Plan Review Stops For Permit 08050784 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2008-10-09 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-10-09 |
Time |
14:33 |
Rev Time |
0.33 |
Received By |
jwitmer |
Date |
2008-10-09 |
Time |
14:33 |
Sent To |
|
|
Notes |
2008-10-09 14:33:30 | BUILDING PROVISO: FBC BUILDING 3110.1.2 / CITY OF WPB | | CODE OF ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED | | IN AN "A" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE MAY | | BE REQUIRED. DEPENDING ON THE TIMING OF THE BUILDING | | C.O. IF THE GENERATORS ARE GOING TO RECEIVE THEIR CO AT | | THE SAME TIME AS THE BUILDING A FLOOD ZONE CERTIFICATE | | WILL BE REQUIRED. IF THE GENERATORS ARE GOING TO BE | | FINAL AFTER THE BUILDING C.O. THEN EITHER A SURVEY WITH | | ELEVATION HEIGHT OR DESIGNER OF RECORD PROVIDING SITE | | PLAN WITH ASSOCIATED SLAB ELEVATION. THE MINIMUM FLOOD | | ELEVATION THE SLAB MAY BE SET AT IS 13'-6" IN A "A-9" | | FLOOD ZONE, THIS MAY BE ACCOMPLISHED AT TIME OF THE | | FINAL. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2008-08-12 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-08-12 |
Time |
07:30 |
Rev Time |
0.55 |
Received By |
jwitmer |
Date |
2008-08-12 |
Time |
07:30 |
Sent To |
|
|
Notes |
2008-08-12 07:32:25 | BUILDING PLAN REVIEW | | PERMIT: 08050784 | | ADD: 1641 WORTHINGTON RD | | CONT: HEDRICK BROTHERS | | TEL: (561)662-0785 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | 08-12-08 | | 2NDREVIEW | | ACTION: DENIED | | | | 1)COMPLIED. | | | | 2) NOTE, BUILDING PROVISO:FBC BUILDING 3110.1.2 / | | CITY OF WPB CODE OF ORDINANCES SECTION 94-546. | | STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD | | ELEVATION CERTIFICATE MAY BE REQUIRED. DEPENDING ON THE | | TIMING OF THE BUILDING C.O. IF THE GENERATORS ARE GOING | | TO BE CO'ED AT THE SAME TIME AS THE BUILDING A FLOOD | | ZONE CERTIFICATE WILL BE REQUIRED. IF THE GENERATORS | | ARE GOING TO BE FINALED AFTER THE BUILDING C.O. THEN | | EITHER A SURVEY WITH ELEVATION HEIGTH OR DESIGNER OF | | RECORD PROVIDING SITE PLAN WITH ASSCIATED SLAB | | ELEVATION. THE MINIMUM FLOOD ELEVATION THE SLAB MAY BE | | SET AT IS 13'-6" IN A "A-9" FLOOD ZONE, THIS MAY BE | | ACCOMPLISHED AT TIME OF THE FINAL. | | | | 3) 2ND REQUEST, THERE ARE NO ARCHITECTURAL OR | | STRUCTURAL PLANS INDICATING THE SIZE OFANCHOR FROM | | THE EQUIPMENT PAD TO THE GENERATOR FRAME TO RESIST THE | | MOMENT OF OVERTURNING. 1609. 1.3, ANCHORAGE AGAINST | | MOMENT OF OVERTURNING, UPLIFT AND SLIDING. | | | | 4) COMPLIED. | | | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2008-08-12 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-08-11 |
Time |
16:57 |
Rev Time |
1.33 |
Received By |
jwitmer |
Date |
2008-08-11 |
Time |
16:57 |
Sent To |
PC |
|
Notes |
2008-08-11 16:58:15 | BUILDING PLAN REVIEW | | PERMIT: 08050784 | | ADD: 1641 WORTHINGTON RD | | CONT: HEDRICK BROTHERS | | TEL: (561)662-0785 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | 2NDREVIEW |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2008-06-16 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-06-16 |
Time |
16:14 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2008-06-16 |
Time |
16:14 |
Sent To |
|
|
Notes |
2008-06-16 16:15:01 | BUILDING PLAN REVIEW | | PERMIT: 08050784 | | ADD: 1641 WORTHINGTON RD | | CONT: HEDRICK BROTHERS | | TEL: (561)662-0785 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | 1STREVIEW | | ACTION: DENIED | | | | 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, | | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR | | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL | | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A | | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN | | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED | | FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS | | WEST PALM BEACH ADMINISTRATIVE CODE. | | | | 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE | | CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN | | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO | | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO | | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION | | SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE | | CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR | | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | DETERMINED BY THE BUILDING OFFICIAL. | | | | 1D ) INFORMATIONAL FL S S 713.13NOTICE OF | | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. | | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS | | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & | | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | INSPECTION. | | | | 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST | | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO | | THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS. | | | | 2) NOTE, BUILDING PROVISO:FBC BUILDING 3110.1.2 / | | CITY OF WPB CODE OF ORDINANCES SECTION 94-546. | | STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD | | ELEVATION CERTIFICATE MAY BE REQUIRED. DEPENDING ON THE | | TIMING OF THE BUILDING C.O. IF THE GENERATORS ARE GOING | | TO BE CO'ED AT THE SAME TIME AS THE BUILDING A FLOOD | | ZONE CERTIFICATE WILL BE REQUIRED. IF THE GENERATORS | | ARE GOING TO BE FINALED AFTER THE BUILDING C.O. THEN | | EITHER A SURVEY WITH ELEVATION HEIGTH OR DESIGNER OF | | RECORD PROVIDING SITE PLAN WITH ASSCIATED SLAB | | ELEVATION. THE MINIMUM FLOOD ELEVATION THE SLAB MAY BE | | SET AT IS 13'-6" IN A "A-9" FLOOD ZONE, THIS MAY BE | | ACCOMPLISHED AT TIME OF THE FINAL. | | | | 3) THERE ARE NO ARCHITECTURAL OR STRUCTURAL PLANS | | INDICATING THE SIZE OFEQUIPMENT PADS, TYPE OF | | COMPOSITION, AND CONNECTION FROM THE EQUIPMENT PAD TO | | THE GENERATOR FRAME TO RESIST THE MOMENT OF | | OVERTURNING. 1609. 1.3, ANCHORAGE AGAINST MOMENT OF | | OVERTURNING, UPLIFT AND SLIDING. | | | | 4) MISSING THE WIND DESIGN DATA: 1603.1.4 WIND DESIGN | | DATA. | | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL | | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE | | DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE | | BUILDING: | | 1.BASIC WIND SPEED (3-SECOND GUST), MILES PER | | HOUR (KM/HR). | | 2.WIND IMPORTANCE FACTOR, I W , AND BUILDING | | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 | | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3. | | WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS | | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND | | DIRECTION SHALL BE INDICATED. | | 4.THE APPLICABLE ENCLOSURE CLASSIFICATIONS | | AND, IF DESIGNING WITH ASCE 7, INTERNAL PRESSURE | | COEFFICIENT. | | 5.COMPONENTS AND CLADDING. THE DESIGN WIND | | PRESSURES IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE | | SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS | | NOT SPECIFICALLY DESIGNED BY THE | | REGISTERED DESIGN PROFESSIONAL. | | | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2008-10-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-10-10 |
Time |
16:52 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-10-10 |
Time |
16:52 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2008-08-12 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-08-12 |
Time |
14:59 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-08-12 |
Time |
14:59 |
Sent To |
|
|
Notes |
2008-08-12 15:00:00 | ** DENIED PLANS.** | | | | ** PLANS ARE COMING BACK FOR OTHER CORRECTIONS. | | | | | | 1) NOTE: PLANS/RISER NEED TO BE LABELED WITH ALL NEW | | SIGNAGE FOR DISCONNECTING MEANS OF NORMAL AND EMERGENCY | | POWER. | | 230.2E, 702.8 | | | | 2) NOTE: PLANS CALL FOR A SEPARATELY DERIVED GENERATOR | | YET THE SPECS/MANUFACTURES CUT SHEETS/ BILL OF | | MATERIALS INDICATES TRANSFER SWITCH AS 3-POLE. IT WAS | | NOTED BY ENGINEER OF RECORD HOWEVER NO NEW SPECS WERE | | SUBMITTED. | | PLEASE SEE SHEET IN REAR OF SUBMITTAL PACKAGE WHICH | | STATES THE ISOLATORS ARE N/A. (NOT APPLICABLE). PLEASE | | SEE NFPA-110 CHAPTER 7. | | | | 3) NOTE: PLEASE SEE E.01 AS THE 2002 NFPA-70 (NEC) IS | | QUOTED. THIS CAN BE REDLINED WITHOUT CHANGING SHEET. | | | | | | | | **IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2008-06-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-06-20 |
Time |
16:08 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-06-20 |
Time |
16:08 |
Sent To |
|
|
Notes |
2008-06-20 16:09:07 | ** DENIEDREVIEW ** | | | | | | 1) NOTE: | | | | 2) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS | | FOR THE NEW PROPOSED TRANSFER SWITCH EQUIPMENT. 110.3, | | 90.7 AS PROPOSED SYSTEMS AND ATS DOES NOT SHOW THESE AS | | FOUR UNITS A FULL LIST OF COMMENTS CAN NOT BE GIVEN. | | PLEASE SEE 250.50,250.32, 250.20 ETC PLEASE COMPLETE | | RISER SHOWING BONDING ETC FOR SDS. | | FBC 106.1.2 | | | | 3) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT | | SHEETS FOR THE NEW PROPOSED GENERATORS. 110.3,90.7 | | PLEASE SEE COMMENTS FROM OTHER TRADES FOR INFORMATION | | REQUIRED FOR THE PRIME MOVER OF THE GENERATOR. | | FBC 106.1.2 FOR ADDITIONAL INFORMATION. | | | | 4) NOTE: PLEASE SEE THE RISER AS THIS IS MISSING THE | | REQUIRED EQUIPMENT GROUNDING CONDUCTORS FROM THE | | GENERATOR TO THE BUILDING. 250.32 | | | | 5) NOTE: PLEASE PROVIDE VOLTAGE DROP CALCULATIONS PER | | 13-413.1ABC.1, .1.1 AND .1.2 | | | | 6) NOTE: PLEASE SUBMIT SHOW THE SIZES OF THE PANELS, | | CONDUITS AND CONDUCTORS FROM ATS DEVICES TO EACH PANEL | | H1, H2, H3, H4.L | | | | ** IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF | | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT | | HESITATE IN CONTACTING THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2008-10-10 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-10-10 |
Time |
16:23 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-10-10 |
Time |
16:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2008-08-21 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-08-21 |
Time |
13:45 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-08-21 |
Time |
13:45 |
Sent To |
|
|
Notes |
2008-08-21 13:52:00 | ***DENIED*** | | | | 1) ADD NFPA 110, STANDARD FOR EMERGENCY POWER AND | | STANDBY SYSTEMS TO LIST OF CODES AND STANDARDS ON SHEET | | E0.1. RESPONSE LETTER INDICATES REVISED SHEET BUT CODE | | REFERENCE WAS NOT FOUND. | | | | 2) RESPONSE LETTER INDICATES THAT COMMENT WAS ADDRESSED | | BY KAMM CONSULTING. KAMM LETTER DOES NOT ADDRESS THIS | | ISSUE. | | | | 3) OK | | | | 4) FLOOR PLAN DOES NOT CLEARLY ILLUSTRATE THE LOCATION | | OF BUILDING OPENINGS WITH REGARD TO EXHAUST TERMINUS. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2008-06-30 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-06-30 |
Time |
13:58 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-06-30 |
Time |
13:58 |
Sent To |
|
|
Notes |
2008-06-30 14:02:25 | ***DENIED*** | | | | 1) ADD NFPA 110, STANDARD FOR EMERGENCY POWER AND | | STANDBY SYSTEMS TO LIST OF CODES AND STANDARDS ON SHEET | | E0.1. | | | | 2) PLEASE IDENTIFY WHAT BUILDING SYSTEMS AND LIFE | | SAFETY EQUIPMENT WILL BE CONNECTED TO GENERATORS. | | | | 3) SUBMIT MANUFACTURER SPECIFICATION SHEETS FOR | | GENERATORS AND ASSOCIATED EQUIPMENT. | | | | 4) CLEARLY ILLUSTRATE LOCATION OF BUILDING OPENINGS AND | | EXIT DISCHARGE WITH RELATION TO EXHAUST TERMINATION. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|
|
Review Stop |
FUEL |
DIESEL GENERATOR |
Rev No |
3 |
Status |
P |
Date |
2008-10-03 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-10-03 |
Time |
14:13 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2008-10-03 |
Time |
14:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FUEL |
DIESEL GENERATOR |
Rev No |
2 |
Status |
F |
Date |
2008-08-11 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-08-11 |
Time |
11:12 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2008-08-11 |
Time |
11:12 |
Sent To |
|
|
Notes |
2008-08-11 11:23:15 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) PLANS PAGE E5.1 GENERATOR SPECIFICATIONS LINE #4 | | STATES THE FUEL TANK IS 500 GALLONS, THE BILL OF | | MATERIAL SUBMITTAL STATES THE FUEL TANK IS 1,215 | | GALLONS. THE TWO MUST COINSIDE, PLEASE CORRECT. | | | | 2) AS NOTED IN LAST REVIEW 6-23-08. SHOW ON PLAN SP-1, | | TYPE OF FUEL, FUEL TANK CAPACITY, AND LOCATION OF FUEL | | STORAGE TANK FOR GENERATOR, PER NFPA 30 4.3.2.1. | | | | 3) AFTER CORRECTING PLANS THEY NEED TO BE SUBMITTED TO | | PALM BEACH COUNTY DEPT. OF ENVIRONMENTAL RESOURCES | | MANAGEMENT (D.E.R.M.) FOR REVIEW AND STAMPING, YOU MAY | | CALL (561) 233-2400 FOR MORE INFORMATION. THEN SUBMIT | | TO CITY OF W.P.B. BUILDING DEPT.. | | | | FUEL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
FUEL |
DIESEL GENERATOR |
Rev No |
1 |
Status |
F |
Date |
2008-08-11 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-06-23 |
Time |
11:08 |
Rev Time |
0.20 |
Received By |
tgordon |
Date |
2008-06-23 |
Time |
11:08 |
Sent To |
|
|
Notes |
2008-08-11 11:11:04 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) SUBMIT A SITE PLAN SHOWING PROPERTY LINES GENERATOR | | LOCATION, AND BUILDING OPENINGS, PER NFPA 37. | | | | 2) SHOW ON PLANS TYPE OF FUEL, TANK CAPACITY, AND | | LOCATION OF FUEL STORAGE TANK FOR GENERATOR, PER NFPA | | 30 4.3.2.1. | | | | 3) PLEASE SUBMIT MANUFACTURER'S SPECIFICATION'S AND | | INSTALLATION INSTRUCTIONS. | | | | FUEL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2008-07-02 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-07-02 |
Time |
15:58 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2008-07-02 |
Time |
15:58 |
Sent To |
I |
|
Notes |
2008-07-02 16:01:51 | NOTE: SHEET E5.2 GENERATOR SPECIFICATIONS INDICATES | | THAT THE GENERATOR IS DIESEL POWERED. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2008-10-02 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-10-02 |
Time |
11:31 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-10-02 |
Time |
11:31 |
Sent To |
|
|
Notes |
2008-10-02 11:34:05 | TO "COMM" BD#3 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2008-08-05 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-08-05 |
Time |
15:56 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-08-05 |
Time |
15:56 |
Sent To |
|
|
Notes |
2008-08-05 15:59:35 | TO "COMM" BD#7 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-07-02 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-07-02 |
Time |
16:02 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2008-05-30 |
Time |
16:42 |
Sent To |
PC |
|
Notes |
2008-05-30 16:45:29 | TO "COMM" BD#52 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2008-10-03 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-10-03 |
Time |
14:13 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2008-10-03 |
Time |
14:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2008-08-11 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-08-11 |
Time |
11:11 |
Rev Time |
0.20 |
Received By |
tgordon |
Date |
2008-08-11 |
Time |
11:11 |
Sent To |
|
|
Notes |
2008-08-11 11:12:32 | SEE FUEL REVIEW NOTES. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2008-06-23 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-06-23 |
Time |
08:02 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2008-06-23 |
Time |
08:02 |
Sent To |
|
|
Notes |
2008-06-23 08:12:33 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) SUBMIT A SITE PLAN SHOWING PROPERTY LINES GENERATOR | | LOCATION, AND BUILDING OPENINGS, PER NFPA 37. | | | | 2) SHOW ON PLANS TYPE OF FUEL, TANK CAPACITY, AND | | LOCATION OF FUEL STORAGE TANK FOR GENERATOR, PER NFPA | | 30 4.3.2.1. | | | | 3) PLEASE SUBMIT MANUFACTURER'S SPECIFICATION'S AND | | INSTALLATION INSTRUCTIONS. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2008-10-07 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2008-10-07 |
Time |
20:40 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2008-10-07 |
Time |
20:40 |
Sent To |
|
|
Notes |
2008-10-07 20:40:38 | ***PROVISO*** | | | | CREEPING FIG VINE SHALL BE INSTALLED ON THE EXTERIOR OF | | THE SCREEN WALL PRIOR TO FINAL INSPECTION. | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER, | | AT 822-1435. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2008-08-20 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2008-08-20 |
Time |
09:31 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2008-08-20 |
Time |
09:31 |
Sent To |
|
|
Notes |
2008-08-20 09:31:21 | ***PROVISO*** | | | | CREEPING FIG VINE SHALL BE INSTALLED ON THE EXTERIOR OF | | THE SCREEN WALL PRIOR TO FINAL INSPECTION. | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER, | | AT 822-1435. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2008-06-04 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2008-06-04 |
Time |
09:22 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2008-06-04 |
Time |
09:22 |
Sent To |
|
|
Notes |
2008-06-04 09:26:48 | ***FAILED*** | | | | 1) TWO (2) COPIES OF A CURRENT AND ACCURATE SURVEY | | SHALL BE PROVIDED. | | | | 2) TWO (2) COPIES OF A SITE PLAN SHOWING THE LOCATION | | OF THE GENERATOR ON THE ENTIRE PROPERTY SHALL BE | | PROVIDED.SETBACK DIMENSIONS SHALL BE PROVIDED FROM | | THE GENERATOR TO THE ADJACENT PROPERTY LINES. | | | | 3) PLEASE NOTE WHETHER OR NOT THE SCREEN WALL IS | | EXISTING.IF THE WALL IS NOT EXISTING, THEN DETAILS | | WILL NEED TO BE PROVIDED OF THE PROPOSED WALL. | | | | 4) PLEASE NOTE THE HEIGHT OF THE SCREEN WALL. | | | | 5) PLEASE PROVIDE AN ELEVATION OF THE GENERATOR | | INDICATING THE OVERALL HEIGHT OF THE GENERATOR.THE | | SCREEN WALL SHALL COMPLETELY SCREEN THE GENERATOR FROM | | VIEW. | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER, | | AT (561) 822-1435. |
|
|