2008-06-04 13:55:39 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| (F.S.). |
| |
| *** DENIED *** |
| 1) THE JOB ADDRESS 777 S. FLAGLER DR. NEEDS TO BE IN |
| THE TITLE BLOCK, PER WPB AMEND. 106.1.3. |
| |
| 2)THE LIEBERT A/C SYSTEM MODEL NUMBERS C/U |
| PFH037A-PL3 AND A/H MMD36E-POEDO LISTED ON THE A/C |
| EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE LIEBERT |
| WEB-SITE, PLEASE SUBMIT DETAILED MANUFACTURER'S |
| SPECIFICATION'S AND INSTALLATION INSTRUCTIONS, PER 2004 |
| FBC 106.3.5. |
| |
| 3) PLAN M2.1 SHOWS A OPEN RETURN AIR GRILL IN THE |
| NORTHEAST CORNER OF THE IT ROOM. PLEASE EXPLAIN OR |
| CORRECT, AS THIS IS A RATED ROOM AND DOES NOT HAVE A |
| OPEN PLENUM ABOVE THE CEILING, PER 2004 FBC/M 602. |
| |
| 4) PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR |
| PER-ENGINEERED CONDENSER STANDS, SEE FS 553.842(1) AND |
| FAC RULE 9B-72, 9B-72.005, AND FAC 9B-72.010(31)(G). |
| |
| **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG. |
| |
| *** PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED IN |
| WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND |
| SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B. |
| AMEND. 106.3. |
| |