueir Date 2008-11-22 Time 16:48 Rev Time 0.00
Received By rregueir Date   Time   Sent To  
Notes
2008-11-22 16:49:54PROVIDE PRODUCT APPROVAL DOCUMENTATION FOR BUILDING
 PLAN REVIEW WHICH HAS BEEN APPROVED IN WRITING BY THE
 DESIGNER OR RECORD IN ACCORDANCE WITH FBCB 106.3.3.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-06-26 Cont ID  
Sent By tgordon Date 2008-06-26 Time 08:17 Rev Time 0.45
Received By tgordon Date 2008-06-26 Time 08:17 Sent To  
Notes
2008-06-26 08:20:45PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SHOW COMPLIANCE WITH NFPA 37, 6.3.2.4 FUEL
 TANKS WITHIN STRUCTURES SHALL BE PROVIDED WITH SPILL
 CONTAINMENT CONSISTING OF EITHER A WALL, A CURB, OR A
 DIKE HAVING A CAPACITY AT LEAST EQUAL TO THAT OF THE
 LARGEST SURROUNDED TANK.
  
 2) PLEASE SHOW ON PLANS OR STATE IF THERE ARE ANY OTHER
 BUILDINGS, BUILDING OPENINGS, PROPERTY LINES, OR
 WALKWAYS WITH IN 10 FEET OF THE GENERATOR EXHAUST
 OUTLET, PER NFPA 37.
  
 3) PLAN M-1 SHOWS A 72"X48" LOUVER IS TO BE INSTALLED.
 PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR LOUVER,
 SEE FS 553.842(1) AND FAC RULE 9B-72, 9B-72.005, AND
 FAC 9B-72.010(31)(C).
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 *** PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND
 SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B.
 AMEND. 106.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-04-29 Cont ID  
Sent By jwitmer Date 2009-04-29 Time 13:55 Rev Time 0.00
Received By jwitmer Date 2009-04-29 Time 13:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2008-11-24 Cont ID  
Sent By mflis Date 2008-11-24 Time 12:14 Rev Time 0.00
Received By mflis Date 2008-11-24 Time 12:14 Sent To  
Notes
2008-11-24 12:15:17ZONING REVIEW: PASSED WITH PROVISO:
  
 ** PARKING SPACE #22 SHALL BE REMOVED AND STRIPED OFF
 IN WHITE AS THE INSTALLATION OF THE BOLLARDS AND
 EQUIPMENT WILL MAKE IN NON-FUNCTIONAL.
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status P Date 2008-06-14 Cont ID  
Sent By astelly Date 2008-06-14 Time 09:51 Rev Time 0.00
Received By astelly Date 2008-06-14 Time 09:51 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved