Plan Review Details - Permit 08050685
Plan Review Stops For Permit 08050685
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-09-26 Cont ID  
Sent By shill Date 2008-09-26 Time 17:21 Rev Time 0.00
Received By shill Date 2008-09-26 Time 17:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-09-26 Cont ID  
Sent By shill Date 2008-09-26 Time 13:46 Rev Time 0.00
Received By shill Date 2008-09-26 Time 13:46 Sent To  
Notes
2008-09-26 15:14:23****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 1. SEE PAGE11 OF STORM PANEL PRODUCT APPROVAL. A FACTOR
 OF .86 MUST BE APPLIED TO FASTENER SPACING, BOTTOM.
 YOU'VE CIRCLED 12" BOTTOM 1 WITH 3" EDGE DISTANCE. IT
 APPEARS THAT THE FACTOR WAS APPLIED TO THE TOP BUT NOT
 TO THE BOTTOM. TWO DIFFERENT ANCHORS WERE CIRCLED ON
 THE FACTOR CHART ON PAGE 11, BUT ONLY ONE ANCHOR
 SPECIFIED ON THE INSTALLATION SCHEDULE.
  
 2. WHEN COMPLETING THE INSTALLATION SCHEDULE, THE
 SHUTTER MOUNTING CONNECTION TYPE SHOULD CORRELATE WITH
 THE ANCHOR SCHEDULE; IT APPEARS THAT YOU ARE USING TOP
 1 AND BOTTOM 1. THE SPECIFIC ANCHOR TYPE SHOULD BE THE
 ANCHOR; NOT CLEAR WHICH ANCHOR YOU ARE USING BECAUSE
 YOU'D WRITTEN "TAPCON" IN ANOTHER PLACE BUT CIRCLED TWO
 DIFFERENT ANCHORS ON THE PRODUCT APPROVAL.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-09-08 Cont ID  
Sent By shill Date 2008-09-08 Time 12:48 Rev Time 0.00
Received By shill Date 2008-09-08 Time 12:48 Sent To  
Notes
2008-09-08 12:58:00****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 1. SEE PAGE11 OF STORM PANEL PRODUCT APPROVAL. A FACTOR
 OF .86 MUST BE APPLIED TO FASTENER SPACING, BOTTOM.
 YOU'VE CIRCLED 12" BOTTOM 1 WITH 3" EDGE DISTANCE. IT
 APPEARS THAT THE FACTOR WAS APPLIED TO THE TOP BUT NOT
 TO THE BOTTOM. TWO DIFFERENT ANCHORS WERE CIRCLED ON
 THE FACTOR CHART ON PAGE 11, BUT ONLY ONE ANCHOR
 SPECIFIED ON THE INSTALLATION SCHEDULE.
  
 2. WHEN COMPLETING THE INSTALLATION SCHEDULE, THE
 SHUTTER MOUNTING CONNECTION TYPE SHOULD CORRELATE WITH
 THE ANCHOR SCHEDULE; IT APPEARS THAT YOU ARE USING TOP
 1 AND BOTTOM 1. THE SPECIFIC ANCHOR TYPE SHOULD BE THE
 ANCHOR; NOT CLEAR WHICH ANCHOR YOU ARE USING BECAUSE
 YOU'D WRITTEN "TAPCON" IN ANOTHER PLACE BUT CIRCLED TWO
 DIFFERENT ANCHORS ON THE PRODUCT APPROVAL.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-08-25 Cont ID  
Sent By shill Date 2008-08-25 Time 13:28 Rev Time 0.00
Received By shill Date 2008-08-25 Time 13:28 Sent To  
Notes
2008-08-25 13:30:29****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 1.COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR
 PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT, FBC*106.TWO SETS REQUIRED.
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 2.PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS
 WILL BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH
 THE INSTALLATION SCHEDULE, ITEM 2 ABOVE.
  
 3.SHOW EMERGENCY MEANS OF ESCAPE ON THE PLAN, FBC
 R301.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-05-29 Cont ID  
Sent By shill Date 2008-05-29 Time 10:24 Rev Time 0.00
Received By shill Date 2008-05-29 Time 10:24 Sent To  
Notes
2008-05-29 10:24:23****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 ***WINDOW OR DOOR PERMIT APPLICATION, ONLY CHECKED
 ITEMS APPLY***
  
 ____1.A NOTICE OF COMMENCEMENT MUST BE FILED WITH
 THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13.
  
 ____2.PROVIDE BUILDING HEIGHT.DESIGN PRESSURES
 FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE DESIGNED
 USING ASCE7, FBC1609.1.1. DOCUMENTS PREPARED BY AN
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED SEALED ORIGINALS FAC61G15-23.002.
  
 ____3.PROVIDE A COPY OF THE CONDO ASSOCIATION
 APPROVAL.
  
 _XX_4.IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2.PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE ATTACHED INSTALLATION SCHEDULE.
 IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 507.3,
 PROVIDE CALCULATIONS.
  
 ____5.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 ____6.PROVIDE A FLOOR PLAN SHOWING: WINDOW
 LOCATIONS, SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE
 EXISTING CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE
 FOR BEDROOMS, FBC R310, FBC EB 505.1.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-09-19 Cont ID  
Sent By adarroug Date 2008-09-19 Time 09:30 Rev Time 0.00
Received By adarroug Date 2008-09-19 Time 09:30 Sent To B
Notes
2008-09-19 09:30:30TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-09-03 Cont ID  
Sent By adarroug Date 2008-09-03 Time 12:19 Rev Time 0.00
Received By adarroug Date 2008-09-03 Time 12:19 Sent To B
Notes
2008-09-03 12:20:15TO "SHILL' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-18 Cont ID  
Sent By adarroug Date 2008-08-18 Time 08:27 Rev Time 0.00
Received By adarroug Date 2008-08-18 Time 08:27 Sent To B
Notes
2008-08-18 08:27:41TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-29 Cont ID  
Sent By shill Date 2008-05-29 Time 10:24 Rev Time 0.00
Received By shill Date 2008-05-27 Time 14:28 Sent To  
Notes
2008-05-27 14:29:14TO "MISC" BOX#1

Review Stop Z ZONING
Rev No 1 Status N Date 2008-08-24 Cont ID  
Sent By mcruz Date 2008-08-24 Time 11:25 Rev Time 0.00
Received By mcruz Date 2008-08-24 Time 11:25 Sent To  
Notes
***NONE***