2008-05-30 14:23:19 | RESIDENTIAL (R3) RE-ROOFING BUILDING REVIEW CHECKLIST. |
| REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| |
| 1-VALUE OF STRUCTURE IS OVER $300,000, THEREFORE NEED |
| TO COMPLY WITH THE STRENGTHENINGRETROFIT REQUIREMENTS |
| REQUIRED BY FLORIDA STATES SEC. 553.844.CONTRACTOR |
| NEEDSTO SPECIFYHOW COMPLYING WITH THIS SECTION. SEE |
| ATTACHED COPY OF RULE 9B-3.0475. |
| STRUCTURAL WORK REQUIRES SEPARATE BUILDING PERMIT. |
| |
| 2- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| SEC. 713.13 FLORIDA STATUTES. |
| |
| 3- PROVIDE PRODUCT APPROVAL FOR POLYFOAM TO BE USED AS |
| REQUIRED BY DCA RULE 9B-72.SEE ROOF TILE PRODUCT |
| APPROVAL FOR TYPE OF POLYFOAM LISTED. |
| |
| 4- FLAT ROOF PRODUCT APPROVAL SUBMITTED: |
| A)THERE ARE TWO DIFFERENT BASE SHEET FASTENING |
| OPTIONSSHOWN ON SELECTED ASSEMBLY.CLEARLY MARK |
| WHICH FASTENING OPTION IS GOING TO BE USED FOR APPROVED |
| ASSEMBLY SHOWN ON SHEET 16 OF 18 OF NOA 07-0730.03 |
| SUBMITTED. |
| |
| B) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING |
| AT PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL |
| LIMITATION #7. |
| ***NOTE:FOR RAS 117 CALCULATIONS KEEP IN MIND THAT |
| HOUSE IS LOCATED ON EXPOSURE "C" AS REQUIRED BY SEC. |
| R301.2.1.4(3) OF 2004 FLORIDA RESIDENTIAL CODE. |
| |