Plan Review Stops For Permit 08050778 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2008-06-17 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-06-17 |
Time |
11:39 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-06-17 |
Time |
09:33 |
Sent To |
PC |
|
Notes |
2008-06-17 11:40:43 | BUILDING PROVISO: | | TO BE IN PLACE AT C.O: | | | | PRIVATE | | 1) 424.2.17.1 OUTDOOR SWIMMING POOLS. OUTDOOR SWIMMING | | POOLS SHALL BE PROVIDED WITH A BARRIER COMPLYING WITH | | 424.2.17.1.1 THROUGH 424.2.17.1.14. | | | | 424.2.17.1.5 CHILD SAFETY BARRIERASTM D5034 100 LB | | TENSILE STRNGTHASTM D3787 150 LB BALL BURST STRENGTH | | | | 2) 13-612.1.ABC.2.3.2 COVERS REQUIRED. SPAS AND HEATED | | SWIMMING POOLS SHALL BE EQUIPPED WITH A COVER DESIGNED | | TO MINIMIZE HEAT LOSS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2008-06-06 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-06-06 |
Time |
16:17 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-06-06 |
Time |
16:17 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
4 |
Status |
N |
Date |
2008-08-28 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-08-28 |
Time |
13:59 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2008-08-28 |
Time |
13:59 |
Sent To |
R |
|
Notes |
2008-08-28 14:00:15 | CONTRACTOR INFORMATION | | NOTE: GAS PERMIT REQUIRED. LICENSED GAS OR PLUMBING | | CONTRACTOR TO SUBMIT PLANS WITH PERMIT APPLICATION. ALL | | GAS INSPECTIONS TO BE COMPLETE BEFORE FINAL POOL | | INSPECTION. | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
N |
Date |
2008-08-21 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-08-21 |
Time |
13:34 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2008-08-21 |
Time |
13:34 |
Sent To |
PC |
|
Notes |
2008-08-21 13:36:37 | CONTRACTOR INFORMATION | | NOTE: GAS PERMIT REQUIRED. LICENSED GAS OR PLUMBING | | CONTRACTOR TO SUBMIT PLANS WITH PERMIT APPLICATION. ALL | | GAS INSPECTIONS TO BE COMPLETE BEFORE FINAL POOL | | INSPECTION. | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
N |
Date |
2008-08-08 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-08-08 |
Time |
10:58 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2008-08-08 |
Time |
10:58 |
Sent To |
PC |
|
Notes |
2008-08-08 11:00:49 | CONTRACTOR INFORMATION | | NOTE: GAS PERMIT REQUIRED. LICENSED GAS OR PLUMBING | | CONTRACTOR TO SUBMIT PLANS WITH PERMIT APPLICATION. ALL | | GAS INSPECTIONS TO BE COMPLETE BEFORE FINAL | | INSPECTION. | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2008-06-09 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-06-09 |
Time |
13:59 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2008-06-09 |
Time |
13:59 |
Sent To |
B |
|
Notes |
2008-06-09 14:02:56 | GAS PLAN REVIEW: | | DENIED: | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | 1. PLEASE REFERENCE PLUMBING COMMENT #3 AND COMPLY. | | | | END OF COMMENTS: | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2008-08-27 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-08-27 |
Time |
16:14 |
Rev Time |
0.00 |
Received By |
tgordon |
Date |
2008-08-27 |
Time |
16:14 |
Sent To |
P |
|
Notes |
2008-08-27 16:14:48 | TO "PLUMB" MIKE P. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2008-08-21 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-08-21 |
Time |
09:10 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-08-21 |
Time |
09:10 |
Sent To |
P |
|
Notes |
2008-08-21 09:11:41 | TO "P" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2008-08-07 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-08-07 |
Time |
08:36 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-08-07 |
Time |
08:36 |
Sent To |
Z |
|
Notes |
2008-08-07 08:37:11 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-06-17 |
Time |
|
Rev Time |
|
Received By |
mjacobs |
Date |
2008-06-02 |
Time |
08:22 |
Sent To |
|
|
Notes |
2008-06-02 08:22:13 | TO "Z" BOX |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2008-08-28 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-08-28 |
Time |
13:58 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2008-08-28 |
Time |
13:58 |
Sent To |
G |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2008-08-21 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-08-21 |
Time |
13:22 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2008-08-21 |
Time |
13:22 |
Sent To |
G |
|
Notes |
2008-08-21 13:34:20 | PLUMBING PLAN REVIEW: | | DENIED **3RD TIME: | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE | | DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW | | COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW | | COMMENTS. | | NOTE: THERE WAS NO COMMENT RESPONSE FROM THE | | DESIGNER. | | | | 1. "OK" COMMENT ADDRESSED. | | | | 2. "OK" COMMENT ADDRESSED | | | | 3. "OK" COMMENT ADDRESSED. | | | | 4. "OK" PREVIOUS COMMENTS ADDRESSED. | | | | **THE FOLLOWING IS A NEW COMMENT** | | | | 5. ONE SET OF RESUBMITTED PLANS HAS A PHOTOCOPY OF THE | | ENGINEER OF RECORD SIGNATURE AND NO RAISED SEAL ON THE | | POOL EQUIPMENT ANCHORING DETAIL. PER CHAPTER FS 471 ANY | | DOCUMENT WITH A TITLE BLOCK OF THE ENGINEER OF RECORD | | SHALL CONTAIN THE ORIGINAL SIGNATURE, DATE, AND SEAL OF | | SAID ENGINEER. | | | | ********IMPORTANT INFORMATION******** | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | END OF COMMENTS: | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | PHONE= (561) 805-6730 | | FAX= (561) 805-6731 | | E-MAIL= [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2008-08-08 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-08-08 |
Time |
10:36 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2008-08-08 |
Time |
10:36 |
Sent To |
G |
|
Notes |
2008-08-08 10:42:05 | PLUMBING PLAN REVIEW: | | DENIED **2ND TIME: | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE | | DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW | | COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW | | COMMENTS. | | NOTE: THERE WAS NO COMMENT RESPONSE FROM THE | | DESIGNER. | | | | 1. SHEET 2, PLUMBING HAS TWO DIFFERENT VENT SIZES | | BEING INDICATED FOR THE POOL MAIN DRAIN, ONE AS BEING | | 1" AND THE OTHER BEING 1-1/2", ALSO THE SPA MAIN DRAIN | | VENT PIPING IS BEING INDICATED AS 1-1/2", HOWEVER THE | | "ENTRAPMENT AVOIDANCE VENT PIPE ANALYSIS - MAXIMUM | | LENGTH" SHEET IS ONLY INDICATING A VENT PIPE TABLE FOR | | 1" PIPE. PLEASE CORRELATE AND CORRECT RESUBMITTED | | SHEETS WITH VENT PIPE SIZES. PER (W.P.B. AS AMENDED) | | SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | **PREVIOUS COMMENT HAS NOT BEEN ADDRESSED. THE | | RESUBMITTED PLANS ARE INDICATING AN 1-1/2" VENT, | | HOWEVER THE ENTRAPMENT AVOIDANCE VENT PIPE | | ANALISIS-MAXIMUM LENGTH DETAIL IS FOR A 1" VENT PIPE. | | AS REQUESTED IN THE FIRST PLAN REVIEW PLEASE CORRELATE | | ALL SHEETS TO REFLECT THE SAME VENT PIPE SIZE. PER | | (W.P.B. AS AMENDED) SECTION 106.1.1 INFORMATION ON | | CONSTRUCTION DOCUMENTS AND FBC-2004 RESIDENTIAL CHAPTER | | 41, SECTION R4101.6 ENGINEERING DESIGN. | | | | 2. "OK" COMMENT ADDRESSED | | | | 3. "OK" COMMENT ADDRESSED. | | | | **THE FOLLOWING IS A NEW COMMENT** | | | | 4. SEE ATTACHED NOTICE FS 553.80(2)(B) REGARDING FOUR | | TIMES THE FEE. | | | | ********IMPORTANT INFORMATION******** | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | END OF COMMENTS: | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | PHONE= (561) 805-6730 | | FAX= (561) 805-6731 | | E-MAIL= [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2008-06-09 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-06-09 |
Time |
13:26 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2008-06-09 |
Time |
13:25 |
Sent To |
G |
|
Notes |
2008-06-09 13:59:28 | PLUMBING PLAN REVIEW: | | DENIED: | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | 1. SHEET 2, PLUMBING HAS TWO DIFFERENT VENT SIZES | | BEING INDICATED FOR THE POOL MAIN DRAIN, ONE AS BEING | | 1" AND THE OTHER BEING 1-1/2", ALSO THE SPA MAIN DRAIN | | VENT PIPING IS BEING INDICATED AS 1-1/2", HOWEVER THE | | "ENTRAPMENT AVOIDANCE VENT PIPE ANALYSIS - MAXIMUM | | LENGTH" SHEET IS ONLY INDICATING A VENT PIPE TABLE FOR | | 1" PIPE. PLEASE CORRELATE AND CORRECT RESUBMITTED | | SHEETS WITH VENT PIPE SIZES. PER (W.P.B. AS AMENDED) | | SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | 2. FBC-2004 SEC. 424.2.6.6.5, OR | | FBCR-2004 SEC. R4101.6.6.5 WHERE | | PROVIDED, THE VACUUM OR PRESSURE CLEANER | | FITTING SHALL BE LOCATED AT LEAST 6" AND | | NOT GREATER THAN 12" BELOW THE MINIMUM | | OPERATING WATER LEVEL OR AS AN | | ATTACHMENT TO THE SKIMMER. | | ( DETAIL REQUIRED WITH MAKE AND MODEL NUMBER OR | | PROVIDE MANUFACTURER'S SPECIFICATION SHEET WITH THE | | MAKE AND MODEL NUMBER) | | | | 3. FBC-2004 SEC. 424.2.14.1, OR | | FBCR-2004 SEC. R4101.14.1 SWIMMING POOL | | WATER HEATERS SHALL BEAR THE LABEL OF A | | RECOGNIZED TESTING AGENCY. (MANUFACTURE | | SHEETS REQUIRED, PLEASE SUBMIT) | | NOTE: THE SUBMITTED MANUFACTURE SHEET FOR THE POOL | | HEATER DOES NOT INDICATE A LISTING FROM A NATIONALLY | | RECOGNIZED TESTING LABORATORY. | | | | ********IMPORTANT INFORMATION******** | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | END OF COMMENTS: | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | PHONE= (561) 805-6730 | | FAX= (561) 805-6731 | | E-MAIL= [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2008-08-07 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2008-08-07 |
Time |
17:47 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2008-08-07 |
Time |
17:47 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2008-06-06 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2008-06-06 |
Time |
08:21 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2008-06-06 |
Time |
08:21 |
Sent To |
E |
|
Notes |
2008-06-06 08:23:59 | ***FAILED*** | | | | | | 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED POOL | | EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION | | 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT | | PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK. | | MINIMUM REQUIRED SIDE SETBACK FOR SHOWN LOCATION OF | | POOL EQUIPMENT IS 3.5 FEET. | | | | 2)AS THE SURVEY DOES NOT SHOW AN EXISTING PERMANENT | | FENCE COMPLETELY SURROUNDING THE POOL, A FENCE PERMIT | | SHALL BE SUBMITTED CONCURRENTLY AND SHALL CONFORM TO | | THE MINIMUM STANDARDS PROVIDED BELOW. | | | | PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND | | DEVELOPMENT REGULATIONS, SECTION, 94-304(D)(2)(B)+(C): | | B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE | | OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT | | ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF | | THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED. | | BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN | | HEIGHT ABOVE GRADE. | | C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE | | THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND | | SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR | | WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF | | GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL | | SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH | | WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT | | SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A | | 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE, | | AT THE PROPERTY LINE, TO ENSURE PRIVACY. | | | | IF A FENCE PERMIT HAS BEEN APPLIED FOR PLEASE INDICATE | | THE EXISTING FENCE ENCLOSURE ON THE SURVEYS AND | | INDICATE THE PERMIT NUMBER. | | | | | | NOTE:IF A PATIO OR PAVED AREA IS PROVIDED ADJACENT | | TO OR SURROUNDING A POOL, IT SHALL BE DESIGNED TO DRAIN | | AWAY FROM THE POOL, BUT NOT ONTO ADJACENT PROPERTIES. | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | ZONING TECHNICIAN (561)805-6720 |
|
|