Plan Review Details - Permit 08050629
Plan Review Stops For Permit 08050629
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-07-22 Cont ID  
Sent By mjacobs Date 2008-07-22 Time 11:58 Rev Time 0.00
Received By mjacobs Date 2008-07-22 Time 10:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-20 Cont ID  
Sent By mjacobs Date 2008-06-20 Time 11:07 Rev Time 0.00
Received By mjacobs Date 2008-06-19 Time 11:44 Sent To  
Notes
2008-06-20 11:07:43BUILDING PLAN REVIEW
 PERMIT: 08050629
 ADD: 777 S. FLAGLER DRIVE SUITE 1500
 CONT: BUTLER CONSTRUCTION
 TEL: (561)832-9700
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 6-19-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4)2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 5)THE DOOR SCHEDULE HAS CONFLICTING INFORMATION WHEN
 REFERRING TO THE DOOR TYPES EXAMPLE, DOOR #1510; THE
 DOOR SCHEDULE INDICATETYPE (C)AS A SOLID WOOD
 SINGLE DOOR ACCORDING TO THE DOOR TYPES, HOWEVER THE
 MATERIAL IS NOTED AS GLASS ON THE SCHEDULE. PLEASE NOTE
 THERE IS NO TYPE (A2) DOOR SHOWN ON SHEET A-1.0,
 HOWEVER IT IS INDICATED IN THE DOOR SCHEDULE.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED. 106.1.1.
  
 6)INDICATE HOW THE METAL TRACK OR ANY MATERIAL WILL
 BE FASTENED TO THE STRUCTURE ABOVE. THE DETAIL SHEETS
 SHALL STATE THE TYPE OF FASTENERS TO BE USED. THERE IS
 NO INDICATION AS TO WHAT TYPE OF FASTENERS WILL BE
 USED.
 7)FBC 603. DUE TO THE FACT THAT THIS IS A TYPE I
 BUILDING THE FURRING AND BACKING MATERIALS SHALL BE
 FIRE-RETARDANT-WOOD WHICH IS NOT STATED ON SOME OF THE
 DETAIL SHEETS. INTERIOR FINISH MATERIALS ARE REQUIRED
 TO BE APPLIED DIRECTLY TO EXPOSED SURFACES OF
 STRUCTURAL ELEMENTS OR TO FURRING STRIPS NOT EXCEEDING
 1.75 INCHES ATTACHED TO SUCH SURFACES. FBC 803.4.1.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
2008-06-19 15:50:45REVIEW IN PROGRESS

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-10-07 Cont ID  
Sent By dpalmer Date 2008-10-07 Time 10:39 Rev Time 0.00
Received By dpalmer Date 2008-10-07 Time 10:39 Sent To PC
Notes
2008-10-07 10:39:59REV FOR A/C UNITS E-2 AND E-4

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-08-04 Cont ID  
Sent By dpalmer Date 2008-08-04 Time 11:18 Rev Time 0.00
Received By dpalmer Date 2008-08-04 Time 11:17 Sent To PC
Notes
2008-08-04 11:19:15 
 **REDLINED PLANS**
  
 1) NOTE: PLEASE SEE PANEL R1 WHICH SHOWS #8 TO PANEL R3
 HOWEVER RISER SHOWS #3.THE #3 IS THE CORRECT SIZE PER
 310.16.
 SPOKE TO ENGINEER HE IS AWARE OF THE REDLINE.
  
 ** DURING CONSTRUCTION REVISE ALONG WITH ANY OTHER
 REVISIONS AS NEEDED.
  
  
 ** IF THERE ARE ANY QUESTIONS OR IF THE COMMENTS ARE
 NOT CLEAR IN ANY MANOR PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-07-25 Cont ID  
Sent By dpalmer Date 2008-07-25 Time 14:16 Rev Time 0.00
Received By dpalmer Date 2008-07-25 Time 14:16 Sent To PC
Notes
2008-07-25 14:37:39*** NOTE ADDED ***
  
 1) NOTE: PLEASE COORIDNATE SUITE/UNIT ON PLANS AS
 PERMIT APPLICATION AND ARCHITECTURAL SHEETS SHOW SUITE
 #1500 YET MEP PLANS INDICATE SUITE #1501. THIS CAN BE
 NEATLY HAND PRINTED ON SHEETS WHICH DO NOT NEED TO BE
 RE-PRINTED FOR COMMENTS.
 FAC 61G1-16.004, 61G15-23.002, FBC 106.5
2008-07-25 14:16:31** DENIED **
  
 ** PLEASE SEE THE FOLLOWING ITEMS ARE NEW COMMENTS
 BASED ON PLANS (ELECTRICAL RISER/SERVICE) BEING
 COMPLETELY REVISED FROM PREVIOUS SUBMITTED PLANS. AS
 THE PREVIOUS PLANS DID NOT CONTAIN THESE NEW ELECTRICAL
 PANELS, GUTTERS, MAINS ETC THESE ITEMS WERE NOT
 REVIEWED ON INITIAL REVIEW. ALL SERVICE EQUIPMENT ON
 PREVIOUS PLANS WERE SHOWN AS EXISTING.
  
 1) NOTE: PLEASE SEE PANEL *H* WHICH ON SCHEDULE IS
 SHOWING TO BE A 200AMP MAIN CIRCUIT BREAKER PANEL YET
 THE RISER MENTIONS THIS PANEL WILL NOW BE BACK FED TO
 THE EXISTING 150AMP SUB BRANCH BREAKER.THE RISER
 SHOWS 1/0 CONDUCTORS WHICH ARE NOW BEING FED FROM THE
 NEW GUTTER. IF PANEL *H* CONTAINS THE 200AMP MAIN
 CIRCUIT BREAKER AS STATED ON SCHEDULE THE CONDUCTORS
 ARE NOT OF SUFFICIENT SIZE PER 240.21,310.16,110.14.
 PLEASE ADJUST.
  
 2) NOTE: PLEASE SEE PANEL *H* AS THIS PANEL SHOWS 3/0
 CONDUCTORS YET THE RISER SHOWS 1/0 TAPPED CONDUCTORS.
 DEPENDING ON OVER CURRENT PROTECTION FOR TAPPED
 CONDUCTORS ARE NOTED ABOVE IN NOTE #1 THIS WILLNEED
 TO CHANGE AND COORDINATE.
 240.21,310.16 ETC
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 3) NOTE: PLEASE SEE THE NEW PANEL *S* WHICH BASED ON
 THE PANEL SCHEDULE IT SHOWS NEW FEEDERS TO BE 4-#3 AND
 1#8 FOR EQUIPMENT GROUNDING HOWEVER BASED ON THE RISER
 THE FEEDERS ARE SHOWN AS 4-#6 AND 1-#10 EQUIPMENT
 GROUND. PANEL SCHEDULE R1 STATES #6.
 PLEASE ALSO SEE THE PANEL IS NOTING THIS AS AN 18
 CIRCUIT PANEL YET THE PANEL IS SHOWN AS 42 CIRCUIT.
 WHICH WILL BE THE FEEDERS?
 310.16,240.4 ETC
 FBC 106.1.1, 106.1.2 FOR CLARITY AND COORDINATION.
  
 4) NOTE: PLEASE SEE PANEL *R1* AS THE RISER SHOWS THIS
 PANEL AS A 400AMP RATED PANEL WITH 400AMP MAIN CIRCUIT
 BREAKER YET THE PANEL *R1* SHOWS THIS PANEL AS A 225AMP
 RATED PANEL WITH A 200AMP MAIN. BASED ON THE LOAD ON
 PANEL THE PANEL MAY NOT CONTAIN A 200AMP BREAKER. THE
 LOAD EXCEEDS THE RATING OF THE 200AMP MAIN. PLEASE ALSO
 SEE THIS SAME PANEL IS NOTED WITH 30 CIRCUITS YET
 SCHEDULE INDICATES 42 CIRCUITS. CAN NOT BE 30 CIRCUITS
 AS THERE ARE BRANCH CIRCUITS SHOWN ABOVE THE 30
 CIRCUITS ON SCHEDULE.
 PLEASE ADJUST ALL DEVICES, PANEL RATINGS, MAINS,
 CIRCUITS ETC.
 240.21,408.36, 408.4 ETC
 FBC 106.1.1, 106.1.2 FOR CLARITY AND COORDINATION.
  
 5) NOTE: PLEASE SEE PANEL *H* WHICH STILL INDICATES A
 150AMP SUB BRANCH BREAKER TO FEED EXISTING TRANSFORMER
 YET THE RISER SHOWS THE TRANSFORMER NOW BEING FED FROM
 A NEW MAIN DISCONNECT TAPPED FROM THE GUTTER. BASED ON
 REVISED RISER THE TRANSFORMER IS NO LONGER BEING FED
 FROM PANEL *H*.
 408.4
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 6) NOTE: PLEASE SEE PREVIOUS COMMENTS IN REFERENCE TO
 ROOM 1514 WHICH IS NOTED ON PLANS AS A SERVER ROOM.
 THIS ROOM HAS SEPARATE AC EQUIPMENT, SEPARATE PANEL
 FEEDING TWO SERVERS AND THE RESPONSE WAS THE EPO BUTTON
 WAS REMOVED. THE PREVIOUS REVIEW NOTED STATED THAT IF
 THIS IS NOT AN IT ROOM BY NEC 645 DEFINITIONS THEN
 PLACE NOTE ON PLANS THAT WIRING METHODS IN NEC 645 ARE
 NOT PERMITTED. WIRING METHODS UNDER NEC 645 ARE LESS
 STRINGENT THAN CHAPTERS 1-4.
  
 7) NOTE: PLEASE SEE PANELS R2 AND R3 ARE BOTH SHOWN AS
 200AMP MAIN CIRCUIT BREAKER PANELS YET THE RISER SHOWS
 BOTH AS MAIN LUG ONLY.
 PLEASE COORDINATE.
 408
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 8) NOTE: PLEASE SEE THE MAIN ELECTRICAL ROOM HAS NOT
 BEEN REVISED ON PLANS TO SHOW NEW EQUIPMENT WITH NEW
 LOCATIONS.
 240.24, 110.26
 FBC 106.3.5.1.2, 106.1.1
  
 9) NOTE: PLEASE SEE THE FIXTURE *H* WHICH WAS MISSING
 THE FIXTURE DESIGNATION ON PREVIOUS PLANS INDICATES THE
 LIGHTING CONTROL CIRCUIT TO G2-2, YET THE SCHEDULE
 SHOWN ON E-5 DOES NOT LIST THE FIXTURE *H* UNDER G2-2
 ONLY FIXTURES *B* AND *BE* ARE LISTED.
 PLEASE REVISE CIRCUITING ON SCHEDULES ON SHEET E-5 AS
 THIS IS A NEW SHEET WITH NEW CIRCUITS FOR LIGHTING
 WHICH WAS NOT PART OF THE PREVIOUS REVIEWED PLANS. THIS
 IS NOT THE ONLY CIRCUIT WHICH DOES NOT COORDINATE. AN
 ADDITIONAL EXAMPLE IS CIRCUIT G2-6 AS THIS IS SHOWN AS
 A SPARE ON SHEET E-5 YET PLEASE SEE CORRIDOR 1510 ON
 PLANS AS FIXTURES *C* ARE CLEARLY SHOWN WITH THIS SAME
 CIRCUIT.
 PLEASE BE SURE TO GO OVER ALL NEW CIRCUITING AND
 SCHEDULE..
 FBC 13-415.1.ABC.1.1, .1.3.
 FBC 106.1.1.1
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-06-20 Cont ID  
Sent By dpalmer Date 2008-06-20 Time 10:05 Rev Time 0.00
Received By dpalmer Date 2008-06-20 Time 10:05 Sent To  
Notes
2008-06-20 10:05:29** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE VERIFY THE KEYPADS AND LOCATIONS WHICH
 APPEAR TO BE SHOWN ON PLANS WITH A K INSIDE A SQUARE.
 THIS REVIEWER COULD NOT LOCATE THIS ON THE SYMBOL
 LEGEND FOR TYPE OF DEVICE. PLEASE ALSO STATE THE
 MAXIMUM TIME FOR OVER RIDE OF THESE KEYPAD DEVICES.
 (MAXIMUM FOUR HRS FOR TIMER TYPE DEVICES AND 30MINS FOR
 OCCUPANCY SENSORS).
 PLEASE SEE THE LOCATIONS FOR KEYPADS ARE REQUIRED TO BE
 SHOWN AT ALL LOCATIONS SO THAT WHEN AN OCCUPANT IS
 ENTERING A SPACE THE LIGHTING CAN BE CONTROLLED AND THE
 OCCUPANT CAN VISUALLY SEE ALL LIGHTING WHICH IS BEING
 CONTROLLED.IF THE OCCUPANT CAN NOT VISUALLY SEE AL
 LIGHTING WHICH IS BEING CONTROLLED THEN DEVICES SUCH AS
 PILOT LIGHTS ARE REQUIRED AND WOULD NEED TO BE SHOWN ON
 PLANS.
 THERE IS A NOTE ON PLANS ON SHEET E-3 ON UPPER RIGHT
 HAND SIDE OF FLOOR LAYOUT WHICH STATES THE LOCATIONS OF
 KEYPADS ARE TO BE VERIFIED WITH ARCHITECT. THE
 LOCATIONS MAY BE VERIFIED WITH ARCHITECT HOWEVER THE
 MINIMUM LOCATIONS PER CODE NEED TO BE DETERMINED AND
 SHOWN ON PLANS.
 PLEASE SEE ONE LOCATION FOR EXAMPLE WHICH APPEARS TO BE
 IN THE RECEPTION AREA WHERE THE ASSUMED KEYPAD IS
 LOCATED INSIDE AND AROUND THE CORNER.
 IF ZONES ARE IN DESIGN PLEASE SHOW ZONES FOR ASSUMED
 KEYPADS. IF ALL COMMON AREA LIGHTING IS GOING TO BE
 CONTROLLED FROM ALL KEYPAD LOCATIONS AS NOTED ABOVE
 PILOT LIGHT CONTROL PANELS WITH ALL AREA DESIGNATIONS
 ARE REQUIRED.
 13-415.1.ABC.1.1, .1.2.
  
 2) NOTE: PLEASE SUBMIT SCHEDULING, AND INFORMATION ON
 PROPOSED LIGHTING CONTROLLED PANEL. PLANS SHOW A
 LIGHTING CONTROL PANEL HOWEVER NO OTHER INFORMATION FOR
 DEVICES ETC AS NOTED ABOVE IS SHOWN.
 13-415.1.ABC.1, NEC 110.3, 90.7
 FBC 106.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 3) NOTE: PLEASE SEE 13-415.1.ABC.1.3 FOR REQUIRED
 ADDITIONAL CONTROLS.
 CONTROLS ARE REQUIRED IN THE FOLLOWING CASES: 1.DISPLAY
 OR ACCENT LIGHTING. DISPLAY OR ACCENT LIGHTING SHALL
 HAVE A SEPARATE CONTROL.
  
 4) NOTE: PLEASE LABEL THE FIXTURES SHOWN IN WAITING
 RECEPTION AREA 1502 WHICH ARE SHOWN DIAGONALLY ACROSS
 THE CEILING AREA. NO FIXTURE DESIGNATION COULD BE
 LOCATED AT OR NEAR THESE FIXTURES AND COMPLIANCE WITH
 LIGHTING CONTROLS ABOVE, LIGHTING PERFORMANCE
 CALCULATIONS AND LIGHTING FIXTURE LEGEND NEED TO BE
 VERIFIED.
 13-415.2.ABC.1.1, .1.2, 13-415.2, 13-415.1.ABC.1.3.
  
 5) NOTE: PLEASE STATE AND SHOW THE MINIMUM LEVELS FOR
 ADA COMPLIANCE FOR HORN AND STROBE LEVELS.
 PLEASE SEE FBC 11-4.28.1, .2 AND .3(4).
  
 6) NOTE: PLEASE SEE PLANS WHICH APPEAR TO BE SHOWING AN
 EPO EMERGENCY POWER OFF BUTTON AT SERVER ROOM DOOR.
 PLANS ALTHOUGH DO NOT APPEAR TO BE SHOWING A ONE HOUR
 WALL AROUND ROOM BASED ON ARCHITECTURAL PLANS. BASED ON
 THE ROOM AS SHOWN NOT FALLING UNDER AN IT ROOM PER
 645.2 DEFINITIONS PLEASE PLACE A NOTE ON ELECTRICAL
 PLANS WHICH NEEDS TO STATE * ALL WIRING METHODS SHALL
 MEET CHAPTERS 1-4* WIRING METHODS IN 645 ARE NOT
 PERMITTED.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-07-23 Cont ID  
Sent By mwennerg Date 2008-07-23 Time 13:19 Rev Time 0.00
Received By mwennerg Date 2008-07-23 Time 13:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-06-30 Cont ID  
Sent By mawillia Date 2008-06-30 Time 15:38 Rev Time 0.00
Received By mawillia Date 2008-06-30 Time 14:44 Sent To  
Notes
2008-06-30 15:38:41*****PROVISO*****
  
 1.ON SHEET A1.0, DOORS 1530, 1531, AND 1532 TO BE
 EQUIPPED WITH SELF CLOSERS SO THAT THE DOORS CLOSES AND
 LATCHES UPON RELEASE.
  
  
 *******************************************************
 *******************************************************
 *******************************************************
 ***********
 PLAN SHEET A-1.0, A-1.3, FA-1, AND FS2.1 TO BE
 FIRE-STAMPED WHEN THE OTHER REVIEWERS COMMENTS' AS WELL
 AS THE ABOVE COMMENT HAS BEEN ADDRESSED.
 *******************************************************
 *******************************************************
 *******************************************************
 ************
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-10-14 Cont ID  
Sent By adarroug Date 2008-10-14 Time 09:37 Rev Time 0.00
Received By adarroug Date 2008-10-14 Time 09:37 Sent To M
Notes
2008-10-14 09:41:56TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-09-22 Cont ID  
Sent By adarroug Date 2008-09-22 Time 13:54 Rev Time 0.00
Received By adarroug Date 2008-09-22 Time 13:54 Sent To  
Notes
2008-09-22 13:57:35TO "COMM" BD#9

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-09-22 Cont ID  
Sent By adarroug Date 2008-09-22 Time 13:48 Rev Time 0.00
Received By adarroug Date 2008-09-22 Time 13:48 Sent To M
Notes
2008-09-22 13:49:02TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-07-31 Cont ID  
Sent By adarroug Date 2008-07-31 Time 12:41 Rev Time 0.00
Received By adarroug Date 2008-07-31 Time 12:41 Sent To E
Notes
2008-07-31 12:41:29TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-14 Cont ID  
Sent By adarroug Date 2008-07-14 Time 09:14 Rev Time 0.00
Received By adarroug Date 2008-07-14 Time 09:14 Sent To  
Notes
2008-07-14 09:21:17TO "COMM" BD#12/PLANS ON RACK/1 ROLL/FOLDED PLANS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-30 Cont ID  
Sent By mawillia Date 2008-06-30 Time 14:44 Rev Time 0.00
Received By mawillia Date 2008-05-22 Time 16:56 Sent To  
Notes
2008-05-29 11:26:48TO "COMM" BD#10
2008-05-22 16:56:21WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-11-02 Cont ID  
Sent By rregueir Date 2008-11-02 Time 14:34 Rev Time 0.00
Received By rregueir Date 2008-11-02 Time 14:34 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-10-11 Cont ID  
Sent By rregueir Date 2008-10-11 Time 14:49 Rev Time 0.00
Received By rregueir Date 2008-10-11 Time 14:49 Sent To PC
Notes
2008-10-11 14:49:46REVISED CFM VALUES SK-1

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-10-07 Cont ID  
Sent By rregueir Date 2008-10-07 Time 08:32 Rev Time 0.00
Received By rregueir Date 2008-10-03 Time 16:48 Sent To E
Notes
2008-10-07 08:32:35REVISED M2.1 AND M6.1

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-07-23 Cont ID  
Sent By rregueir Date 2008-07-23 Time 16:56 Rev Time 0.00
Received By rregueir Date 2008-07-23 Time 14:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-06-20 Cont ID  
Sent By rregueir Date 2008-06-20 Time 13:50 Rev Time 0.00
Received By rregueir Date 2008-06-20 Time 10:20 Sent To  
Notes
2008-06-20 13:50:33REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PLANS ARE CODE COMPLIANT. HOWEVER, THERE ARE TWO
 OUTSTANDING ISSUES WHICH SHALL BE RESOLVED PRIOR TO
 PERMIT ISSUANCE:
  
 1. PG M2.1: IT IS UNCLEAR AT THIS TIME OF SERVER ROOM
 1514 WILL BE CLASSIFIED AS AN I.T. ROOM. PLEASE SEE
 ELECTRICAL COMMENTS. A 1-HOUR RATING MAY BE REQUIRED AT
 THE WALLS OF THIS ROOM. IN THIS CASE, THE DUCT
 PENETRATIONS INTO THIS ROOM WILL NEED TO BE PROTECTED
 IN ACCORDANCE WITH FBCM 607.5.
  
 2. PG M7.1: DETAIL #5 CALLES FOR A PRE-ENGINEERED A/C
 STAND TO BE INSTALLED. THESE STANDS ARE DEFINED AS
 STRUCTURAL COMPONENTS BY FAC RULE 9B-72 AND PRODUCT
 APPROVAL IS REQUIRED. PLEASE PROVIDE PRODUCT APPROVAL
 DOCUMENTATION APPROVED IN WRITING BY THE DESIGNER OF
 RECORD IN ACCORDANCE WITH FBCB 106.3.3. FOR MORE
 INFORMATION ON THE FLORIDA PRODUCT APPROVAL SYSTEM
 PLEASE VISIT WWW.FLORIDABUILDING.ORG.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-07-22 Cont ID  
Sent By kstevens Date 2008-07-22 Time 12:51 Rev Time 0.00
Received By kstevens Date 2008-07-22 Time 12:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-06-11 Cont ID  
Sent By kstevens Date 2008-06-11 Time 15:48 Rev Time 0.00
Received By kstevens Date 2008-06-11 Time 15:48 Sent To  
Notes
2008-06-11 16:01:27DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT A-5.1 DETAIL #10PER SECTION 11-4.24.3 KNEE
 CLEARANCES OF AT LEAST 27" HIGH, 30" WIDE AND 19" DEEP
 IS REQUIRED UNDER THE ACCESSIBLE SINK. DETAIL #10 DOES
 NOT COMPLY AS THERE IS A GARBAGE DISPOSAL IN THE
 CLEARANCE.PLEASE DELETE THE GARBAGE DISPOSAL OR
 INDICATE A CODE COMPLIANT SINK WITH THE DRAIN IN THE
 BACK AND AN ADA APPROVED GARBAGE DISPOSAL THAT IS NOT
 IN THE KNEE CLEARANCE.
  
 2. SHT A-5.1 DETAIL #7 LAV DETAIL REQUIRES 6" MAXIMUM
 AT THE BOTTOM OF THE CLEARANCE. IT SCALES OUT AT 7-1/2"
 AT THE BOTTOM WHICH CHANGES THE ANGLE OF THE NEW PLAS
 LAM 3/4" PLYWOOD. PLEASE INDICATE THE 6" REQUIRED AS
 SHOWN IN FIGURE 11-32.
  
 3. SHT P2.2 WATER ISOMETRIC RISER DIAGRAM. SHOW THE
 PIPING TO AND FROM THE INSTA HOT WATER HEATERS FOR THE
 SINKS. SECTION 106.3.5.1.3.--SHOW THE WATER HAMMER
 ARRESTORS REQUIRED AT THE ICE MAKERS AND DISH WASHERS
 SECTION 604.9.--RISER SHOWS COLD WATER TO THE
 DISHWASHERS. PLUMBING KEY NOTE #3 ON SHT P2.1 INDICATES
 HOT WATER TO THE DISH WASHERS. PLEASE CLARIFY &
 CORRELATE.
  
 4. SHT P4.1 DETAIL #4 INDICATES STOP VALVES FOR SINK
 COLD WATER WITH A PORT TO SHUT OFF THE WATER TO THE
 WATER HEATER. PER SECTION 606.1(7) A FULL OPEN VALVE IS
 REQUIRED ON THE WATER SUPPLY PIPE TO THE WATER HEATER.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]