Plan Review Details - Permit 08050719
Plan Review Stops For Permit 08050719
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-07-25 Cont ID  
Sent By mjacobs Date 2008-07-25 Time 16:39 Rev Time 0.00
Received By mjacobs Date 2008-07-25 Time 14:12 Sent To PC
Notes
2008-07-25 16:40:09NOTE: PROVISOR: EPOXY OR ENAMEL PAINT ON DRYWALL IS NOT
 CONSIDERED A HARD SURFACE. A DIFFERENT TYPE OF MATERIAL
 SHALL BE USED TO MEET THE REQUIREMENTS OF FBC 1210.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-02 Cont ID  
Sent By mjacobs Date 2008-06-02 Time 12:24 Rev Time 0.00
Received By mjacobs Date 2008-06-02 Time 08:27 Sent To  
Notes
2008-06-02 12:24:27 
 BUILDING PLAN REVIEW
 PERMIT: 08050719
 ADD: 2475 MERCER AVE #301- 302 B
 CONT: PHILLIP E JOHNSON INC.
 TEL: (561)366-1034
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 6-2-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1)WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)106.3.5.1.1(5), FS 553.79(2) FIRE SPRINKLER PLANS
 REQUIRED.
 PROVIDE A FIRE SPRINKLER LAYOUT SHOWING THE SPRINKLER
 HEADS IN REFERENCE TO THE NEW WALLS BEING CONSTRUCTED.
 THIS MAY BE SHOWN ON THE REFLECTED CEILING PLANS
  
 3)SHOW THE ELEVATION OF THE RECEPTIONIST WINDOW
 SHOWING ALL DIMENSIONS MEETING THE REQUIREMENTS OF FBC
 SECTION 11-7 WHERE A PORTION OF THE COUNTER SHALL HAVE
 A MAXIMUM HEIGHT OF 36 INCHES AND MINIMUM WIDTH OF 36
 INCHES WHEN SERVICES ARE RENDERED TO THE PUBLIC.
  
 4)ADDITIONAL INFORMATION IS REQUIRED FOR THE ROOM
 FINISHES; INDICATING WHICH WALL RECEIVES THE REQUIRED
 FINISH. THE SCHEDULE PROVIDED IS NOT CLEAR, AND THERE
 ARE NOT ROOM NUMBERS ON THE SCHEDULE. NOTE: 1210.2
 WALLS WITHIN 2 FEET OF URINALS AND WATER CLOSETS SHALL
 HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT
 OF 4 FEET ABOVE THE FINISH FLOOR.
  
 5) INDICATE THE VERTICAL ACCESSIBILITY FOR THE BUILDING
 ON THE DRAWINGS. FBC 11-4.1.3(5) ONE PASSENGER ELEVATOR
 COMPLYING WITH 11-4.10 SHALL SERVE EACH LEVEL,
 INCLUDING MEZZANINES, IN ALL MULTISTORY BUILDINGS AND
 FACILITIES.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-06-05 Cont ID  
Sent By btrobaug Date 2008-06-05 Time 13:33 Rev Time 0.00
Received By btrobaug Date 2008-06-05 Time 13:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-07-22 Cont ID  
Sent By mwennerg Date 2008-07-22 Time 14:49 Rev Time 0.00
Received By mwennerg Date 2008-07-22 Time 14:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-06-05 Cont ID  
Sent By mwennerg Date 2008-06-05 Time 15:15 Rev Time 0.00
Received By mwennerg Date 2008-06-05 Time 15:15 Sent To  
Notes
2008-06-05 15:17:47***PROVISO***
  
 PLANS WILL BE STAMPED IF BUILDING COMMENT #2 IS
 SATISFIED WHEN RE-SUBMITTED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-09 Cont ID  
Sent By adarroug Date 2008-07-09 Time 15:44 Rev Time 0.00
Received By adarroug Date 2008-07-09 Time 15:44 Sent To  
Notes
2008-07-11 16:29:05TO "BOB"#11
2008-07-09 15:45:06WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-05 Cont ID  
Sent By mwennerg Date 2008-06-05 Time 15:25 Rev Time 0.00
Received By mwennerg Date 2008-05-29 Time 14:54 Sent To  
Notes
2008-05-29 14:54:49TO "BOB"#5

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-06-04 Cont ID  
Sent By tgordon Date 2008-06-04 Time 10:00 Rev Time 0.30
Received By tgordon Date 2008-06-04 Time 10:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-07-15 Cont ID  
Sent By mperson Date 2008-07-15 Time 16:48 Rev Time 0.00
Received By mperson Date 2008-07-15 Time 16:48 Sent To  
Notes
2008-07-15 16:49:22NOTE: PREVIOUS COMMENTS WERE ADDRESSED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-06-05 Cont ID  
Sent By mperson Date 2008-06-05 Time 11:11 Rev Time 0.00
Received By mperson Date 2008-06-05 Time 11:11 Sent To  
Notes
2008-06-05 11:58:39PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET P-1.0 PLUMBING FLOOR PLAN, SANITARY AND WATER
 RISER DIAGRAMS: CLEARLY IDENTIFY ALL FIXTURES AS TWO
 ARE NOT IDENTIFIED ON THE PLUMBING FLOOR PLAN AND ONE
 IS NOT IDENTIFIED ON THE SANITARY AND WATER RISER
 DIAGRAMS IN KITCHEN #109. PER FBC-2004 PLUMBING SECTION
 601.1 SCOPE AND SECTION 701.1 SCOPE.
  
 2. SHEET P-1.0 WATER RISER DIAGRAM: CLEARLY IDENTIFY
 WHAT IS BEING INSTALLED AT EACH FIXTURE FOR WATER
 HAMMER. SHEET P-2.0 GENERAL PLUMBING NOTES #17 STATES
 "CONTRACTOR SHALL PROVIDE MAINTENANCE FREE MECHANICAL
 SHOCK ARRESTORS AT ALL FIXTURES WITH QUICK CLOSING
 VALVES", HOWEVER THE FIXTURES INDICATED IN THE WATER
 RISER DIAGRAM ARE NOT QUICK CLOSING. AIR CHAMBERS ARE
 NOT ACCEPABLE UNLESS THEY ARE PER "STANDARD PDI-WH 201,
 A RECHARGABLE TYPE OF AIR CHAMBER"(DETAIL REQUIRED).
 PER FBC- 2004 PLUMBING SECTION 604.9 WATER HAMMER.
  
 3. SHEET A-2.01 DETAIL #3: CLEARLY INDICATE THE KNEE
 CLEARANCE COMPLIANT WITH FBC-2004 CHAPTER 11 SECTION
 11-4.24.3 (27" HIGH, 30" WIDE, AND 19" DEEP SHALL BE
 PROVIDED UNDERNEATH SINKS.
  
 4. SHEET 1A-1.01 THIRD FLOOR PLAN: CLEARLY INDICATE
 THE CLEAR FLOOR SPACE FOR THE SINK IN KITCHEN #109 AND
 AND SINK ACROSS FROM ROOM #105 COMPLIANT WITH FBC-2004
 CHAPTER 11 SECTION 11-4.24.5 (30" X 48" AND SHALL
 EXTEND A MAXIMUM OF 19" UNDERNEATH THE SINK).
  
 5. SHEET P-2.0 PLUMBING FIXTURE CONNECTION SCHEDULE:
 FIXTURE P-4 DISCRIPTION IS BEING INDICATED AS A SERVICE
 SINK WITH A 2" WASTE. ISN'T THIS A 6-1/2" DEEP
 STAINLESS STEEL SINK WITH A 1-1/2" WASTE. PLEASE
 CLARIFY THIS ON THE RESUBMITTAL. PER FBC-2004 PLUMBING
 SECTION 401.1 SCOPE.
  
 6. SHEET A-2.01 DETAIL #2 ADA FOUNTAIN: PER
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR SUCH AS A
 CUP HOLDER).
  
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2008-06-06 Cont ID  
Sent By choops Date 2008-06-06 Time 13:39 Rev Time 0.00
Received By choops Date 2008-06-06 Time 13:39 Sent To  
Notes
2008-06-06 13:39:23*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.