Plan Review Details - Permit 08050661
Plan Review Stops For Permit 08050661
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-09-10 Cont ID  
Sent By mjacobs Date 2008-09-10 Time 08:59 Rev Time 0.00
Received By mjacobs Date 2008-09-09 Time 11:53 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-07-30 Cont ID  
Sent By mjacobs Date 2008-07-30 Time 07:38 Rev Time 0.00
Received By mjacobs Date 2008-07-29 Time 12:36 Sent To  
Notes
2008-07-30 07:38:11BUILDING PLAN REVIEW
 PERMIT: 08050661
 ADD: 515 N. FLAGLER DR. P-100
 CONT: FISHER CONTRACTING CORP.
 TEL: (561)691-4718
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
  
 NEEDS
 1)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 NO RESPONSE NOT ADDTESSED
 2)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS.
  
 3)OK
  
 NO RESPONSE NOT ADDRESSED
 4) 106.1.2*ADDITIONAL INFORMATION IS REQUIRED FOR FOR
 THE NEW SOFFIT. PROVIDE THE FRAMING DETAILS SHOWING HOW
 IT WILL BE FASTENED TO THE EXISTING STRUCTURE.
  
 NO RESPONSE NOT ADDRESSED
 5)NOTE: ONE SET OF THE DRAWINGS IS MISSING SHEET
 A-6.1. PROVIDE A FIRE SPRINKLER PLAN SHOWING THE
 LOCATION OF THE SPRINKLER HEADS IN RELATION TO THE NEW
 CONSTRUCTION. THIS INFORMATION CAN BE SHOWN ON THE
 REFLECTED CEILING PLANS. FBC106.3.5.1.1(5)
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-25 Cont ID  
Sent By mjacobs Date 2008-06-25 Time 10:58 Rev Time 0.00
Received By mjacobs Date 2008-06-24 Time 12:44 Sent To  
Notes
2008-06-25 10:58:26BUILDING PLAN REVIEW
 PERMIT: 08050661
 ADD: 515 N. FLAGLER DR. P-100
 CONT: FISHER CONTRACTING CORP.
 TEL: (561)691-4718
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS.
  
 3)THE CONSTRUCTION TYPE OF BUILDING INDICATED ON THE
 DRAWINGS IS TYPE II. THIS BUILDING IS OVER 20 STORIES
 HIGH, THEREFORE, THE BUILDING WILL BE A TYPE I
 CONSTRUCTION TYPE PER FBC SECTION 503 TABLE 503.
 CHAPTER 6 SHALL ALSO BE LOOK AT FOR MORE INFORMATION.
  
 4) 106.1.2*ADDITIONAL INFORMATION IS REQUIRED FOR FOR
 THE NEW SOFFIT. PROVIDE THE FRAMING DETAILS SHOWING HOW
 IT WILL BE FASTENED TO THE EXISTING STRUCTURE.
  
 5)NOTE: ONE SET OF THE DRAWINGS IS MISSING SHEET
 A-6.1. PROVIDE A FIRE SPRINKLER PLAN SHOWING THE
 LOCATION OF THE SPRINKLER HEADS IN RELATION TO THE NEW
 CONSTRUCTION. THIS INFORMATION CAN BE SHOWN ON THE
 REFLECTED CEILING PLANS. FBC106.3.5.1.1(5)
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-12-31 Cont ID  
Sent By dpalmer Date 2008-12-31 Time 09:05 Rev Time 0.00
Received By dpalmer Date 2008-12-31 Time 09:05 Sent To  
Notes
2008-12-31 09:10:24** DENIED REVIEW **
  
  
 ** SHEET E0.1 AND 2.1 ARE OK.
  
 1) NOTE: POWER PLANS ARE NOW MISSING THE REQUIRED
 DISCONNECTS PER 440.11 FOR MECHANICAL EQUIPMENT YET THE
 EQUIPMENT IS STILL BEING SHOWN.
 440.11, 110.26.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-07-28 Cont ID  
Sent By dpalmer Date 2008-07-28 Time 10:07 Rev Time 0.00
Received By dpalmer Date 2008-07-28 Time 10:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-06-20 Cont ID  
Sent By dpalmer Date 2008-06-20 Time 12:49 Rev Time 0.00
Received By dpalmer Date 2008-06-20 Time 12:48 Sent To  
Notes
2008-06-20 12:49:09** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1, .1.2.
  
 2) NOTE: PLEASE INDICATE MAXIMUM OVER RIDE TIMES FOR
 DEVICES AS SHOWN. PLEASE COORDINATE SYMBOL LEGEND.
 PLEASE SEE THE SYMBOL LEGEND MENTIONS TO SEE DETAIL ON
 E7.1 HOWEVER NO ELECTRICAL SHEET E7.1 WAS IN SET OR
 SUBMITTED.
  
 3) NOTE: PLEASE SEE PANEL LA AS SHOWN IS A *MAIN LUG
 ONLY* PANEL. THIS SHALL CONTAIN OVER CURRENT PROTECTION
 ON THE SECONDARY SIDE OF THE TRANSFORMER.
 240.21, 408.36, 240.4, 310.16 ETC
 ** NOTE ON TRANSFORMER SCHEDULE STATES THE BREAKER ON
 SECONDARY PANEL HAS MAIN BUT DOES NOT COORDINATE WITH
 OTHER ITEMS ON SAME SHEET.
  
 IF A MAIN BREAKER DOES NOT EXIST ONE WILL BE REQUIRED
 AS THIS IS A FIRE AND LIFE SAFETY HAZARD.
  
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2009-01-16 Cont ID  
Sent By efabian Date 2009-01-16 Time 13:24 Rev Time 0.00
Received By efabian Date 2009-01-16 Time 13:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-01-21 Cont ID  
Sent By mwennerg Date 2009-01-21 Time 11:04 Rev Time 0.00
Received By mwennerg Date 2009-01-21 Time 11:04 Sent To  
Notes
2009-01-21 11:05:19REVISION #2 DATED 12/12/08

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-09-09 Cont ID  
Sent By mawillia Date 2008-09-09 Time 13:11 Rev Time 0.00
Received By mawillia Date 2008-09-09 Time 12:43 Sent To B1
Notes
2008-09-09 13:11:03*****APPROVED*****
  
  
 ALL PREVIOUS COMMENTS HAVE BEEN ADDRESSED; PLAN SHEETS
 A-2.1, A-6.1, E-2.1, FA0.1, FA2.1, AND FP-1 WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-07-30 Cont ID  
Sent By mwennerg Date 2008-07-30 Time 15:04 Rev Time 0.00
Received By mwennerg Date 2008-07-30 Time 15:04 Sent To  
Notes
2008-07-30 15:08:55***DENIED***
  
 1) OK
  
 2) PLEASE PROVIDE LAYOUT OF FIRE SPRINKLER COVERAGE.
 SEE BUILDING COMMENT #5.
  
 3) NOT ADDRESSED. DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL
 REQUIREMENTS. AMEND FIRE ALARM NOTE #17 ON SHEET
 FA0.1.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-06-25 Cont ID  
Sent By mawillia Date 2008-06-25 Time 14:32 Rev Time 0.00
Received By mawillia Date 2008-06-25 Time 13:08 Sent To  
Notes
2008-06-25 14:31:38*****PROVISO*****
  
 THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN THE
 BELOW COMMENTS HAVE BEEN ADDRESSED:
  
 1.SHOW THE LOCATION OF THE 2A10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATIFIES THE 75' TRAVEL
 DISTANCE.
  
 2.PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS FOR
 THE NEW FLOOR PLAN.
  
 3.AMEND FIRE ALARM NOTE #17 (ON SHEET FA0.1) TO
 REFLECT THAT DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-12-19 Cont ID  
Sent By adarroug Date 2008-12-19 Time 15:33 Rev Time 0.00
Received By adarroug Date 2008-12-19 Time 15:33 Sent To  
Notes
2008-12-19 15:33:44TO "COMM" BD#11

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-09-03 Cont ID  
Sent By adarroug Date 2008-09-03 Time 15:03 Rev Time 0.00
Received By adarroug Date 2008-09-03 Time 15:01 Sent To  
Notes
2008-09-03 15:26:07TO "COMM" BD#21

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-10 Cont ID  
Sent By adarroug Date 2008-07-10 Time 10:22 Rev Time 0.00
Received By adarroug Date 2008-07-10 Time 10:22 Sent To  
Notes
2008-07-10 10:25:15TO "COMM" BD#53

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-27 Cont ID  
Sent By mperson Date 2008-06-27 Time 16:26 Rev Time 0.00
Received By mperson Date 2008-05-23 Time 13:39 Sent To PC
Notes
2008-05-29 11:51:58TO "COMM" BD#15
2008-05-23 13:49:27WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-01-24 Cont ID  
Sent By rregueir Date 2009-01-24 Time 18:12 Rev Time 0.00
Received By rregueir Date 2009-01-24 Time 18:11 Sent To E
Notes
2009-01-24 18:12:31REVISED M0.1, M2.1, M5.1 CHANGING WATER COOLED PACKAGE
 FROM NEW TO EXISTING.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-07-23 Cont ID  
Sent By rregueir Date 2008-07-23 Time 14:33 Rev Time 0.00
Received By rregueir Date 2008-07-21 Time 16:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-06-19 Cont ID  
Sent By rregueir Date 2008-06-19 Time 13:30 Rev Time 0.00
Received By rregueir Date 2008-06-19 Time 09:07 Sent To  
Notes
2008-06-19 13:30:30REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. M0.1: NOTE #15, SMOKE DETECTORS SHALL BE TIED TO THE
 BUILDING FIRE ALARM SYSTEMS IN ACCORDANCE WITH FBCM
 606.4.1.
  
 2. M2.1: NEW BATHROOM EXHAUST FAN HAS AN EXHAUST DUCT
 IN THE PLENUM WHICH IS UNDER POSITIVE PRESSURE. EXHAUST
 DUCTS UNDER POSITIVE PRESSURE SHALL NOT EXTEND INTO OR
 PASS THROUGH DUCTS OR PLENUMS IN ACCORDANCE WITH FBCM
 601.3.
  
 3. M2.1: THE OUTDOOR AIR SUPPLY SYSTEM SHALL BE
 EQUIPPED WITH A MOTORIZED DAMPER THAT WILL
 AUTOMATICALLY SHUT WHEN THE SYSTEM OR SPACE SERVED IS
 NOT IN USE IN ACCORDANCE WITH FBCB 13-409.1.ABC.3.3.
  
 4. M5.1: OUTSIDE AIR CLACULATIONS SHOW A DESIGN BASED
 ON ASHRAE 62-01. OUTSIDE AIR CALCULATIONS SHALL BE
 DETERMINED IN ACCORDANCE WITH FBCM TABLE 403.3 OR
 ASHRAE 62.1-2004 IN ACCORDANCE WITH FBCM 403.4.
  
 5. M5.1: HEAT PUMP SCHEDULE, ACH HYDRONIC HEAT PUMP
 SHALL HAVE A TWO-POSITION AUTOMATIC VALVE INTERLOCKED
 TO SHUT OFF WATER FLOW WHEN THE COMPRESSOR IS OFF IN
 ACCORDANCE WITH FBCB 13-411.1.ABC.1.4.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-07-24 Cont ID  
Sent By mperson Date 2008-07-24 Time 15:24 Rev Time 0.00
Received By mperson Date 2008-07-24 Time 15:24 Sent To  
Notes
2008-07-24 15:41:23****************PROVISO****************
 A} GRAB BAR BEHIND H/C WATER CLOSET SHALL BE A MINIMUM
 OF 36 INCHES (36"). PER FBC-2004 CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE, SECTION 11-4.16.4.
 B} H/C LAV SHALL COMPLY WITH FIG. 31 FOR KNEE & TOE
 CLEARANCE. PER FBC-2004 CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE, SECTION 11-4.19.2.
 C} WATER-HAMMER ARRESTORS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANFACTURER'S RECOMENDATIONS. PER
 FBC-2004 PLUMBING SECTION 604.9.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-06-27 Cont ID  
Sent By mperson Date 2008-06-27 Time 14:53 Rev Time 0.00
Received By mperson Date 2008-06-27 Time 14:53 Sent To I
Notes
2008-06-27 16:26:36PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A-0.0 GROUP B OCCUPANCY LOAD OF 51: PLANS ARE
 NOT COMPLIANT PER FBC- PLUMBING TABLE 403.1 MINIMUM
 NUMBER OF REQUIRED PLUMBING FIXTURES. PROPOSED FLOOR
 PLAN ON SHEET A-2.1 INDICATES ONE (1) WATER CLOSET AND
 ONE (1) LAVATORY, HOWEVER THREE (3) WATER CLOSETS ARE
 REQUIRED, THREE (3) LAVATORIES ARE REQUIRED, AND ONE
 (1) DRINKING FOUNTAIN IS REQUIRED.
  
 2. SHEET A-1.1 DEMO PLANS ARE INCOMPLETE PER FIELD
 INSPECTION THERE IS AN EXISTING MOP SINK AND SINK
 ROUGHED IN THAT ARE NOT INDICATED ON THE DEMO PLANS.
 ALL FIXTURES THAT ARE TO BE DEMOED SHALL BE INDICATED
 ON THE PLANS. PER FBC- PLUMBING 401.1 AND 701.1 SCOPE
 AND PER FBC- PLUMBING, SECTION 704.5 DEAD ENDS: IN THE
 INSTALLATION OR REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED. A PLUMBING
 PERMIT IS REQUIRED AND AN INSPECTION IS REQUIRED OF
 PLUMBING DEMO WORK PRIOR TO COVERING DEMO WORK WITH
 FINNISH WALLS, CIELINGS, OR POURED CONCRETE SLABS.
 (PLEASE ADD TO NOTES)
  
 3. SHEET A-2.1 HANDICAPPED BATHROOM PLAN & ELEVATIONS
 DETAIL (B) H.C. TOILET ROOM ELEVATION: THE LAVATORY
 NEEDS TO INDICATE COMPLIANCE WITH 11-4.19.2 PROVIDE A
 CLEARANCE OF AT LEAST 29 INCHES ABOVE FINNISH FLOOR TO
 THE BOTTOM OF THE APRON. KNEE AND TOE CLEARANCES SHALL
 COMPLY WITH FIGURE 31. ALSO 11-4.19.5 FAUCETS NEEDS TO
 BE INDICATED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]