Plan Review Details - Permit 08060012
Plan Review Stops For Permit 08060012
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-07-31 Cont ID  
Sent By mjacobs Date 2008-07-31 Time 13:35 Rev Time 0.00
Received By mjacobs Date 2008-07-31 Time 09:38 Sent To  
Notes
2008-07-31 13:35:08 
 BUILDING PLAN REVIEW
 PERMIT: 08060012
 ADD: 1117 N. ROSEMARY AVE.
 CONT: KDN CONSTRUCTION SERVICES
 TEL: (561)662-1002
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 **NO RESPONSE NOT ADDRESSED** INDICATE THE TYPE OF
 BUILDING PER CHAPTER 6 AND TABLE 601 AND TABLE 503. IS
 THERE A FIRE SPRINKLER SYSTEM IN THE BUILDING? IF SO,
 SHOW HOW THE NEW WALLS WILL AFFECT THE LAYOUT OF THE
 SPRINKLER HEADS. THE NEW LAYOUT MAY BE SHOWN ON THE
 REFLECTED CEILING PLANS. 106.3.5.1.1(5)
 3)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 **NO RESPONSE NOT ADDRESSED**
 4) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
  
 **NO COMMENT NOT ADDRESSED**
 5)IF BOTH BATHROOMS ARE TO BE ACCESSIBLE THEY SHALL
 MEET THE REQUIREMENTS 11-4.16, 11-4.19, 11-4.20 AND
 11-4.23. INDICATE THE CLEAR FLOOR SPACE ON THE
 DRAWINGS.THE PLANS SHALL INDICATE THE TYPE OF BACKING
 SUPPORT FOR THE GRAB RAILS. THE PROPOSED SECOND FLOOR
 BATH ROOM IS MISSING THE LOCATION THE GRAB BARS. AS
 STATED IN THE FIRST REVIEW THE ACCESSIBLE BATHROOMS
 SHALL MEET THE REQUIREMENTS OF SECTIONS ABOVE. AN
 IN-TUB SEAT SHALL BE PROVIDED PER 11-4.20.3 AND FIG 33
 AND 34. IF A SHOWER IS INSTALLED INSTEAD OF A TUB, SEE
 11-4.21. PROVIDE ELEVATION DRAWINGS SHOWING THESE
 REQUIREMENTS.
  
 6) OK
  
 7)STATE WHAT TYPE OF MATERIALS WILL BE USED TO
 CONSTRUCT THE NEW STORAGE ROOM AND INDICATE THE TYPE
 AND QUANTITY OF MATERIALS WHICH WILL BE STORED. NOTE:
 THE WALLS MAY REQUIRE A FIRE RATING, DEPENDING ON THE
 STORED MATERIALS. ADDITIONAL INFORMATION IS REQUIRED.
 106.1.2*
  
 THE SCALE ON THE PLANS INDICATES 1/4" PER FOOT;
 HOWEVER, THE DIMENSIONS INDICATED ON THE DRAWINGS DO
 NOT CORRESPOND WITH THE ?? SCALE. INDICATE THE SIZE OF
 THE DOORS OF THE NEW ACCESSIBLE BATHROOMS. SEE FBC
 (EXISSTING) 605.5.1.1
 8)ALL SHEETS SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON TAKING RESPONSIBILITY FOR THE
 DRAWINGS. BUILDING PLANS SHALL BE DRAWN TO A MINIMUM
 1/8 INCH SCALE. 106.1.3
  
 **NEW** THE CLAIMED VALUATION ON THE PERMIT APPLICATION
 IS LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD) MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 712.4.1.2 FLOOR PENETRATIONS FOR THE PIPES SHALL MEET
 THE REQUIREMENTS BELOW, WHICH SHALL BE SHOWN ON THE
 DRAWINGS.
 THROUGH PENETRATIONS SHALL BE PROTECTED BY AN APPROVED
 THROUGH-PENETRATION FIRE-STOP SYSTEM INSTALLED AND
 TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A
 MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH OF
 WATER. THE SYSTEM SHALL HAVE AN F RATING AND A T RATING
 OF NOT LESS THAN 1 HOUR BUT NOT LESS THAN THE REQUIRED
 RATING OF THE FLOOR PENETRATED.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-11 Cont ID  
Sent By mjacobs Date 2008-06-11 Time 08:39 Rev Time 0.00
Received By mjacobs Date 2008-06-11 Time 06:03 Sent To  
Notes
2008-06-11 08:39:13BUILDING PLAN REVIEW
 PERMIT: 08060012
 ADD: 1117 N. ROSEMARY AVE.
 CONT: KDN CONSTRUCTION SERVICES
 TEL: (561)662-1002
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 5)IF BOTH BATHROOMS ARE TO BE ACCESSIBLE THEY SHALL
 MEET THE REQUIREMENTS11-4.16, 11-4.19, 11-4.20 AND
 11-4.23.
  
 6)INDICATE CLEARLY WEATHER THIS IS A TRANSIENT OR
 NONTRANSIENT FACILITY. SEE FBC 310.
  
 7)STATE WHAT TYPE OF MATERIALS WILL BE USED TO
 CONSTRUCT THE NEW STORAGE ROOM AND INDICATE THE TYPE
 AND QUANTITY OF MATERIALS WHICH WILL BE STORED. NOTE:
 THE WALLS MAY REQUIRE A FIRE RATING, DEPENDING ON THE
 STORED MATERIALS. ADDITIONAL INFORMATION IS REQUIRED.
 106.1.2*
  
 8)ALL SHEETS SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON TAKING RESPONSIBILITY FOR THE
 DRAWINGS. BUILDING PLANS SHALL BE DRAWN TO A MINIMUM
 1/8 INCH SCALE. 106.1.3
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-07-17 Cont ID  
Sent By btrobaug Date 2008-07-17 Time 13:48 Rev Time 0.00
Received By btrobaug Date 2008-07-17 Time 13:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-06-10 Cont ID  
Sent By btrobaug Date 2008-06-10 Time 12:49 Rev Time 0.00
Received By btrobaug Date 2008-06-10 Time 12:20 Sent To  
Notes
2008-06-10 12:48:12 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 2} 210.70(B) GUEST ROOMS OR GUEST SUITES IN HOTELS,
 MOTELS, OR SIMILAR OCCUPANCIES, GUEST ROOMS OR GUEST
 SUITES SHALL HAVE AT LEAST ONE WALL SWITCH-CONTROLLED
 LIGHTING OUTLET INSTALLED IN EVERY HABITABLE ROOM AND
 BATHROOM.** INDICATE COMPLIANCE WITH SAME ON THE
 PLAN.SEE CHAPTER 11 FBC ACCESSIBILITY FOR REACH
 REQUIREMENTS IN THE ACCESSIBLE BATHROOM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-08-01 Cont ID  
Sent By mwennerg Date 2008-08-01 Time 10:28 Rev Time 0.00
Received By mwennerg Date 2008-08-01 Time 10:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-06-10 Cont ID  
Sent By mwennerg Date 2008-06-10 Time 13:58 Rev Time 0.00
Received By mwennerg Date 2008-06-10 Time 13:58 Sent To  
Notes
2008-06-10 14:03:14***DENIED***
  
 1) SEE ELECTRICAL COMMENT #1 REGARDING REQUIREMENTS FOR
 DRAWINGS.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 3) WILL WORK IMPACT EXISTING FIRE SPRINKLER SYSTEM AND
 SMOKE ALARMS?
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-15 Cont ID  
Sent By adarroug Date 2008-07-15 Time 08:43 Rev Time 0.00
Received By adarroug Date 2008-07-15 Time 08:43 Sent To  
Notes
2008-07-15 08:44:06TO "BOB"#9

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-11 Cont ID  
Sent By tgordon Date 2008-06-11 Time 15:46 Rev Time 0.00
Received By tgordon Date 2008-06-03 Time 11:13 Sent To  
Notes
2008-06-03 11:15:34TO "BOB"#6

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-07-16 Cont ID  
Sent By tgordon Date 2008-07-16 Time 09:40 Rev Time 0.30
Received By tgordon Date 2008-07-16 Time 09:40 Sent To  
Notes
2008-07-16 09:41:31BATH EXHAUST FANS ONLY.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-06-11 Cont ID  
Sent By tgordon Date 2008-06-11 Time 15:37 Rev Time 0.30
Received By tgordon Date 2008-06-11 Time 15:37 Sent To  
Notes
2008-06-11 15:45:03PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE BATHROOMS WILL REQUIRE EXHAUST FANS THAT
 DISCHARGE TO THE OUTDOORS, PER 2004 FBC/M 402.3.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-07-16 Cont ID  
Sent By mperson Date 2008-07-17 Time 16:09 Rev Time 0.00
Received By mperson Date 2008-07-17 Time 09:39 Sent To  
Notes
2008-07-16 16:17:47PLUMBING PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW
 COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW
 COMMENTS.
 NOTE: THERE WERE NO COMMENT RESPONSES FROM THE
 DESIGNER.
  
 1. A} & B} "OK" COMMENTS ADDRESSED.
  
 2. A} & B} "OK" COMMENT ADDRESSED.
  
 3. PROVIDE DETAILS OF FIRE STOPPING OF NEW PROPOSED
 PVC SANITARY PLUMBING PIPIES THROUGH FLOORS COMPLIANT
 WITH FBC-2004 BUILDING SECTION 717 CONCEALED SPACES
 WITH UL LISTINGS.
  
 **NOTE: NO COMMENT RESPONSE FROM THE DESIGNER AND
 COMMENT WAS NOT ADDRESSED.
  
 4. CLEARLY IDENTIFY ALL PLUMBING FIXTURES ON THE
 PROPOSED BATHROOM FLOOR PLANS. THE SHOWER ON THE FLOOR
 PLAN LOOKS LIKE A BATHTUB. PER FBC-2004 PLUMBING
 SECTION 401.1 SCOPE.
  
 **NOTE: NO COMMENT RESPONSE FROM THE DESIGNER AND THE
 COMMENT WAS NOT COMPLETELY ADDRESSED. SOME FIXTURES ARE
 STILL NOT CLEARLY IDENTIFIED.
  
 5. PROVIDE THE FOLLOWING INFORMATION FOR THE PROPOSED
 1ST FLOOR ADA BATHROOM COMPLIANT WITH FBC-2004 CHAPTER
 11 FLORIDA ACCESSIBILITY CODE.
  
 **NOTE: NO COMMENT RESPONSE FROM THE DESIGNER AND THE
 COMMENT WAS PARTIALLY ADDRESSED. BELOW ARE THE ITEMS
 THAT STILL NEED TO BE ADDRESSED TO MEET ADA
 COMPLIANCE.
  
 **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
  
 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28.**NOTE:
 COMMENT NOT ADDRESSED. CLEARLY INDICATE THE CLEAR FLOOR
 SPACE ON THE PROPOSED ADA COMPLIANT 1ST FLOOR BATHROOM
 FLOOR PLAN.
  
 11-4.16.3 HEIGHT. 17" TO 19".
 **NOTE: COMMENT NOT ADDRESSED ON WATER CLOSET ADA
 DETAILS.
  
 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44"
 HIGH.
 **NOTE: COMMENT NOT ADDRESSED ON WATER CLOSET ADA
 DETAILS.
  
 11-4.16.6 DISPENSERS. SEE FIGURE 29(B).
 **NOTE: COMMENT NOT ADDRESSED ON WATER CLOSET ADA
 DETAILS.
  
 **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL
 REQUIRED WITH THE FOLLOWING INFORMATION)
  
 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE
 32)
 **NOTE: COMMENT NOT ADDRESSED. CLEARLY INDICATE THE
 CLEAR FLOOR SPACE ON THE PREPOSED ADA COMPLIANT 1ST
 FLOOR BATHROOM FLOOR PLAN.
  
 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 **NOTE: COMMENT NOT ADDRESSED ON LAVATORY & MIRROR ADA
 DETAIL.
  
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
 **NOTE: COMMENT NOT ADDRESSED ON LAVATORY & MIRROR ADA
 DETAIL.
  
 ** 11-4.20 BATHTUBS (ELAVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION)
  
 11-4.20.2 CLEARFLOOR SPACE. (SEE FIGURE 33)**NOTE:
 COMMENT NOT ADDRESSED. CLEARLY INDICATE THE CLEAR FLOOR
 SPACE ON THE PROPOSED ADA COMPLIANT 1ST FLOOR BATHROOM
 FLOOR PLAN.
  
 11-4.20.3 SEAT. REQUIRED. (SEE FIGURE 33 & 34)**NOTE:
 COMMENT NOT ADDRESSED ON BATHTUB ADA DETAIL. CLEARLY
 INDICATE THE SEAT ON THE DETAIL.
  
 6. "OK" COMMENT ADDRESSED.
  
 **THE FOLLOWING ARE NEW ITEMS THAT NEED TO BE
 ADDRESSED DUE TO THE RESUBMITTED PLANS WITH DESIGN
 CHANGES**
  
 7. 1ST AND 2ND FLOOR PLAN PLUMBING ISOMETRICS: PLEASE
 CLEARLY INDICATE THE VENT TERMINATION FROM THE PROPOSED
 1ST FLOOR BATHROOM. PLAN INDICATES "TO 2ND FLOOR",
 HOWEVER THERE IS NO CONTINUATION OF THIS VENT INDICATED
 ON THE 2ND FLOOR ISOMETRIC. PER FBC- PLUMBING SECTION
 901.1 SCOPE AND SECTION 903.3 VENT TERMINATION.
  
 8. DUE TO THE FACT THAT THIS IS A COMMERICIAL R-2
 BUILDING PLEASE PROVIDE THE FOLLOWING. PER FBC-2004
 CHAPTER 1, SECTION 106.3.5.1.3, PLUMBING
 (3)(5)(8)(10)(13): AN ISOMETRIC POTABLE WATER RISER
 DIAGRAM IS REQUIRED FOR THE PROPOSED WORK FOR BOTH THE
 HOT AND COLD WATER INDICATING THE PIPE SIZES, VALVE
 LOCATIONS, LOCATION OF THE WATER SUPPLY LINE WITH
 BACKFLOW PREVENTER **608, THERMAL EXPANSION CONTROL FOR
 THE WATER HEATER **607.3, AND LOCATION OF THE
 WATER-HAMMER ARRESTORS WHERE QUICK CLOSING VALVES ARE
 UTILIZED (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE
 MAKERS) **604.9.
 NOTE: IF THE WATER HEATER W/THERMAL EXPANSION CONTROL
 AND THE BACKFLOW PREVENTER ARE EXISTING, PLEASE CLEARLY
 INDICATE THIS ON THE PLANS.
  
 9. THE 1ST AND 2ND FLOOR PLAN PLUMBING ISOMETRICS: THE
 LEGENDS DO NOT INDICATE WHAT A BT (BATHTUB W/SHOWER)
 TYPE FIXTURE IS. ALSO ON THE 2ND FLOOR PLAN PLUMBING
 ISOMETRIC THE BT (BATHTUB W/SHOWER) IS NOT IDENTIFIED.
 PER FBC- PLUMBING SECTIONS 401.1 AND 701.1 SCOPE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-06-11 Cont ID  
Sent By mperson Date 2008-06-11 Time 13:14 Rev Time 0.00
Received By mperson Date 2008-06-11 Time 13:14 Sent To  
Notes
2008-06-11 14:20:48PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. 1ST FLOOR PLAN PLUMBING ISOMETRIC: PLEASE CORRECT
 THE FOLLOWING PER FBC-2004 PLUMBING THE FOLLOWING
 SECTIONS.
  
 A} PLEASE DELETE THE WATER-SEAL TRAP BEING INDICATED
 FOR THE WATER CLOSET. A WATER CLOSET HAS AN INTEGRAL
 TRAP AND ONE IS NOT REQUIRED. PER SECTION 1002.1
 FIXTURE TRAPS.
  
 B} WHY IS THERE A CLEANOUT BEING INDICATED BETWEEN THE
 WATER CLOSET AND THE SHOWER? ITS NOT REQUIRED AND
 SHOULD BE DELETED. PER SECTION 701.1 SCOPE.
  
 2. 2ND FLOOR PLAN PLUMBING ISOMETRIC: PLEASE CORRECT
 THE FOLLOWING PER FBC-2004 PLUMBING THE FOLLOWING
 SECTIONS.
  
 A} PLEASE DELETE THE WATER-SEAL TRAP BEING INDICATED
 FOR THE WATER CLOSET. A WATER CLOSET HAS AN INTEGRAL
 TRAP AND ONE IS NOT REQUIRED. PER SECTION 1002.1
 FIXTURE TRAPS.
  
 B} THE HORIZONTAL DRY VENT BEING INDICATED BETWEEN THE
 WATER CLOSET AND THE VENT STACK IS NOT ALLOWED. PLEASE
 REFERENCE THE ATTACHED ISOMETRIC EXAMPLE ATTACHED TO
 THE 2ND FLOOR ISOMETRIC SHEET THATS COMPLIANT. PER
 SECTION 905.3 VENT CONNECTION TO DRAINAGE SYSTEM.
  
 3. PROVIDE DETAILS OF FIRE STOPPING OF NEW PROPOSED
 PVC SANITARY PLUMBING PIPIES THROUGH FLOORS COMPLIANT
 WITH FBC-2004 BUILDING SECTION 717 CONCEALED SPACES
 WITH UL LISTINGS.
  
 4. CLEARLY IDENTIFY ALL PLUMBING FIXTURES ON THE
 PROPOSED BATHROOM FLOOR PLANS. THE SHOWER ON THE FLOOR
 PLAN LOOKS LIKE A BATHTUB. PER FBC-2004 PLUMBING
 SECTION 401.1 SCOPE.
  
 5. PROVIDE THE FOLLOWING INFORMATION FOR THE PROPOSED
 1ST FLOOR ADA BATHROOM COMPLIANT WITH FBC-2004 CHAPTER
 11 FLORIDA ACCESSIBILITY CODE.
  
 **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. 11-4.16.3
 HEIGHT. 17" TO 19".
 11-4.16.4 GRAB BARS. SEE FIGURE 29. GRAB BAR BEHIND W/C
 36" LONG.
 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44"
 HIGH.
 11-4.16.6 DISPENSERS. SEE FIGURE 29(B).
  
 **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL
 REQUIRED WITH THE FOLLOWING INFORMATION)
 11-4.19.2 HEIGHT AND CLEARANCES. MAXIMUM 34" TO RIM OR
 COUNTER. 29" A.F.F. TO THE BOTTOM OF THE APRON. (SEE
 FIGURE 31)
 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE
 32)
 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
 11-4.19.6 MIRRORS. 40" MAXIMUM A.F.F.
  
 ** 11-4.20 BATHTUBS (ELAVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION)
 11-4.20.2 FLOOR SPACE. (SEE FIGURE 33)
 11-4.20.3 SEAT. REQUIRED. (SEE FIGURE 33 & 34)
 11-4.20.4 GRAB BARS. REQUIRED. (SEE FIGURE 33 & 34)
 11-4.20.5 CONTROLS. (SEE FIGURE 34)
 11-4.20.6 SHOWER UNIT. SHOWER SPRAY UNIT WITH A HOSE
 MINIMUM 60" LONG USED BOTH AS A FIXED OR HAND HELD
 SHALL BE PROVIDED.
  
 **11-4.21 SHOWER STALLS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
 11-4.21.2 SIZE AND CLEARANCES. (SEE FIGURES 35(A) OR
 (B) AND FIGURES 57 (A) OR (B)
 11-4.21.3 SEAT. REQUIRED IN A 36" X 36" (17"-19" HIGH)
 11-4.21.4 GRAB BARS. REQUIRED (SEE FIGURE 37) 11-4.21.5
 CONTROLS. REQUIRED (SEE FIGURE 37) 11-4.21.7 CURBS. 36"
 X 36" MAXIMUM 1/2" CURB (NO CURB REQUIRED IN MINIMUM
 30" X 60" STALLS)
  
 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE
 SHALL BE 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR
 SPACE (PER 11-4.2.3)
  
 6. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
 NOTE: FLOOR PLAN SHEETS ARE NOT SIGNED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2008-07-28 Cont ID  
Sent By astelly Date 2008-07-28 Time 16:36 Rev Time 0.00
Received By astelly Date 2008-07-28 Time 16:36 Sent To  
Notes
2008-07-28 17:41:31AMY STELLY
 URBAN DESIGN
 822-1440
  
 1. PLEASE SHOW THE LOCATION OF ALL WINDOWS SO THAT
 ADEQUATE VENTILLATIONAND LIGHTING CAN BE VERIFIED.
  
 ARTICLE IV, SEC 18-95
 (B)EVERY HABITABLE ROOM SHALL HAVE AT LEAST ONE
 WINDOW OR SKYLIGHT FACING DIRECTLY TO THE OUTSIDE OR
 OTHER MEANS OF LIGHTING WHICH IS APPROVED AS ADEQUATE
 BY THE INSPECTOR. THE MINIMUM TOTAL WINDOW AREA FOR
 EVERY HABITABLE ROOM SHALL BE TEN PERCENT OF THE TOTAL
 FLOOR AREA OF SUCH ROOM; IF THE ONLY WINDOW IN A ROOM
 IS THE SKYLIGHT TYPE, THE MINIMUM TOTAL WINDOW AREA
 SHALL BE 15 PERCENT OF TOTAL FLOOR AREA OF SUCH ROOM,
 EXCEPT WHERE OTHER MEANS OF ARTIFICIAL LIGHTING ARE
 APPROVED.
  
 ARTICLE IV, SEC. 18-96.MINIMUM STANDARDS FOR
 VENTILATION.
 (A)EVERY HABITABLE ROOM SHALL HAVE AT LEAST ONE
 WINDOW OR SKYLIGHT OPENING DIRECTLY TO THE OUTDOORS
 WHICH CAN EASILY BE OPENED, OR SUCH OTHER DEVICE AS
 WILL ADEQUATELY VENTILATE THE ROOM. THE MINIMUM TOTAL
 OPENABLE WINDOW AREA IN EVERY HABITABLE ROOM SHALL BE
 EQUAL TO 45 PERCENT OF THE MINIMUM TOTAL WINDOW AREA
 REQUIRED IN SUBSECTION 18-95(B), EXCEPT WHERE THERE IS
 SUPPLIED SOME OTHER DEVICE AFFORDING ADEQUATE
 VENTILATION AND APPROVED BY THE BUILDING OFFICIAL. (B)
 WHEN WALLS OR OTHER PORTIONS OF STRUCTURES FACE A
 WINDOW AND ARE LOCATED LESS THAN THREE FEET FROM THE
 WINDOW AND EXTEND TO A LEVEL ABOVE THAT OF THE CEILING
 OF THE ROOM SO AS TO BE A LIGHT OBSTRUCTION FEATURE,
 SUCH WINDOW SHALL NOT BE INCLUDED AS CONTRIBUTING TO
 THE REQUIRED MINIMUM TOTAL WINDOW AREA.
 (C)EVERY BATHROOM SHALL HAVE VENTILATION EQUAL TO
 FOUR SQUARE FEET OR SUCH OTHER DEVICE AS WILL
 ADEQUATELY VENTILATE THE ROOM AND WHICH IS APPROVED BY
 THE BUILDING OFFICIAL.
  
 2. PLEASE SUBMIT A SITE PLAN SHOWING PARKING AND
 DUMPSTER LOCATION.
  
 3. THERE ARE ROOMING UNITS ON THE PLAN THAT ARE LESS
 THAN 70 SQUARE FEET. PLEASE CONSIDER ENLARGING THE
 UNITS.
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status N Date 2008-06-06 Cont ID  
Sent By choops Date 2008-06-06 Time 13:41 Rev Time 0.00
Received By choops Date 2008-06-06 Time 13:41 Sent To  
Notes
2008-06-06 13:41:27*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.