Plan Review Details - Permit 08050784
Plan Review Stops For Permit 08050784
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-10-09 Cont ID  
Sent By jwitmer Date 2008-10-09 Time 14:33 Rev Time 0.33
Received By jwitmer Date 2008-10-09 Time 14:33 Sent To  
Notes
2008-10-09 14:33:30BUILDING PROVISO: FBC BUILDING 3110.1.2 / CITY OF WPB
 CODE OF ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED
 IN AN "A" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE MAY
 BE REQUIRED. DEPENDING ON THE TIMING OF THE BUILDING
 C.O. IF THE GENERATORS ARE GOING TO RECEIVE THEIR CO AT
 THE SAME TIME AS THE BUILDING A FLOOD ZONE CERTIFICATE
 WILL BE REQUIRED. IF THE GENERATORS ARE GOING TO BE
 FINAL AFTER THE BUILDING C.O. THEN EITHER A SURVEY WITH
 ELEVATION HEIGHT OR DESIGNER OF RECORD PROVIDING SITE
 PLAN WITH ASSOCIATED SLAB ELEVATION. THE MINIMUM FLOOD
 ELEVATION THE SLAB MAY BE SET AT IS 13'-6" IN A "A-9"
 FLOOD ZONE, THIS MAY BE ACCOMPLISHED AT TIME OF THE
 FINAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-08-12 Cont ID  
Sent By jwitmer Date 2008-08-12 Time 07:30 Rev Time 0.55
Received By jwitmer Date 2008-08-12 Time 07:30 Sent To  
Notes
2008-08-12 07:32:25BUILDING PLAN REVIEW
 PERMIT: 08050784
 ADD: 1641 WORTHINGTON RD
 CONT: HEDRICK BROTHERS
 TEL: (561)662-0785
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 08-12-08
 2NDREVIEW
 ACTION: DENIED
  
 1)COMPLIED.
  
 2) NOTE, BUILDING PROVISO:FBC BUILDING 3110.1.2 /
 CITY OF WPB CODE OF ORDINANCES SECTION 94-546.
 STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD
 ELEVATION CERTIFICATE MAY BE REQUIRED. DEPENDING ON THE
 TIMING OF THE BUILDING C.O. IF THE GENERATORS ARE GOING
 TO BE CO'ED AT THE SAME TIME AS THE BUILDING A FLOOD
 ZONE CERTIFICATE WILL BE REQUIRED. IF THE GENERATORS
 ARE GOING TO BE FINALED AFTER THE BUILDING C.O. THEN
 EITHER A SURVEY WITH ELEVATION HEIGTH OR DESIGNER OF
 RECORD PROVIDING SITE PLAN WITH ASSCIATED SLAB
 ELEVATION. THE MINIMUM FLOOD ELEVATION THE SLAB MAY BE
 SET AT IS 13'-6" IN A "A-9" FLOOD ZONE, THIS MAY BE
 ACCOMPLISHED AT TIME OF THE FINAL.
  
 3) 2ND REQUEST, THERE ARE NO ARCHITECTURAL OR
 STRUCTURAL PLANS INDICATING THE SIZE OFANCHOR FROM
 THE EQUIPMENT PAD TO THE GENERATOR FRAME TO RESIST THE
 MOMENT OF OVERTURNING. 1609. 1.3, ANCHORAGE AGAINST
 MOMENT OF OVERTURNING, UPLIFT AND SLIDING.
  
 4) COMPLIED.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-08-12 Cont ID  
Sent By jwitmer Date 2008-08-11 Time 16:57 Rev Time 1.33
Received By jwitmer Date 2008-08-11 Time 16:57 Sent To PC
Notes
2008-08-11 16:58:15BUILDING PLAN REVIEW
 PERMIT: 08050784
 ADD: 1641 WORTHINGTON RD
 CONT: HEDRICK BROTHERS
 TEL: (561)662-0785
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-16 Cont ID  
Sent By jwitmer Date 2008-06-16 Time 16:14 Rev Time 0.77
Received By jwitmer Date 2008-06-16 Time 16:14 Sent To  
Notes
2008-06-16 16:15:01BUILDING PLAN REVIEW
 PERMIT: 08050784
 ADD: 1641 WORTHINGTON RD
 CONT: HEDRICK BROTHERS
 TEL: (561)662-0785
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) NOTE, BUILDING PROVISO:FBC BUILDING 3110.1.2 /
 CITY OF WPB CODE OF ORDINANCES SECTION 94-546.
 STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD
 ELEVATION CERTIFICATE MAY BE REQUIRED. DEPENDING ON THE
 TIMING OF THE BUILDING C.O. IF THE GENERATORS ARE GOING
 TO BE CO'ED AT THE SAME TIME AS THE BUILDING A FLOOD
 ZONE CERTIFICATE WILL BE REQUIRED. IF THE GENERATORS
 ARE GOING TO BE FINALED AFTER THE BUILDING C.O. THEN
 EITHER A SURVEY WITH ELEVATION HEIGTH OR DESIGNER OF
 RECORD PROVIDING SITE PLAN WITH ASSCIATED SLAB
 ELEVATION. THE MINIMUM FLOOD ELEVATION THE SLAB MAY BE
 SET AT IS 13'-6" IN A "A-9" FLOOD ZONE, THIS MAY BE
 ACCOMPLISHED AT TIME OF THE FINAL.
  
 3) THERE ARE NO ARCHITECTURAL OR STRUCTURAL PLANS
 INDICATING THE SIZE OFEQUIPMENT PADS, TYPE OF
 COMPOSITION, AND CONNECTION FROM THE EQUIPMENT PAD TO
 THE GENERATOR FRAME TO RESIST THE MOMENT OF
 OVERTURNING. 1609. 1.3, ANCHORAGE AGAINST MOMENT OF
 OVERTURNING, UPLIFT AND SLIDING.
  
 4) MISSING THE WIND DESIGN DATA: 1603.1.4 WIND DESIGN
 DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1.BASIC WIND SPEED (3-SECOND GUST), MILES PER
 HOUR (KM/HR).
 2.WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3.
 WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4.THE APPLICABLE ENCLOSURE CLASSIFICATIONS
 AND, IF DESIGNING WITH ASCE 7, INTERNAL PRESSURE
 COEFFICIENT.
 5.COMPONENTS AND CLADDING. THE DESIGN WIND
 PRESSURES IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE
 SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS
 NOT SPECIFICALLY DESIGNED BY THE
 REGISTERED DESIGN PROFESSIONAL.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-10-10 Cont ID  
Sent By dpalmer Date 2008-10-10 Time 16:52 Rev Time 0.00
Received By dpalmer Date 2008-10-10 Time 16:52 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-08-12 Cont ID  
Sent By dpalmer Date 2008-08-12 Time 14:59 Rev Time 0.00
Received By dpalmer Date 2008-08-12 Time 14:59 Sent To  
Notes
2008-08-12 15:00:00** DENIED PLANS.**
  
 ** PLANS ARE COMING BACK FOR OTHER CORRECTIONS.
  
  
 1) NOTE: PLANS/RISER NEED TO BE LABELED WITH ALL NEW
 SIGNAGE FOR DISCONNECTING MEANS OF NORMAL AND EMERGENCY
 POWER.
 230.2E, 702.8
  
 2) NOTE: PLANS CALL FOR A SEPARATELY DERIVED GENERATOR
 YET THE SPECS/MANUFACTURES CUT SHEETS/ BILL OF
 MATERIALS INDICATES TRANSFER SWITCH AS 3-POLE. IT WAS
 NOTED BY ENGINEER OF RECORD HOWEVER NO NEW SPECS WERE
 SUBMITTED.
 PLEASE SEE SHEET IN REAR OF SUBMITTAL PACKAGE WHICH
 STATES THE ISOLATORS ARE N/A. (NOT APPLICABLE). PLEASE
 SEE NFPA-110 CHAPTER 7.
  
 3) NOTE: PLEASE SEE E.01 AS THE 2002 NFPA-70 (NEC) IS
 QUOTED. THIS CAN BE REDLINED WITHOUT CHANGING SHEET.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-06-20 Cont ID  
Sent By dpalmer Date 2008-06-20 Time 16:08 Rev Time 0.00
Received By dpalmer Date 2008-06-20 Time 16:08 Sent To  
Notes
2008-06-20 16:09:07** DENIEDREVIEW **
  
  
 1) NOTE:
  
 2) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS
 FOR THE NEW PROPOSED TRANSFER SWITCH EQUIPMENT. 110.3,
 90.7 AS PROPOSED SYSTEMS AND ATS DOES NOT SHOW THESE AS
 FOUR UNITS A FULL LIST OF COMMENTS CAN NOT BE GIVEN.
 PLEASE SEE 250.50,250.32, 250.20 ETC PLEASE COMPLETE
 RISER SHOWING BONDING ETC FOR SDS.
 FBC 106.1.2
  
 3) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE NEW PROPOSED GENERATORS. 110.3,90.7
 PLEASE SEE COMMENTS FROM OTHER TRADES FOR INFORMATION
 REQUIRED FOR THE PRIME MOVER OF THE GENERATOR.
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 4) NOTE: PLEASE SEE THE RISER AS THIS IS MISSING THE
 REQUIRED EQUIPMENT GROUNDING CONDUCTORS FROM THE
 GENERATOR TO THE BUILDING. 250.32
  
 5) NOTE: PLEASE PROVIDE VOLTAGE DROP CALCULATIONS PER
 13-413.1ABC.1, .1.1 AND .1.2
  
 6) NOTE: PLEASE SUBMIT SHOW THE SIZES OF THE PANELS,
 CONDUITS AND CONDUCTORS FROM ATS DEVICES TO EACH PANEL
 H1, H2, H3, H4.L
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-10-10 Cont ID  
Sent By mwennerg Date 2008-10-10 Time 16:23 Rev Time 0.00
Received By mwennerg Date 2008-10-10 Time 16:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-08-21 Cont ID  
Sent By mwennerg Date 2008-08-21 Time 13:45 Rev Time 0.00
Received By mwennerg Date 2008-08-21 Time 13:45 Sent To  
Notes
2008-08-21 13:52:00***DENIED***
  
 1) ADD NFPA 110, STANDARD FOR EMERGENCY POWER AND
 STANDBY SYSTEMS TO LIST OF CODES AND STANDARDS ON SHEET
 E0.1. RESPONSE LETTER INDICATES REVISED SHEET BUT CODE
 REFERENCE WAS NOT FOUND.
  
 2) RESPONSE LETTER INDICATES THAT COMMENT WAS ADDRESSED
 BY KAMM CONSULTING. KAMM LETTER DOES NOT ADDRESS THIS
 ISSUE.
  
 3) OK
  
 4) FLOOR PLAN DOES NOT CLEARLY ILLUSTRATE THE LOCATION
 OF BUILDING OPENINGS WITH REGARD TO EXHAUST TERMINUS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-06-30 Cont ID  
Sent By mwennerg Date 2008-06-30 Time 13:58 Rev Time 0.00
Received By mwennerg Date 2008-06-30 Time 13:58 Sent To  
Notes
2008-06-30 14:02:25***DENIED***
  
 1) ADD NFPA 110, STANDARD FOR EMERGENCY POWER AND
 STANDBY SYSTEMS TO LIST OF CODES AND STANDARDS ON SHEET
 E0.1.
  
 2) PLEASE IDENTIFY WHAT BUILDING SYSTEMS AND LIFE
 SAFETY EQUIPMENT WILL BE CONNECTED TO GENERATORS.
  
 3) SUBMIT MANUFACTURER SPECIFICATION SHEETS FOR
 GENERATORS AND ASSOCIATED EQUIPMENT.
  
 4) CLEARLY ILLUSTRATE LOCATION OF BUILDING OPENINGS AND
 EXIT DISCHARGE WITH RELATION TO EXHAUST TERMINATION.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FUEL DIESEL GENERATOR
Rev No 3 Status P Date 2008-10-03 Cont ID  
Sent By tgordon Date 2008-10-03 Time 14:13 Rev Time 0.30
Received By tgordon Date 2008-10-03 Time 14:13 Sent To  
Notes
***NONE***

Review Stop FUEL DIESEL GENERATOR
Rev No 2 Status F Date 2008-08-11 Cont ID  
Sent By tgordon Date 2008-08-11 Time 11:12 Rev Time 0.30
Received By tgordon Date 2008-08-11 Time 11:12 Sent To  
Notes
2008-08-11 11:23:15PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLANS PAGE E5.1 GENERATOR SPECIFICATIONS LINE #4
 STATES THE FUEL TANK IS 500 GALLONS, THE BILL OF
 MATERIAL SUBMITTAL STATES THE FUEL TANK IS 1,215
 GALLONS. THE TWO MUST COINSIDE, PLEASE CORRECT.
  
 2) AS NOTED IN LAST REVIEW 6-23-08. SHOW ON PLAN SP-1,
 TYPE OF FUEL, FUEL TANK CAPACITY, AND LOCATION OF FUEL
 STORAGE TANK FOR GENERATOR, PER NFPA 30 4.3.2.1.
  
 3) AFTER CORRECTING PLANS THEY NEED TO BE SUBMITTED TO
 PALM BEACH COUNTY DEPT. OF ENVIRONMENTAL RESOURCES
 MANAGEMENT (D.E.R.M.) FOR REVIEW AND STAMPING, YOU MAY
 CALL (561) 233-2400 FOR MORE INFORMATION. THEN SUBMIT
 TO CITY OF W.P.B. BUILDING DEPT..
  
 FUEL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status F Date 2008-08-11 Cont ID  
Sent By tgordon Date 2008-06-23 Time 11:08 Rev Time 0.20
Received By tgordon Date 2008-06-23 Time 11:08 Sent To  
Notes
2008-08-11 11:11:04PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SUBMIT A SITE PLAN SHOWING PROPERTY LINES GENERATOR
 LOCATION, AND BUILDING OPENINGS, PER NFPA 37.
  
 2) SHOW ON PLANS TYPE OF FUEL, TANK CAPACITY, AND
 LOCATION OF FUEL STORAGE TANK FOR GENERATOR, PER NFPA
 30 4.3.2.1.
  
 3) PLEASE SUBMIT MANUFACTURER'S SPECIFICATION'S AND
 INSTALLATION INSTRUCTIONS.
  
 FUEL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2008-07-02 Cont ID  
Sent By mperson Date 2008-07-02 Time 15:58 Rev Time 0.00
Received By mperson Date 2008-07-02 Time 15:58 Sent To I
Notes
2008-07-02 16:01:51NOTE: SHEET E5.2 GENERATOR SPECIFICATIONS INDICATES
 THAT THE GENERATOR IS DIESEL POWERED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-02 Cont ID  
Sent By adarroug Date 2008-10-02 Time 11:31 Rev Time 0.00
Received By adarroug Date 2008-10-02 Time 11:31 Sent To  
Notes
2008-10-02 11:34:05TO "COMM" BD#3

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-05 Cont ID  
Sent By adarroug Date 2008-08-05 Time 15:56 Rev Time 0.00
Received By adarroug Date 2008-08-05 Time 15:56 Sent To  
Notes
2008-08-05 15:59:35TO "COMM" BD#7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-02 Cont ID  
Sent By mperson Date 2008-07-02 Time 16:02 Rev Time 0.00
Received By mperson Date 2008-05-30 Time 16:42 Sent To PC
Notes
2008-05-30 16:45:29TO "COMM" BD#52

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-10-03 Cont ID  
Sent By tgordon Date 2008-10-03 Time 14:13 Rev Time 0.30
Received By tgordon Date 2008-10-03 Time 14:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-08-11 Cont ID  
Sent By tgordon Date 2008-08-11 Time 11:11 Rev Time 0.20
Received By tgordon Date 2008-08-11 Time 11:11 Sent To  
Notes
2008-08-11 11:12:32SEE FUEL REVIEW NOTES.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-06-23 Cont ID  
Sent By tgordon Date 2008-06-23 Time 08:02 Rev Time 0.30
Received By tgordon Date 2008-06-23 Time 08:02 Sent To  
Notes
2008-06-23 08:12:33PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SUBMIT A SITE PLAN SHOWING PROPERTY LINES GENERATOR
 LOCATION, AND BUILDING OPENINGS, PER NFPA 37.
  
 2) SHOW ON PLANS TYPE OF FUEL, TANK CAPACITY, AND
 LOCATION OF FUEL STORAGE TANK FOR GENERATOR, PER NFPA
 30 4.3.2.1.
  
 3) PLEASE SUBMIT MANUFACTURER'S SPECIFICATION'S AND
 INSTALLATION INSTRUCTIONS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2008-10-07 Cont ID  
Sent By jroach Date 2008-10-07 Time 20:40 Rev Time 0.00
Received By jroach Date 2008-10-07 Time 20:40 Sent To  
Notes
2008-10-07 20:40:38***PROVISO***
  
 CREEPING FIG VINE SHALL BE INSTALLED ON THE EXTERIOR OF
 THE SCREEN WALL PRIOR TO FINAL INSPECTION.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT 822-1435.

Review Stop Z ZONING
Rev No 2 Status P Date 2008-08-20 Cont ID  
Sent By jroach Date 2008-08-20 Time 09:31 Rev Time 0.00
Received By jroach Date 2008-08-20 Time 09:31 Sent To  
Notes
2008-08-20 09:31:21***PROVISO***
  
 CREEPING FIG VINE SHALL BE INSTALLED ON THE EXTERIOR OF
 THE SCREEN WALL PRIOR TO FINAL INSPECTION.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-06-04 Cont ID  
Sent By jroach Date 2008-06-04 Time 09:22 Rev Time 0.00
Received By jroach Date 2008-06-04 Time 09:22 Sent To  
Notes
2008-06-04 09:26:48***FAILED***
  
 1) TWO (2) COPIES OF A CURRENT AND ACCURATE SURVEY
 SHALL BE PROVIDED.
  
 2) TWO (2) COPIES OF A SITE PLAN SHOWING THE LOCATION
 OF THE GENERATOR ON THE ENTIRE PROPERTY SHALL BE
 PROVIDED.SETBACK DIMENSIONS SHALL BE PROVIDED FROM
 THE GENERATOR TO THE ADJACENT PROPERTY LINES.
  
 3) PLEASE NOTE WHETHER OR NOT THE SCREEN WALL IS
 EXISTING.IF THE WALL IS NOT EXISTING, THEN DETAILS
 WILL NEED TO BE PROVIDED OF THE PROPOSED WALL.
  
 4) PLEASE NOTE THE HEIGHT OF THE SCREEN WALL.
  
 5) PLEASE PROVIDE AN ELEVATION OF THE GENERATOR
 INDICATING THE OVERALL HEIGHT OF THE GENERATOR.THE
 SCREEN WALL SHALL COMPLETELY SCREEN THE GENERATOR FROM
 VIEW.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.