Review Stop G GAS REVIEW
Rev No 5 Status P Date 2009-03-11 Cont ID  
Sent By lwagner Date 2009-03-11 Time 11:28 Rev Time 0.00
Received By lwagner Date 2009-03-11 Time 09:49 Sent To  
Notes
2009-03-11 09:49:30REVISION OK

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2008-06-11 Cont ID  
Sent By mperson Date 2008-06-11 Time 15:23 Rev Time 0.00
Received By mperson Date 2008-06-11 Time 15:23 Sent To PC
Notes
2008-06-11 15:25:17REVISION: "OK" CHANGED PIPING LAYOUT TO DRYER.
  
 ****************PROVISO****************
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 3,850 CUBIC FEET REQUIRED.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2008-06-10 Cont ID  
Sent By mperson Date 2008-06-10 Time 08:52 Rev Time 0.00
Received By mperson Date 2008-06-10 Time 08:52 Sent To PC
Notes
2008-06-10 09:12:50GAS PLAN REVIEW:
 DENIED REVISION:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 1. ALL CHANGES TO THE PLAN ARE TO BE CLOUDED WITH
 REVISION NUMBERS/DATES PER FBC-2004 CHAPTER 1, SECTION
 106.1.3 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM.
 NOTE: A TRANSMITTAL LETTER IS HELPFUL.
  
 2. PER FBC-2004 CHAPTER 1, SECTION106.1 SUBMITTAL
 DOCUMENTS. CONSTRUCTION DOCUMENTS, SPECIAL INSPECTION
 AND STRUCTURAL OBSERVATION PROGRAMS, AND OTHER DATA
 SHALL BE SUBMITTED IN TWO OR MORE SETS WITH EACH
 APPLICATION FOR A PERMIT AND REVISIONS TO PERMITTED
 PLANS.
 NOTE: ONLY ONE REVISED SET OF PLANS WERE SUBMITTED,
 TWO SETS ARE REQUIRED.
  
 3. NOTE: THIS WAS SUBMITTED AS A SUBMITTAL. THIS IS
 NOT A SUBMITTAL THIS IS A REVISION DUE TO DESIGN
 CHANGES. FEES OF $70.00 ARE DUE FOR THIS REVISION PLAN
 REVIEW AND FEES WILL ALSO BE REQUIRED FOR THE NEXT
 REVISION SUBMITTED FOR PLAN REVIEW.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-06-02 Cont ID  
Sent By mperson Date 2008-06-02 Time 13:13 Rev Time 0.00
Received By mperson Date 2008-06-02 Time 13:13 Sent To PC
Notes
2008-06-02 13:41:37****************PROVISO****************
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 3,850 CUBIC FEET REQUIRED.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-05-27 Cont ID  
Sent By mperson Date 2008-05-27 Time 13:14 Rev Time 0.00
Received By mperson Date 2008-05-27 Time 13:14 Sent To I
Notes
2008-05-27 13:48:38GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE VALUE ON THE PERMIT APPLICATION APPEARS LOW.
 THE VALUE ON THE PERMIT APPLICATION MUST INCLUDE THE
 TOTAL COST OF LABOR AND MATERIALS. VALUATION REFERENCES
 MAY INCLUDE THE LATEST PUBLISHED DATA OF A NATIONAL
 CONSTRUCTION COST ANALYSIS (MARSHALL-SWIFT, MEANS,
 ECT...) ADJUST THE VALUE AT THE PERMIT CLERK'S DESK AND
 PAY THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING OR
 PROVIDE A COPY OF THE SIGNED CONRACT BY BOTH PARTIES
 (CONTRACTOR AND CUSTOMER) TO VERIFY THE PERMIT
 APPLICATION VALUE. PER (W.P.B. AS AMENDED) SECTION
 108.3 BUILDING PERMIT VALUATION.
  
 2. THE SUBMITTED FLOOR PLAN FOR THE GAS PIPING HAS AN
 ARCHITECT'S TITLE BLOCK.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 3. THE SUBMITTED GAS ISOMETRIC DOES NOT HAVE
 CORRESPONDING LENGTHS BEING INDICATED FOR ALL CUT
 SECTIONS OF PIPE. PLEASE REFERENCE THE RED CIRCLED
 YELLOW HIGH LIGHTED CUT SECTIONS WITHOUT CORRESPONDING
 LENGTHS BEING INDICATED. A GAS PLAN REVIEW CAN NOT BE
 DONE UNLESS ALL CUT SECTION OF PIPE HAVE CORRESPONDING
 LENGTHS INDCATED. PER FBC-2004 FUEL GAS SECTION 401.1.
  
 4. THE SUBMITTED GAS ISOMETRIC DOES NOT HAVE ALL CUT
 SECTIONS OF PIPE BEING SIZED. PLEASE REFERENCE THE CSST
 PIPING FROM THE 1-1/4"X1"X1" BLK/STEEL TEE TO THE
 77,000 BTU WATER HEATER THAT NOT SIZED. PLEASE SIZE ALL
 CUT SECTIONS OF PIPE ON THE RESUBMITTAL. PER FBC-2004
 FUEL GAS SECTION 401.1 SCOPE.
  
 5. CLEARLY INDICATE THAT ALL FUTURE APPLIANCES WILL BE
 CAPPED GAS TIGHT (FUTURE POOL HEATER AND FUTURE FIRE
 PLACE). PER FBC-2004 FUEL GAS SECTION 404.12 OUTLET
 CLOSURES.
  
 6. PLEASE INDICATE ON THE RESUBMITTED FLOOR PLAN THAT
 THE GAS WATER HEATER IN THE 1 CAR GARAGE WILL BE
 PROTECTED FROM PHYSICAL DAMAGE BY APPROVED BARRIERS.
 PER FBC-2004 FUEL GAS SECTION 303.4 PROTECTIN FRO
 PHYSICAL DAMAGE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-06-10 Cont ID  
Sent By adarroug Date 2008-06-10 Time 14:17 Rev Time 0.00
Received By adarroug Date 2008-06-10 Time 14:17 Sent To G
Notes
2008-06-10 14:18:11TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-06 Cont ID  
Sent By adarroug Date 2008-06-06 Time 16:37 Rev Time 0.00
Received By adarroug Date 2008-06-06 Time 16:37 Sent To G
Notes
2008-06-06 16:37:53TO "G" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-30 Cont ID  
Sent By adarroug Date 2008-05-30 Time 11:26 Rev Time 0.00
Received By adarroug Date 2008-05-30 Time 11:26 Sent To G
Notes
2008-05-30 11:27:03TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-27 Cont ID  
Sent By mperson Date 2008-05-27 Time 13:48 Rev Time 0.00
Received By mperson Date 2008-05-23 Time 12:57 Sent To PC
Notes
***NONE***