2008-05-27 15:19:55 | GAS PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. THE SUBMITTED GAS FLOOR PLAN IS A COPY OF MASTER |
| PERMIT #07050618 THAT HAS AN ARCHITECTS TITLE BLOCK. |
| PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| FL ADMIN CODE 61G16.003 ARCHITECTS. NOTE: CONTRACTOR |
| CAN SUBMIT AN ORIGINAL GAS FLOOR OF THEIR DESIGN. |
| |
| 2. THE SUBMITTED GAS ISOMETRIC DRAWING DOES NOT HAVE |
| CORRESPONDING LENGTHS OR PIPING MATERIAL TO ALL CUT |
| SECTIONS OF PIPE INDICATED. REFERENCE THE RED CIRCLED |
| YELLOW HIGHLIGHTED CUT SECTIONS WITH NO CORRESPONDING |
| LENGTHS OR PIPING MATERIAL INDICATED. PER FBC-2004 FUEL |
| GAS SECTION 401.1 SCOPE. |
| NOTE: IT APPEARS FROM THE FLOOR PLAN AND THE ISOMETRIC |
| THAT PE PIPING IS GOING INTO THE BUILDING. PE (PLACTIC |
| PIPE,TUBING AND FITTINGS) PIPING SHALL BE USED OUTSIDE |
| UNDERGROUND ONLY. PER FBC-2004 FUEL GAS SECTIONS 403.6 |
| PLASTIC PIPE, TUBING AND FITTINGS AND 404.14.1 |
| LIMITATIONS. |
| |
| 3. PROVIDE MANUFACTURER'S SPECIFICATION SHEETS FOR THE |
| MP REGULATORS CLEARLY INDICATING THE MAKE MODEL NUMBER, |
| BTU LOAD CAPACITY AND A LISTING FROM A NATIONALLY |
| RECOGNIZED TESTING LABORATORY (EXAMPLES ARE UL,CSA OR |
| AGA). ALSO CLEARLY INDICATE THE MAKE AND MODEL NUMBER |
| ON THE RESUBMITTED GAS ISOMETRIC. PER FBC-2004 FUEL GAS |
| SECTION 401.1 SCOPE AND NFPA 54. |
| |
| 4. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| SECTION *106.3.4.3. NOTE: GAS ISOMETRIC REQUIRES |
| SIGNATURE OF THE PERSON TAKING RESPONSIBLITY. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |