2008-07-16 16:17:47 | PLUMBING PLAN REVIEW: |
| DENIED **2ND TIME: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE |
| DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW |
| COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW |
| COMMENTS. |
| NOTE: THERE WERE NO COMMENT RESPONSES FROM THE |
| DESIGNER. |
| |
| 1. A} & B} "OK" COMMENTS ADDRESSED. |
| |
| 2. A} & B} "OK" COMMENT ADDRESSED. |
| |
| 3. PROVIDE DETAILS OF FIRE STOPPING OF NEW PROPOSED |
| PVC SANITARY PLUMBING PIPIES THROUGH FLOORS COMPLIANT |
| WITH FBC-2004 BUILDING SECTION 717 CONCEALED SPACES |
| WITH UL LISTINGS. |
| |
| **NOTE: NO COMMENT RESPONSE FROM THE DESIGNER AND |
| COMMENT WAS NOT ADDRESSED. |
| |
| 4. CLEARLY IDENTIFY ALL PLUMBING FIXTURES ON THE |
| PROPOSED BATHROOM FLOOR PLANS. THE SHOWER ON THE FLOOR |
| PLAN LOOKS LIKE A BATHTUB. PER FBC-2004 PLUMBING |
| SECTION 401.1 SCOPE. |
| |
| **NOTE: NO COMMENT RESPONSE FROM THE DESIGNER AND THE |
| COMMENT WAS NOT COMPLETELY ADDRESSED. SOME FIXTURES ARE |
| STILL NOT CLEARLY IDENTIFIED. |
| |
| 5. PROVIDE THE FOLLOWING INFORMATION FOR THE PROPOSED |
| 1ST FLOOR ADA BATHROOM COMPLIANT WITH FBC-2004 CHAPTER |
| 11 FLORIDA ACCESSIBILITY CODE. |
| |
| **NOTE: NO COMMENT RESPONSE FROM THE DESIGNER AND THE |
| COMMENT WAS PARTIALLY ADDRESSED. BELOW ARE THE ITEMS |
| THAT STILL NEED TO BE ADDRESSED TO MEET ADA |
| COMPLIANCE. |
| |
| **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED WITH |
| THE FOLLOWING INFORMATION) |
| |
| 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28.**NOTE: |
| COMMENT NOT ADDRESSED. CLEARLY INDICATE THE CLEAR FLOOR |
| SPACE ON THE PROPOSED ADA COMPLIANT 1ST FLOOR BATHROOM |
| FLOOR PLAN. |
| |
| 11-4.16.3 HEIGHT. 17" TO 19". |
| **NOTE: COMMENT NOT ADDRESSED ON WATER CLOSET ADA |
| DETAILS. |
| |
| 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44" |
| HIGH. |
| **NOTE: COMMENT NOT ADDRESSED ON WATER CLOSET ADA |
| DETAILS. |
| |
| 11-4.16.6 DISPENSERS. SEE FIGURE 29(B). |
| **NOTE: COMMENT NOT ADDRESSED ON WATER CLOSET ADA |
| DETAILS. |
| |
| **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL |
| REQUIRED WITH THE FOLLOWING INFORMATION) |
| |
| 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND |
| A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE |
| 32) |
| **NOTE: COMMENT NOT ADDRESSED. CLEARLY INDICATE THE |
| CLEAR FLOOR SPACE ON THE PREPOSED ADA COMPLIANT 1ST |
| FLOOR BATHROOM FLOOR PLAN. |
| |
| 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO |
| PROTECT AGAINST CONTACT. |
| **NOTE: COMMENT NOT ADDRESSED ON LAVATORY & MIRROR ADA |
| DETAIL. |
| |
| 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND |
| ELECTRONICALLY CONTROLLED ARE EXAMPLES. |
| **NOTE: COMMENT NOT ADDRESSED ON LAVATORY & MIRROR ADA |
| DETAIL. |
| |
| ** 11-4.20 BATHTUBS (ELAVATION DETAIL REQUIRED WITH THE |
| FOLLOWING INFORMATION) |
| |
| 11-4.20.2 CLEARFLOOR SPACE. (SEE FIGURE 33)**NOTE: |
| COMMENT NOT ADDRESSED. CLEARLY INDICATE THE CLEAR FLOOR |
| SPACE ON THE PROPOSED ADA COMPLIANT 1ST FLOOR BATHROOM |
| FLOOR PLAN. |
| |
| 11-4.20.3 SEAT. REQUIRED. (SEE FIGURE 33 & 34)**NOTE: |
| COMMENT NOT ADDRESSED ON BATHTUB ADA DETAIL. CLEARLY |
| INDICATE THE SEAT ON THE DETAIL. |
| |
| 6. "OK" COMMENT ADDRESSED. |
| |
| **THE FOLLOWING ARE NEW ITEMS THAT NEED TO BE |
| ADDRESSED DUE TO THE RESUBMITTED PLANS WITH DESIGN |
| CHANGES** |
| |
| 7. 1ST AND 2ND FLOOR PLAN PLUMBING ISOMETRICS: PLEASE |
| CLEARLY INDICATE THE VENT TERMINATION FROM THE PROPOSED |
| 1ST FLOOR BATHROOM. PLAN INDICATES "TO 2ND FLOOR", |
| HOWEVER THERE IS NO CONTINUATION OF THIS VENT INDICATED |
| ON THE 2ND FLOOR ISOMETRIC. PER FBC- PLUMBING SECTION |
| 901.1 SCOPE AND SECTION 903.3 VENT TERMINATION. |
| |
| 8. DUE TO THE FACT THAT THIS IS A COMMERICIAL R-2 |
| BUILDING PLEASE PROVIDE THE FOLLOWING. PER FBC-2004 |
| CHAPTER 1, SECTION 106.3.5.1.3, PLUMBING |
| (3)(5)(8)(10)(13): AN ISOMETRIC POTABLE WATER RISER |
| DIAGRAM IS REQUIRED FOR THE PROPOSED WORK FOR BOTH THE |
| HOT AND COLD WATER INDICATING THE PIPE SIZES, VALVE |
| LOCATIONS, LOCATION OF THE WATER SUPPLY LINE WITH |
| BACKFLOW PREVENTER **608, THERMAL EXPANSION CONTROL FOR |
| THE WATER HEATER **607.3, AND LOCATION OF THE |
| WATER-HAMMER ARRESTORS WHERE QUICK CLOSING VALVES ARE |
| UTILIZED (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE |
| MAKERS) **604.9. |
| NOTE: IF THE WATER HEATER W/THERMAL EXPANSION CONTROL |
| AND THE BACKFLOW PREVENTER ARE EXISTING, PLEASE CLEARLY |
| INDICATE THIS ON THE PLANS. |
| |
| 9. THE 1ST AND 2ND FLOOR PLAN PLUMBING ISOMETRICS: THE |
| LEGENDS DO NOT INDICATE WHAT A BT (BATHTUB W/SHOWER) |
| TYPE FIXTURE IS. ALSO ON THE 2ND FLOOR PLAN PLUMBING |
| ISOMETRIC THE BT (BATHTUB W/SHOWER) IS NOT IDENTIFIED. |
| PER FBC- PLUMBING SECTIONS 401.1 AND 701.1 SCOPE. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |