2008-06-19 12:34:43 | ** DENIEDREVIEW ** |
| |
| |
| 1) NOTE:PLEASE SEE THAT PLANS AND DOCUMENTS NEEDED TO |
| BE SUBMITTED ARE NOT COMPLETE AT THIS TIME. THERE MAY |
| VERY WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH |
| CAN NOT BE MADE AT THIS TIME DUE TO LACK OF INFORMATION |
| AND CODE COMPLIANCE. |
| |
| 2) NOTE: PLEASE SEE ATTACHED PRINT OUT FROM THE |
| DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION.AT |
| THE TIME OF THIS REVIEW THE PRINT OUT INDICATES THE |
| ARCHITECT OF RECORD AS SIGNED, DATED AND SEALED ON |
| PLANS LICENSE WAS SUSPENDED IN JULY 2007. THIS LICENSE |
| IS NOT CURRENT AS SHOWN BY THE STATE AND PLANS MAY NOT |
| BE SIGNED, DATED AND SEALED BY THIS ARCHITECT AS |
| SHOWN. |
| ** CONTACT HAS BEEN MADE TO THE BOARD OF ARCHITECTS |
| LEGAL COUNSEL TO VERIFY THE STATE WEBSITE INFORMATION |
| AS SHOWN IS ACCURATE. |
| |
| 3) NOTE: PLEASE BE SURE TO COMPLETE ALL CIRCUITING ON |
| PLANS AND CORRELATE WITH THE SUBMITTED PANEL |
| SCHEDULES. |
| PLEASE SEE MOST OF DEVICES WHICH DO NOT INDICATE ANY |
| CIRCUITS AND MANY CIRCUITS WHICH DO NOT CORRELATE WITH |
| THE SUBMITTED SCHEDULES. THERE ARE SEVERAL CODES WHICH |
| MINIMUM CIRCUITING CAN NOT BE VERIFIED FOR CODE |
| COMPLIANCE AT THIS TIME. |
| FBC ADMIN SECTION 106.3.5.1.2, 106.5.4 |
| NEC 408.4, 240.4, 310.16, 210.52, 210.11 ETC |
| |
| 4) NOTE: PLEASE BE SURE PLANS REFERENCE THE CURRENT |
| CODES IN EFFECT AS LISTED. |
| NFPA-101 2003, NFPA-72 2002, NFPA-70 2005, AND 2004 FBC |
| W/ 2007 REVISIONS. |
| |
| 5) NOTE: PLEASE SUBMIT COMPLETED ENERGY CALCULATIONS |
| FOR ALL AREAS WHICH ARE APPLICABLE FOR USE AND |
| OCCUPANCY. PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2 |
| AND .1.3 FOR LIGHTING PERFORMANCE CALCULATIONS. PLEASE |
| SEE 13-400.3.A, 13-400.3.B, 13-400.3.C, 13-101.3. AS |
| THE MINIMUM REQUIRED CALCULATIONS WERE NOT SUBMITTED |
| MINIMUM CODE COMPLIANCE HAS NOT BEEN MET OR VERIFIED. |
| |
| 6) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AS THE FOLLOWING |
| WORDING IS REQUIRED TO BE ON PLANS. |
| CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT WITHIN 30 |
| DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD |
| DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDED |
| TO THE BUILDING OWNER, INCLUDING:13-413.1.ABC.2.2 |
| MANUALS. |
| CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT AN OPERATING |
| MANUAL AND MAINTENANCE MANUAL BE PROVIDED TO THE |
| BUILDING OWNER. THE MANUALS SHALL INCLUDE, AT A |
| MINIMUM, THE FOLLOWING: |
| 1. SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED |
| OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING |
| MAINTENANCE. |
| 2. OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH |
| PIECE OF EQUIPMENT REQUIRING MAINTENANCE. REQUIRED |
| ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY |
| IDENTIFIED. |
| 3. NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED |
| SERVICE AGENCY. |
| NOTE: ENFORCEMENT AGENCIES SHOULD ONLY CHECK TO BE SURE |
| THAT THE CONSTRUCTION DOCUMENTS REQUIRE THIS |
| INFORMATION TO BE TRANSMITTED TO THE OWNER AND SHOULD |
| NOT EXPECT COPIES OF ANY OF THE MATERIALS. |
| SOME TEXT ABOVE WAS TAKEN DIRECTLY FROM THE FBC FOR |
| EASE OF CORRECT WORDING REQUIRED ON PLANS. |
| |
| 7) NOTE: PLEASE SEE THE RISER SUBMITTED IS NOT COMPLETE |
| AT THIS TIME. PLEASE SEE NO MAINS, NO OVER CURRENT |
| PROTECTION FOR PANELS, MAINS ETC WERE SUBMITTED OR |
| SHOWN. |
| PLEASE SUBMIT A COMPLETE RISER DIAGRAM MEETING MINIMUM |
| CODE COMPLIANCE FOR SERVICES. 230.70,230.71,230.72, |
| 215.5, 310.16, 240.4 ETC |
| ** |
| 8) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING |
| CONDUCTOR TO EACH PANEL. |
| 250.110,250.122, 250.24 ETC. |
| |
| 9) NOTE: PLEASE SEE GROUNDING ELECTRODE SYSTEM MENTIONS |
| TO ATTACH TO FOOTER STEEL? PLEASE KNOW IN AN EXISTING |
| BUILDING, IT IS NOT REQUIRED AND IS NOT RECOMMENDED DUE |
| TO THE STRUCTURAL INTEGRITY OF THE EXISTING |
| STEEL/FOOTER. |
| PLEASE KNOW HOWEVER THIS IS PERMITTED AND IF SHOWN ON |
| RISER, IT WILL BE REQUIRED. |
| 250.50 |
| |
| 10) NOTE: PLEASE SEE 250.66 FOR SIZING OF GROUNDING |
| ELECTRODE CONDUCTOR AS THIS IS CURRENTLY SHOWN AS A |
| "6/0"? PLEASE KNOW THIS IS NOT A RECOGNIZED STANDARD IN |
| THE NATIONAL ELECTRICAL CODE OR THE AMERICAN WIRE GAUGE |
| STANDARD. PLEASE ADJUST AS NEED BASED ON SERVICE |
| ENTRANCE CONDUCTORS WHICH WILL BE BASED ON LOAD |
| CALCULATIONS.PLEASE BE SURE TO SEE COMMENTS BELOW FOR |
| MINIMUM SERVICE ENTRANCE CONDUCTORS TO VERIFY. |
| |
| 11) NOTE: PLEASE SEE NOTE WITH RESPECT TO LOAD |
| CALCULATIONS. AS THE SUBMITTED CALCULATIONS DO NOT |
| MINIMUM CODE COMPLIANCE THE SIZE OF THE EXISTING |
| SERVICE ENTRANCE CONDUCTORS AS SHOWN ON RISER CAN NOT |
| BE VERIFIED. |
| |
| 10) NOTE: PLEASE SUBMIT AIC RATINGS FOR ALL NEW SERVICE |
| EQUIPMENT BEING INSTALLED. PLEASE SEE 110.9 AS MAINS, |
| BREAKERS AND ALL SERVICE EQUIPMENT IS REQUIRED TO RATED |
| FOR THE AVAILABLE FAULT CURRENT. |
| PLEASE SEE NOTE #20 AS LISTED ON E-2 WHICH MENTIONS TO |
| USE FUSES HOWEVER AS NO INFORMATION IS SHOWN ON RISER |
| FOR ANY MAINS, SERVICE EQUIPMENT ETC THESE CAN NOT BE |
| VERIFIED. |
| |
| 12) NOTE: PLEASE SHOW LOAD CALCULATIONS MEETING THE |
| 2005 NEC> PLEASE SEE THE CODE SECTIONS REFLECTED ON |
| PLANS ARE NOT FROM THE 2005 NATIONAL ELECTRICAL CODE. |
| PLEASE SEE THE COMMERCIAL PORTION OF THE BUILDING |
| ACTUALLY SHOWS *RESIDENTIAL* LOAD CALCULATIONS. HOW IS |
| THIS POSSIBLE? WHERE IN THE NEC DOES IT PERMIT |
| RESIDENTIAL LOAD CALCULATIONS IN COMMERCIAL OFFICE |
| SPACE? |
| PLEASE SEE 220.12, 220.14, 220.42, 220.43, ETC. PLEASE |
| BE SURE TO SHOW ALL CONTINUOUS LOADS AT 125% PER 215.3, |
| 230.42 ETC. |
| AS CALCULATIONS ARE NOT COMPLETE AND THERE IS MUCH NEED |
| FOR COORDINATION PLEASE KNOW NEW COMMENTS MAY ARISE |
| ONCE THESE ARE RESUBMITTED. |
| |
| 13) NOTE: PLEASE SEE COMMON AREAS ON PLANS WILL REQUIRE |
| SOME SORT OF *HOUSE/COMMON* ARE PANEL. THESE CIRCUITS |
| IN THESE AREAS MAY NOT BE FED FROM THE APARTMENT UNITS |
| OR COMMERCIAL TENANT SPACE. |
| 210.25 ETC. AS MOST OF THE CIRCUITING IS NOT SHOWN MOST |
| ITEMS CAN NOT BE VERIFIED FOR MINIMUM CODE COMPLIANCE. |
| |
| 14) NOTE: PLEASE SHOW ALL PANEL LOCATIONS FOR |
| VERIFICATION OF CODE COMPLIANCE. |
| 110.26,240.24 ETC. |
| FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION |
| AND COORDINATION. |
| |
| 15) NOTE: PLEASE CORRELATE ALL LOAD FOR A/C SYSTEMS, AS |
| MECHANICAL PLANS INDICATE 10KW UNITS, LOAD |
| CALCULATIONS |
| INDICATE BOTH 9KW LOAD AND 5KW LOAD AND PANEL SCHEDULES |
| INDICATE 5KW HEAT FOR ALL?? |
| PLEASE ADJUST LOAD CALCULATIONS AND COORDINATE OTHER |
| COMMENTS. |
| |
| 16) NOTE: PLEASE SEE 424.3B WHICH REQUIRES ALL MINIMUM |
| OVER CURRENT PROTECTION FOR AIR HANDLER UNIT HEAT TO BE |
| SIZED AT A MINIMUM OF 125%. |
| PLEASE SEE PANEL SCHEDULES SHOWS 50A, #6 AWG ON 5KW |
| UNITS. |
| |
| 17) NOTE: PLEASE SEE CONDUCTORS SHOWN FOR RANGE/OVENS |
| WHICH DO NOT SHOW ANY NEUTRAL CONDUCTOR AS REQUIRED PER |
| 250.140 |
| |
| 18) NOTE: PLEASE SEE MISSING MINIMUM DISCONNECTS FOR |
| ALL AIR CONDITIONING EQUIPMENT. AS NOT ALL EQUIPMENT IS |
| CURRENTLY SHOWN PLEASE BE SURE TO SEE 440.11 AND 110.26 |
| AND SHOW LOCATIONS OF ALL REQUIRED DISCONNECTS. |
| |
| 19) NOTE: PLEASE SEE MISSING REQUIRED GFI SERVICE |
| RECEPTACLE FOR OUTSIDE CONDENSING UNITS.210.63, |
| 210.8A3, 210.8B4. |
| |
| 20) NOTE: PLEASE SEE AN ELEVATOR IS SHOWN ON PLANS, |
| HOWEVER THERE IS NO INDICATION ON ANY PLANS OF THIS |
| EQUIPMENT OR EQUIPMENT ROOM. |
| PLEASE SHOW LOCATION OF EQUIPMENT. |
| PLEASE SEE 620.23, 620.24 FOR MISSING REQUIRED |
| DEDICATED CIRCUITS. PLEASE SEE SAME SECTIONS AS |
| RECEPTACLE SHALL BE GFI PROTECTED. |
| PLEASE SEE 700.16 FOR MISSING BACK UP LIGHT DEPENDING |
| ON LOCATION OF EQUIPMENT. |
| |
| 21) NOTE: PLEASE SEE 13-415.1.ABC.1.4 FOR REQUIRED |
| CONTROL OF OUTSIDE LIGHT. SOME LIGHTS NOTE TO BE |
| CIRCUITED TO A TC (ASSUMING TIME CLOCK) HOWEVER PLEASE |
| SEE CURRENT CODE SECTION GIVEN AS A STANDARD TIME CLOCK |
| IS NOT ACCEPTABLE. |
| PLEASE PROVIDE ONE OF TWO ACCEPTABLE METHODS AND |
| INDICATE ON PLANS. |
| PLEASE BE SURE TO SEE NOTES ABOVE WITH RESPECT TO |
| COMMON AREAS WHICH OUTSIDE LIGHTING WOULD BE TO NEW |
| HOUSE PANEL ETC. |
| |
| 22) NOTE: PLEASE SEE THE MISSING REQUIRED DEDICATED |
| SIGN CIRCUIT AS PER 600.5 |
| |
| 23) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR |
| MINIMUM LIGHTING LEVELS UNDER THE 2003 NFPA-101 LIFE |
| SAFETY CODE FOR EGRESS PATHS AND STAIRS. |
| PLEASE SEE 7.8.1.3, 7.9.2.2. |
| PLEASE KNOW AS THESE ARE COMMON AREAS, CONTROLS AND |
| CIRCUITING NEED TO BE ADJUSTED ACCORDING. |
| |
| 24) NOTE: PLEASE SEE PLANS SHOW SD FOR SMOKE DETECTORS |
| AS DEFINED IN NFAP-72. IF THESE ARE TRULY SMOKE |
| DETECTORS WHICH ONLY DETECT AND DO NOT SOUND AN ALARM |
| PLEASE SUBMIT THE COMPLETE FIRE ALARM SYSTEM INCLUDING |
| HORNS, FIRE ALARM PANEL ETC. |
| PLEASE SEE THE COMMON AREAS MAY NOT HAVE THE |
| RESIDENTIAL UNITS SMOKE ALARMS DEVICES WIRED INLINE OR |
| SAME CIRCUITS. |
| PLEASE ADJUST. |
| PLEASE SEE THE DEFINITIONS FOR SMOKE ALARMS AND SMOKE |
| DETECTORS AND ADJUST DESIGN ACCORDINGLY. |
| |
| 25) NOTE: PLEASE PROVIDE A FIXTURE LEGEND/SCHEDULE AND |
| CORRELATE WITH THE PLANS. PLEASE BE SURE THE FIXTURE |
| LEGEND IS COMPLETE FOR ALL COMMON AREAS AND OFFICE |
| AREAS. PLEASE INCLUDE AREAS FOR RESIDENTIAL ALSO WITH |
| RESPECT TO THE RECESSED LIGHTING FIXTURES. |
| 13-415.2.ABC.1, 13-415.2 FOR COMMERCIAL, |
| 13-606.1.ABC.1.2.4 FOR RESIDENTIAL. |
| |
| 26)NOTE: PLEASE BE SURE TO SEE 700.12F FOR CIRCUITING |
| OF REQUIRED EMERGENCY AND EXIT LIGHT FIXTURES. |
| |
| 27) NOTE: PLEASE SEE 210.8A2WHICH REQUIRES A;; |
| RECEPTACLES IN BATHROOMS TO BE SHOWN AS GFI/GFI |
| PROTECTED. SOME ARE AND SOME ARE NTO. |
| |
| 28) NOTE: PLEASE SEE 210.52D, 210.11C3 FOR MISSING |
| REQUIRED DEDICATES BATH CIRCUITS. MUST BE 20AMP AND #12 |
| MINIMUM. |
| |
| 29) NOTE: PLEASE SEE NFPA-72 11.8.3 FOR LOCATIONS AND |
| TYPES OF SMOKE DETECTION DEVICES WITHIN 20FT OF COOKING |
| APPLIANCES. |
| PLEASE ALSO SEE NOTE ON PLANS WHICH MENTIONS SMOKE |
| DETECTORS ARE TO BE WIRED AHEAD OF THE SWITCHES ON |
| EITHER BATH OR KITCHEN LIGHTING CIRCUIT, PLEASE SEE |
| THIS IS OK, HOWEVER ARC FAULT PROTECTION WILL THEN BE |
| REQUIRED FOR THOSE LIGHTING CIRCUITS. |
| 210.12 NEC |
| |
| 31) NOTE: PLEASE LIST ALL THE REQUIRED ARC FAULT |
| PROTECTED CIRCUITS AS REQUIRED PER 2005 NEC 210.12B. |
| PLEASE SEE COMMENTS ABOVE AS THE CIRCUITS SHALL BE |
| SPECIFIC AND AS OTHER COMMENTS HAVE AFFECTED DEDICATED |
| CIRCUITS PER NOTES PLEASE BE SURE TO COORDINATE. |
| |
| 32) NOTE: PLEASE BE SURE TO SEE 220.52, 210.52B1 FOR |
| DINING ROOM/AREA CIRCUITING. |
| |
| 33) NOTE: PLEASE SEE MANY CIRCUITS ON PLANS MENTIONS |
| *GENERAL LIGHTS* AND GENERAL RECEPTACLES*. |
| PLEASE SEE 408.4 AS ALL CIRCUITING SHALL BE SPECIFIC TO |
| ROOMS AND AREAS IN WHICH THEY FEED. |
| FBC 106.1.2, 106.3.5.1.2, 106.3.5.4 |
| |
| 34) NOTE: PLEASE BE SURE TO LABEL APARTMENT UNITS ON |
| ELECTRICAL PLANS. *A*, *B* ETC |
| FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| REVIEW FOR CIRCUITING WILL NEED TO BE DONE. |
| |
| 35) NOTE: PLEASE SEE 422.30, 422.31 FOR MISSING |
| DISCONNECTS FOR WATER HEATERS. |
| |
| 36) NOTE: PLEASE SEE 210.52 FOR MISSING RECEPTACLES. |
| (REDLINED ON ONE SET OF PLANS. |
| |
| 37) NOTE: PLEASE SEE PLANS FOR OFFICE WHICH SHOWS A |
| CIRCUIT FOR WHAT IS LISTED ON PANEL SCHEDULE AS BEING A |
| MICROWAVE # 14, HOWEVER NO DEVICE OR LOCATION IS SHOWN |
| ON PLANS. |
| |
| 38) NOTE: PLEASE SEE SWITCHES WHICH ARE SHOWN WIRED TO |
| A 3-WAY SYSTEM ON STAIRS, HOWEVER DO NOT INDICATE BEING |
| S3. |
| PLEASE SEE MINIMUM LIGHTING CONTROLS FOR EGRESS |
| LIGHTING IN FBC CHAPTER 10 AND NFPA-1017.8 |
| PLEASE SEE OTHER AREAS OF PLANS IN WHICH 3-WAY |
| SWITCHING IS SHOWN HOWEVER THE 3-WAY SWITCH IS ONLY |
| SHOWN AT ONE END WHEN IT MUST BE AT MORE THAN ONE |
| LOCATION. |
| |
| 39) NOTE: PLEASE SEE THE ELECTRICAL PLANS AS THE PLANS |
| ARE MISSING 210.63, 210.70 COMPLIANCE FOR AIR HANDLING |
| UNITS. |
| AS THESE WERE NOT SHOWN ON ELECTRICAL PLANS THE |
| MECHANICAL PLANS WERE LOOKED AT HOWEVER THIS BECAME |
| MORE CONFUSING AS PACKAGE UNITS AND SPILT SYSTEMS WERE |
| SHOWN. |
| IF THESE UNITS ARE PACKAGE UNITS ON ROOF, THEN WHY ARE |
| THERE CONDENSING UNITS SHOWN ON THE GROUND FLOOR |
| OUTSIDE LEVEL? |
| IT IS UNCLEAR WHAT THE DESIGN IS GOING TO BE AS SPILT |
| SYSTEMS ARE ALSO LISTED ON EQUIPMENT SCHEDULE. PLEASE |
| COORDINATE ALL AND SEE NOTES ABOVE WITH RESPECT TO |
| MISSING DISCONNECTS, COORDINATION OF HEAT STRIPS, OVER |
| CURRENT PROTECTIONS, GFI RECEPTACLES, LIGHTS ETC. |
| |
| 40) NOTE: PLEASE SEE MISSING GFI DESIGNATIONS FOR |
| GARAGE RECEPTACLES. |
| 210.8A2, 5 |
| |
| 41) NOTE: PLEASE SEE MISSING CONTROL FOR EXHAUST FAN ON |
| FIRST FLOOR BATHROOM. |
| FBC 106.1.2 |
| |
| 42) NOTE: PLEASE SEE ELECTRICAL RISER CLEARLY STATES |
| THE FEEDERS AS NOTED WILL BE TYPICAL OF *FOUR* (4) YET |
| THE PLANS ONLY SHOW THREE SPACES, THREE PANELS ETC. |
| PLEASE CLEAR THIS UP AND COORDINATE. |
| |
| 43) NOTE: BASED ON COMMENTS ABOVE ONE SET OF PLANS ARE |
| BEING RETAINED BY THIS OFFICE. |
| |
| |
| ** IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| HESITATE IN CONTACTING THIS OFFICE. |
| |