Plan Review Details - Permit 08050806
Plan Review Stops For Permit 08050806
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-10-22 Cont ID  
Sent By btrobaug Date 2008-10-22 Time 13:41 Rev Time 0.00
Received By btrobaug Date 2008-10-22 Time 13:20 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-06-25 Cont ID  
Sent By btrobaug Date 2008-06-25 Time 13:53 Rev Time 0.00
Received By btrobaug Date 2008-06-25 Time 13:10 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-06-09 Cont ID  
Sent By btrobaug Date 2008-06-09 Time 12:37 Rev Time 0.00
Received By btrobaug Date 2008-06-09 Time 11:16 Sent To I
Notes
2008-06-09 12:37:34 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 645.10 DISCONNECTING MEANS
 A MEANS SHALL BE PROVIDED TO DISCONNECT POWER TO ALL
 ELECTRONIC EQUIPMENT IN THE INFORMATION TECHNOLOGY
 EQUIPMENT ROOM. THERE SHALL ALSO BE A SIMILAR MEANS TO
 DISCONNECT THE POWER TO ALL DEDICATED HVAC SYSTEMS
 SERVING THE ROOM AND CAUSE ALL REQUIRED FIRE/SMOKE
 DAMPERS TO CLOSE. THE CONTROL FOR THESE DISCONNECTING
 MEANS SHALL BE GROUPED AND IDENTIFIED AND SHALL BE
 READILY ACCESSIBLE AT THE PRINCIPAL EXIT DOORS. A
 SINGLE MEANS TO CONTROL BOTH THE ELECTRONIC EQUIPMENT
 AND HVAC SYSTEMS SHALL BE PERMITTED. WHERE A PUSHBUTTON
 IS USED AS A MEANS TO DISCONNECT POWER, PUSHING THE
 BUTTON IN SHALL DISCONNECT THE POWER** SHOW THE
 LOCATION OF THESE DISCONNECTS FOR COMPLIANCE WITH THIS
 ARTICLE..
  
 2} 645.4(2)A SEPARATE
 HEATING/VENTILATING/AIR-CONDITIONING (HVAC) SYSTEM IS
 PROVIDED THAT IS DEDICATED FOR INFORMATION TECHNOLOGY
 EQUIPMENT USE AND IS SEPARATED FROM OTHER AREAS OF
 OCCUPANCY. ANY HVAC SYSTEM THAT SERVES OTHER
 OCCUPANCIES SHALL BE PERMITTED TO ALSO SERVE THE
 INFORMATION TECHNOLOGY EQUIPMENT ROOM IF FIRE/SMOKE
 DAMPERS ARE PROVIDED AT THE POINT OF PENETRATION OF THE
 ROOM BOUNDARY. SUCH DAMPERS SHALL OPERATE ON ACTIVATION
 OF SMOKE DETECTORS AND ALSO BY OPERATION OF THE
 DISCONNECTING MEANS REQUIRED BY 645.10.
  
 3} PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE
 SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-10-20 Cont ID  
Sent By adarroug Date 2008-10-20 Time 09:09 Rev Time 0.00
Received By adarroug Date 2008-10-20 Time 09:09 Sent To E
Notes
2008-10-20 09:09:29TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-14 Cont ID  
Sent By adarroug Date 2008-10-14 Time 09:53 Rev Time 0.00
Received By adarroug Date 2008-10-14 Time 09:52 Sent To M
Notes
2008-10-14 09:53:18TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-20 Cont ID  
Sent By adarroug Date 2008-06-20 Time 08:36 Rev Time 0.00
Received By adarroug Date 2008-06-20 Time 08:36 Sent To M
Notes
2008-06-20 08:36:59TO "TGORDON" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-09 Cont ID  
Sent By btrobaug Date 2008-06-09 Time 12:38 Rev Time 0.00
Received By btrobaug Date 2008-06-04 Time 11:20 Sent To PC
Notes
2008-06-04 11:23:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-10-21 Cont ID  
Sent By tgordon Date 2008-10-21 Time 11:41 Rev Time 0.30
Received By tgordon Date 2008-10-21 Time 11:41 Sent To E
Notes
2008-10-21 11:41:59REVISION TO MECH. PLAN M0.1.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-10-21 Cont ID  
Sent By tgordon Date 2008-10-21 Time 11:05 Rev Time 0.45
Received By tgordon Date 2008-10-21 Time 11:05 Sent To  
Notes
2008-10-21 11:07:26REVISION TO MECH. PLAN M2.1.
  
 *** PROVISO ***
 1) PROVIDE ENGINEERING FOR A/C CONDENSER STAND IF NEW
 OR ALTERED AT TIME OF INSPECTION, PER 2004 FBC 1609.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-06-20 Cont ID  
Sent By tgordon Date 2008-06-20 Time 15:14 Rev Time 0.20
Received By tgordon Date 2008-06-20 Time 15:14 Sent To E
Notes
2008-06-20 15:15:55*** PROVISO ***
 1) PROVIDE ENGINEERING FOR A/C CONDENSER STAND AT TIME
 OF INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-06-04 Cont ID  
Sent By tgordon Date 2008-06-04 Time 13:33 Rev Time 0.45
Received By tgordon Date 2008-06-04 Time 13:33 Sent To E
Notes
2008-06-04 13:55:39PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE JOB ADDRESS 777 S. FLAGLER DR. NEEDS TO BE IN
 THE TITLE BLOCK, PER WPB AMEND. 106.1.3.
  
 2)THE LIEBERT A/C SYSTEM MODEL NUMBERS C/U
 PFH037A-PL3 AND A/H MMD36E-POEDO LISTED ON THE A/C
 EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE LIEBERT
 WEB-SITE, PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS, PER 2004
 FBC 106.3.5.
  
 3) PLAN M2.1 SHOWS A OPEN RETURN AIR GRILL IN THE
 NORTHEAST CORNER OF THE IT ROOM. PLEASE EXPLAIN OR
 CORRECT, AS THIS IS A RATED ROOM AND DOES NOT HAVE A
 OPEN PLENUM ABOVE THE CEILING, PER 2004 FBC/M 602.
  
 4) PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR
 PER-ENGINEERED CONDENSER STANDS, SEE FS 553.842(1) AND
 FAC RULE 9B-72, 9B-72.005, AND FAC 9B-72.010(31)(G).
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 *** PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND
 SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B.
 AMEND. 106.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]