Plan Review Details - Permit 08050627
Plan Review Stops For Permit 08050627
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-17 Cont ID  
Sent By jwitmer Date 2008-06-17 Time 15:54 Rev Time 6.66
Received By jwitmer Date 2008-06-17 Time 15:51 Sent To  
Notes
2008-06-17 15:58:16BUILDING PLAN REVIEW
 PERMIT: 08050627
 ADD: 421 24TH ST
 CONT: ALONSO & ASSOCIATES, INC.
 TEL: (561)253-5350
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS,
 PLEASE UPDATE PLANS TO REFLECT THE CURRENT 2007
 SUPPLEMENTSAND CORRECTED WIND SPEED OF 140 MPH 3 SECOND
 WIND GUST. NOTE AS-1 ONLY NEEDS TO UPDATE TO THE 2007
 SUPPLEMENTS, A-8 MAKES REFRENECE TO THE 2001 FBC
 NUMEROUS TIMES, ALSO TO THE SOUTH FLORIDA BUILDING
 CODE, ASCE -7-98, ASCE7-88.
  
 2) PLEASE PROVIDE 2 ORIGINAL SOILS REPORTS SIGNED AND
 SEALED.1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 3)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4) SHEET A-1 & A-2INDICATE A ELEVATOR WITH THE EGRESS
 STAIRS SURROUNDING THE ELEVATOR ON THREE OF THE FOUR
 SIDES, WHICH IS LOCATED WITHIN THE VERTICAL EXIT.
  
 1019.1 INDICATES AN EXIT ENCLOSURE SHALL NOT BE USED
 FOR ANY PURPOSE OTHER THAN MEANS OF EGRESS.1019.1.1
 OPENINGS INTO EXIT ENCLOSURES SHALL BE LIMITED TO THOSE
 NECESSARY FOR THE EXIT ACCESS TO THE ENCLOSURE FROM
 FORMALLY OCCIED SPACES ANDFOR EGRESS FROM THE
 ENCLOSRE, NOT TO COMMUNICATE AS A CORRIDOR BETWEEN
 OFFICES.
  
 THE SECOND ISSUE WITH THE FIRST FLOOR DESIGN IS THE
 CORRIDOR WHICH IS WITHIN THE VERTICAL EXIT IS A
 HORIZONTAL EXTENSIONOF THE VERTICAL EXIT OR A EXIT
 PASSAGE WAY. PLEASE SEE 1020.4 ELEVATORS SHALL NOT OPEN
 INTO AN EXIT PASSAGEWAY.
  
 5) A-1 THE WALL COMMON TO THE STORAGE ROOM AND THE
 VERTICAL EXIT IS MISSING THE UL FASSEMBLY NUMBER
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 6) SHEET A-1 THE BREAK AREA INDICATES A SIDE APPROACH
 TO THE SINK, PLEASE SEE 11-4.24.2 HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER OR RIM NO HIGHER THAN 34"
 ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 7) SHEET A1 & A-4 BOTH INDICATE THE LOWER ROOF LINE
 ENCROACHES 1'-6" OVER THE PROPERTY LINE, PLEASE REVIEW
 3202.3.2 FOR ALLOWABLE PROJECTIONS INTO THE RIGHT OF
 WAY.
  
 8) SHEET A-7 WINDOW DETAIL B USE OF WOOD BUCKS, PLANS
 INDICATE THE WOOD BUCK BEVELED AND CUT SHORT OFTHE BACK
 HALF OF THE FRAME, 1714.5.4.2 BUCKS SHALL EXTEND BEYOND
 THE INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED.
  
 9) SHEET A-6 TYPICAL WALL SECTION A,PLANS DOES NOT
 INDICATE ON THE KNEE WALL THAT SUPPORT THE SLOPED
 TRUSSES WHAT TYPE OF INSULATION THIS WILL BE? PLEASE
 PROVIDE PRODUCT APPRVAL OR TESTING REPORT FOR THE
 ICYNNE INSULATION THAT WILL BE INSTALLED IN THE
 TRUSSES.
  
 10) SHEET A-7 THE TENNANT SEPERATION WALL WILL NEED TO
 COMPLY WITH 1207.2 AIR-BORNE SOUND TRANSIMTION OF NOT
 LESS THAN 50 STC.
  
 11) SHEET A-7 STRUCTURE -BORNE SOUND FLOOR/ CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS AND OR PUBLIC OR
 SERVICE AREASW WITHIN THE STRUCTURE SHALL HAVE A STC
 RATING OF NOT LESS THAN 50.
  
 12) SHEET A-8 WIRE LATH NOTE INDICATES COMPLIANCE WITH
 THE SOUTH FLORIDA BUILDING CODE, PLEASE UPDATE TO FBC
 2510.3- ASTM C 1063.
  
 13) SHEET A-8 HANDRAIL DETAIL, THE HANDRAIL SHALL
 EXTEND 11" BEYOND THE LAST RISER, 1009.11.5.
  
 14) AC-2 ROOFTOP UNITS WITH CURBS DO NOT INDICATE HOW
 THEY WILL BE ATTACHED TO THE ROOF DECK, PLANS ALSO SEE
 STRUCTURAL FRAMING FOR SUPPORT FRAMING, STRUCTURAL
 PLAANS DO NOT INDICATE ANY ADDITIONAL SUPPORT, 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 15) PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 16) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 17) PGT CASEMENT WINDOWS- PLEASE PROVIDE DOCUMENTATION
 ON THE CLEAR WIDTH OF THE WINDOWS, FROM THE PRODUCT
 APPROVAL THE 26.5 INCH CASEMENT WINDOW WILL END UP WITH
 LESS THAN 20 INCHES CLEAR, 1025.2.1 REQUIRES A MINIMUM
 CLEAR OPENING OF 20" FOR EGRESS WINDOWS.
  
 18) GAF BUILT UP ROOF SYSTEM: PLEASE INDICATE WHICH
 SUB-SYSTEM THAT IS INTENDED TO BE INSTALLED ON THIS
 STRUCTURE. NOTE MOST OFTHESE SYSTEMS HAVE LOW PRESSURES
 AND WILL NEED ENHANCED FASTENING IN ZONES 2 & 3.
  
 19) SHEETS 6 & 7 THE TENANT SEPERATION WALL PLEASE
 INDICATE COMPLIANCE WITH 708.4.1 ROOF CONSTRUCTION.
 WHEN THE FIRE PARTITION IS CONTINUOUS TO THE UNDERSIDE
 OF THE ROOF SHEATHING IN OCCUPANCIES OF GROUPS R-1, R-2
 AND R-3 AS APPLICABLE IN SECTION 101.2 , IN TYPE III,
 IV AND V CONSTRUCTION THE FOLLOWING SHALL BE PROVIDED:
  
  
 708.4.1.1 ROOF SHEATHING.
 THE ROOF SHEATHING OR DECK SHALL BE OF APPROVED
 NONCOMBUSTIBLE MATERIALS OR OF FIRE-RETARDANT-TREATED
 WOOD, FOR A DISTANCE OF 4 FEET (1220 MM); OR
  
 708.4.1.2 ROOF PROTECTION.
 THE ROOF SHALL BE PROTECTED WITH 0.625-INCH (15.88 MM)
 TYPE X GYPSUM BOARD DIRECTLY BENEATH THE UNDERSIDE OF
 THE ROOF SHEATHING OR DECK AND SUPPORTED BY A MINIMUM
 OF NOMINAL 2-INCH (51 MM) LEDGERS ATTACHED TO THE SIDES
 OF THE ROOF FRAMING MEMBERS, FOR A MINIMUM DISTANCE OF
 4 FEET (1220 MM).
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-06-19 Cont ID  
Sent By dpalmer Date 2008-06-19 Time 12:34 Rev Time 0.00
Received By dpalmer Date 2008-06-19 Time 12:34 Sent To  
Notes
2008-06-19 12:34:43** DENIEDREVIEW **
  
  
 1) NOTE:PLEASE SEE THAT PLANS AND DOCUMENTS NEEDED TO
 BE SUBMITTED ARE NOT COMPLETE AT THIS TIME. THERE MAY
 VERY WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 CAN NOT BE MADE AT THIS TIME DUE TO LACK OF INFORMATION
 AND CODE COMPLIANCE.
  
 2) NOTE: PLEASE SEE ATTACHED PRINT OUT FROM THE
 DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION.AT
 THE TIME OF THIS REVIEW THE PRINT OUT INDICATES THE
 ARCHITECT OF RECORD AS SIGNED, DATED AND SEALED ON
 PLANS LICENSE WAS SUSPENDED IN JULY 2007. THIS LICENSE
 IS NOT CURRENT AS SHOWN BY THE STATE AND PLANS MAY NOT
 BE SIGNED, DATED AND SEALED BY THIS ARCHITECT AS
 SHOWN.
 ** CONTACT HAS BEEN MADE TO THE BOARD OF ARCHITECTS
 LEGAL COUNSEL TO VERIFY THE STATE WEBSITE INFORMATION
 AS SHOWN IS ACCURATE.
  
 3) NOTE: PLEASE BE SURE TO COMPLETE ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULES.
 PLEASE SEE MOST OF DEVICES WHICH DO NOT INDICATE ANY
 CIRCUITS AND MANY CIRCUITS WHICH DO NOT CORRELATE WITH
 THE SUBMITTED SCHEDULES. THERE ARE SEVERAL CODES WHICH
 MINIMUM CIRCUITING CAN NOT BE VERIFIED FOR CODE
 COMPLIANCE AT THIS TIME.
 FBC ADMIN SECTION 106.3.5.1.2, 106.5.4
 NEC 408.4, 240.4, 310.16, 210.52, 210.11 ETC
  
 4) NOTE: PLEASE BE SURE PLANS REFERENCE THE CURRENT
 CODES IN EFFECT AS LISTED.
 NFPA-101 2003, NFPA-72 2002, NFPA-70 2005, AND 2004 FBC
 W/ 2007 REVISIONS.
  
 5) NOTE: PLEASE SUBMIT COMPLETED ENERGY CALCULATIONS
 FOR ALL AREAS WHICH ARE APPLICABLE FOR USE AND
 OCCUPANCY. PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2
 AND .1.3 FOR LIGHTING PERFORMANCE CALCULATIONS. PLEASE
 SEE 13-400.3.A, 13-400.3.B, 13-400.3.C, 13-101.3. AS
 THE MINIMUM REQUIRED CALCULATIONS WERE NOT SUBMITTED
 MINIMUM CODE COMPLIANCE HAS NOT BEEN MET OR VERIFIED.
  
 6) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AS THE FOLLOWING
 WORDING IS REQUIRED TO BE ON PLANS.
 CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT WITHIN 30
 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD
 DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDED
 TO THE BUILDING OWNER, INCLUDING:13-413.1.ABC.2.2
 MANUALS.
 CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT AN OPERATING
 MANUAL AND MAINTENANCE MANUAL BE PROVIDED TO THE
 BUILDING OWNER. THE MANUALS SHALL INCLUDE, AT A
 MINIMUM, THE FOLLOWING:
 1. SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED
 OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING
 MAINTENANCE.
 2. OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH
 PIECE OF EQUIPMENT REQUIRING MAINTENANCE. REQUIRED
 ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY
 IDENTIFIED.
 3. NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED
 SERVICE AGENCY.
 NOTE: ENFORCEMENT AGENCIES SHOULD ONLY CHECK TO BE SURE
 THAT THE CONSTRUCTION DOCUMENTS REQUIRE THIS
 INFORMATION TO BE TRANSMITTED TO THE OWNER AND SHOULD
 NOT EXPECT COPIES OF ANY OF THE MATERIALS.
 SOME TEXT ABOVE WAS TAKEN DIRECTLY FROM THE FBC FOR
 EASE OF CORRECT WORDING REQUIRED ON PLANS.
  
 7) NOTE: PLEASE SEE THE RISER SUBMITTED IS NOT COMPLETE
 AT THIS TIME. PLEASE SEE NO MAINS, NO OVER CURRENT
 PROTECTION FOR PANELS, MAINS ETC WERE SUBMITTED OR
 SHOWN.
 PLEASE SUBMIT A COMPLETE RISER DIAGRAM MEETING MINIMUM
 CODE COMPLIANCE FOR SERVICES. 230.70,230.71,230.72,
 215.5, 310.16, 240.4 ETC
 **
 8) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR TO EACH PANEL.
 250.110,250.122, 250.24 ETC.
  
 9) NOTE: PLEASE SEE GROUNDING ELECTRODE SYSTEM MENTIONS
 TO ATTACH TO FOOTER STEEL? PLEASE KNOW IN AN EXISTING
 BUILDING, IT IS NOT REQUIRED AND IS NOT RECOMMENDED DUE
 TO THE STRUCTURAL INTEGRITY OF THE EXISTING
 STEEL/FOOTER.
 PLEASE KNOW HOWEVER THIS IS PERMITTED AND IF SHOWN ON
 RISER, IT WILL BE REQUIRED.
 250.50
  
 10) NOTE: PLEASE SEE 250.66 FOR SIZING OF GROUNDING
 ELECTRODE CONDUCTOR AS THIS IS CURRENTLY SHOWN AS A
 "6/0"? PLEASE KNOW THIS IS NOT A RECOGNIZED STANDARD IN
 THE NATIONAL ELECTRICAL CODE OR THE AMERICAN WIRE GAUGE
 STANDARD. PLEASE ADJUST AS NEED BASED ON SERVICE
 ENTRANCE CONDUCTORS WHICH WILL BE BASED ON LOAD
 CALCULATIONS.PLEASE BE SURE TO SEE COMMENTS BELOW FOR
 MINIMUM SERVICE ENTRANCE CONDUCTORS TO VERIFY.
  
 11) NOTE: PLEASE SEE NOTE WITH RESPECT TO LOAD
 CALCULATIONS. AS THE SUBMITTED CALCULATIONS DO NOT
 MINIMUM CODE COMPLIANCE THE SIZE OF THE EXISTING
 SERVICE ENTRANCE CONDUCTORS AS SHOWN ON RISER CAN NOT
 BE VERIFIED.
  
 10) NOTE: PLEASE SUBMIT AIC RATINGS FOR ALL NEW SERVICE
 EQUIPMENT BEING INSTALLED. PLEASE SEE 110.9 AS MAINS,
 BREAKERS AND ALL SERVICE EQUIPMENT IS REQUIRED TO RATED
 FOR THE AVAILABLE FAULT CURRENT.
 PLEASE SEE NOTE #20 AS LISTED ON E-2 WHICH MENTIONS TO
 USE FUSES HOWEVER AS NO INFORMATION IS SHOWN ON RISER
 FOR ANY MAINS, SERVICE EQUIPMENT ETC THESE CAN NOT BE
 VERIFIED.
  
 12) NOTE: PLEASE SHOW LOAD CALCULATIONS MEETING THE
 2005 NEC> PLEASE SEE THE CODE SECTIONS REFLECTED ON
 PLANS ARE NOT FROM THE 2005 NATIONAL ELECTRICAL CODE.
 PLEASE SEE THE COMMERCIAL PORTION OF THE BUILDING
 ACTUALLY SHOWS *RESIDENTIAL* LOAD CALCULATIONS. HOW IS
 THIS POSSIBLE? WHERE IN THE NEC DOES IT PERMIT
 RESIDENTIAL LOAD CALCULATIONS IN COMMERCIAL OFFICE
 SPACE?
 PLEASE SEE 220.12, 220.14, 220.42, 220.43, ETC. PLEASE
 BE SURE TO SHOW ALL CONTINUOUS LOADS AT 125% PER 215.3,
 230.42 ETC.
 AS CALCULATIONS ARE NOT COMPLETE AND THERE IS MUCH NEED
 FOR COORDINATION PLEASE KNOW NEW COMMENTS MAY ARISE
 ONCE THESE ARE RESUBMITTED.
  
 13) NOTE: PLEASE SEE COMMON AREAS ON PLANS WILL REQUIRE
 SOME SORT OF *HOUSE/COMMON* ARE PANEL. THESE CIRCUITS
 IN THESE AREAS MAY NOT BE FED FROM THE APARTMENT UNITS
 OR COMMERCIAL TENANT SPACE.
 210.25 ETC. AS MOST OF THE CIRCUITING IS NOT SHOWN MOST
 ITEMS CAN NOT BE VERIFIED FOR MINIMUM CODE COMPLIANCE.
  
 14) NOTE: PLEASE SHOW ALL PANEL LOCATIONS FOR
 VERIFICATION OF CODE COMPLIANCE.
 110.26,240.24 ETC.
 FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION
 AND COORDINATION.
  
 15) NOTE: PLEASE CORRELATE ALL LOAD FOR A/C SYSTEMS, AS
 MECHANICAL PLANS INDICATE 10KW UNITS, LOAD
 CALCULATIONS
 INDICATE BOTH 9KW LOAD AND 5KW LOAD AND PANEL SCHEDULES
 INDICATE 5KW HEAT FOR ALL??
 PLEASE ADJUST LOAD CALCULATIONS AND COORDINATE OTHER
 COMMENTS.
  
 16) NOTE: PLEASE SEE 424.3B WHICH REQUIRES ALL MINIMUM
 OVER CURRENT PROTECTION FOR AIR HANDLER UNIT HEAT TO BE
 SIZED AT A MINIMUM OF 125%.
 PLEASE SEE PANEL SCHEDULES SHOWS 50A, #6 AWG ON 5KW
 UNITS.
  
 17) NOTE: PLEASE SEE CONDUCTORS SHOWN FOR RANGE/OVENS
 WHICH DO NOT SHOW ANY NEUTRAL CONDUCTOR AS REQUIRED PER
 250.140
  
 18) NOTE: PLEASE SEE MISSING MINIMUM DISCONNECTS FOR
 ALL AIR CONDITIONING EQUIPMENT. AS NOT ALL EQUIPMENT IS
 CURRENTLY SHOWN PLEASE BE SURE TO SEE 440.11 AND 110.26
 AND SHOW LOCATIONS OF ALL REQUIRED DISCONNECTS.
  
 19) NOTE: PLEASE SEE MISSING REQUIRED GFI SERVICE
 RECEPTACLE FOR OUTSIDE CONDENSING UNITS.210.63,
 210.8A3, 210.8B4.
  
 20) NOTE: PLEASE SEE AN ELEVATOR IS SHOWN ON PLANS,
 HOWEVER THERE IS NO INDICATION ON ANY PLANS OF THIS
 EQUIPMENT OR EQUIPMENT ROOM.
 PLEASE SHOW LOCATION OF EQUIPMENT.
 PLEASE SEE 620.23, 620.24 FOR MISSING REQUIRED
 DEDICATED CIRCUITS. PLEASE SEE SAME SECTIONS AS
 RECEPTACLE SHALL BE GFI PROTECTED.
 PLEASE SEE 700.16 FOR MISSING BACK UP LIGHT DEPENDING
 ON LOCATION OF EQUIPMENT.
  
 21) NOTE: PLEASE SEE 13-415.1.ABC.1.4 FOR REQUIRED
 CONTROL OF OUTSIDE LIGHT. SOME LIGHTS NOTE TO BE
 CIRCUITED TO A TC (ASSUMING TIME CLOCK) HOWEVER PLEASE
 SEE CURRENT CODE SECTION GIVEN AS A STANDARD TIME CLOCK
 IS NOT ACCEPTABLE.
 PLEASE PROVIDE ONE OF TWO ACCEPTABLE METHODS AND
 INDICATE ON PLANS.
 PLEASE BE SURE TO SEE NOTES ABOVE WITH RESPECT TO
 COMMON AREAS WHICH OUTSIDE LIGHTING WOULD BE TO NEW
 HOUSE PANEL ETC.
  
 22) NOTE: PLEASE SEE THE MISSING REQUIRED DEDICATED
 SIGN CIRCUIT AS PER 600.5
  
 23) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR
 MINIMUM LIGHTING LEVELS UNDER THE 2003 NFPA-101 LIFE
 SAFETY CODE FOR EGRESS PATHS AND STAIRS.
 PLEASE SEE 7.8.1.3, 7.9.2.2.
 PLEASE KNOW AS THESE ARE COMMON AREAS, CONTROLS AND
 CIRCUITING NEED TO BE ADJUSTED ACCORDING.
  
 24) NOTE: PLEASE SEE PLANS SHOW SD FOR SMOKE DETECTORS
 AS DEFINED IN NFAP-72. IF THESE ARE TRULY SMOKE
 DETECTORS WHICH ONLY DETECT AND DO NOT SOUND AN ALARM
 PLEASE SUBMIT THE COMPLETE FIRE ALARM SYSTEM INCLUDING
 HORNS, FIRE ALARM PANEL ETC.
 PLEASE SEE THE COMMON AREAS MAY NOT HAVE THE
 RESIDENTIAL UNITS SMOKE ALARMS DEVICES WIRED INLINE OR
 SAME CIRCUITS.
 PLEASE ADJUST.
 PLEASE SEE THE DEFINITIONS FOR SMOKE ALARMS AND SMOKE
 DETECTORS AND ADJUST DESIGN ACCORDINGLY.
  
 25) NOTE: PLEASE PROVIDE A FIXTURE LEGEND/SCHEDULE AND
 CORRELATE WITH THE PLANS. PLEASE BE SURE THE FIXTURE
 LEGEND IS COMPLETE FOR ALL COMMON AREAS AND OFFICE
 AREAS. PLEASE INCLUDE AREAS FOR RESIDENTIAL ALSO WITH
 RESPECT TO THE RECESSED LIGHTING FIXTURES.
 13-415.2.ABC.1, 13-415.2 FOR COMMERCIAL,
 13-606.1.ABC.1.2.4 FOR RESIDENTIAL.
  
 26)NOTE: PLEASE BE SURE TO SEE 700.12F FOR CIRCUITING
 OF REQUIRED EMERGENCY AND EXIT LIGHT FIXTURES.
  
 27) NOTE: PLEASE SEE 210.8A2WHICH REQUIRES A;;
 RECEPTACLES IN BATHROOMS TO BE SHOWN AS GFI/GFI
 PROTECTED. SOME ARE AND SOME ARE NTO.
  
 28) NOTE: PLEASE SEE 210.52D, 210.11C3 FOR MISSING
 REQUIRED DEDICATES BATH CIRCUITS. MUST BE 20AMP AND #12
 MINIMUM.
  
 29) NOTE: PLEASE SEE NFPA-72 11.8.3 FOR LOCATIONS AND
 TYPES OF SMOKE DETECTION DEVICES WITHIN 20FT OF COOKING
 APPLIANCES.
 PLEASE ALSO SEE NOTE ON PLANS WHICH MENTIONS SMOKE
 DETECTORS ARE TO BE WIRED AHEAD OF THE SWITCHES ON
 EITHER BATH OR KITCHEN LIGHTING CIRCUIT, PLEASE SEE
 THIS IS OK, HOWEVER ARC FAULT PROTECTION WILL THEN BE
 REQUIRED FOR THOSE LIGHTING CIRCUITS.
 210.12 NEC
  
 31) NOTE: PLEASE LIST ALL THE REQUIRED ARC FAULT
 PROTECTED CIRCUITS AS REQUIRED PER 2005 NEC 210.12B.
 PLEASE SEE COMMENTS ABOVE AS THE CIRCUITS SHALL BE
 SPECIFIC AND AS OTHER COMMENTS HAVE AFFECTED DEDICATED
 CIRCUITS PER NOTES PLEASE BE SURE TO COORDINATE.
  
 32) NOTE: PLEASE BE SURE TO SEE 220.52, 210.52B1 FOR
 DINING ROOM/AREA CIRCUITING.
  
 33) NOTE: PLEASE SEE MANY CIRCUITS ON PLANS MENTIONS
 *GENERAL LIGHTS* AND GENERAL RECEPTACLES*.
 PLEASE SEE 408.4 AS ALL CIRCUITING SHALL BE SPECIFIC TO
 ROOMS AND AREAS IN WHICH THEY FEED.
 FBC 106.1.2, 106.3.5.1.2, 106.3.5.4
  
 34) NOTE: PLEASE BE SURE TO LABEL APARTMENT UNITS ON
 ELECTRICAL PLANS. *A*, *B* ETC
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
 REVIEW FOR CIRCUITING WILL NEED TO BE DONE.
  
 35) NOTE: PLEASE SEE 422.30, 422.31 FOR MISSING
 DISCONNECTS FOR WATER HEATERS.
  
 36) NOTE: PLEASE SEE 210.52 FOR MISSING RECEPTACLES.
 (REDLINED ON ONE SET OF PLANS.
  
 37) NOTE: PLEASE SEE PLANS FOR OFFICE WHICH SHOWS A
 CIRCUIT FOR WHAT IS LISTED ON PANEL SCHEDULE AS BEING A
 MICROWAVE # 14, HOWEVER NO DEVICE OR LOCATION IS SHOWN
 ON PLANS.
  
 38) NOTE: PLEASE SEE SWITCHES WHICH ARE SHOWN WIRED TO
 A 3-WAY SYSTEM ON STAIRS, HOWEVER DO NOT INDICATE BEING
 S3.
 PLEASE SEE MINIMUM LIGHTING CONTROLS FOR EGRESS
 LIGHTING IN FBC CHAPTER 10 AND NFPA-1017.8
 PLEASE SEE OTHER AREAS OF PLANS IN WHICH 3-WAY
 SWITCHING IS SHOWN HOWEVER THE 3-WAY SWITCH IS ONLY
 SHOWN AT ONE END WHEN IT MUST BE AT MORE THAN ONE
 LOCATION.
  
 39) NOTE: PLEASE SEE THE ELECTRICAL PLANS AS THE PLANS
 ARE MISSING 210.63, 210.70 COMPLIANCE FOR AIR HANDLING
 UNITS.
 AS THESE WERE NOT SHOWN ON ELECTRICAL PLANS THE
 MECHANICAL PLANS WERE LOOKED AT HOWEVER THIS BECAME
 MORE CONFUSING AS PACKAGE UNITS AND SPILT SYSTEMS WERE
 SHOWN.
 IF THESE UNITS ARE PACKAGE UNITS ON ROOF, THEN WHY ARE
 THERE CONDENSING UNITS SHOWN ON THE GROUND FLOOR
 OUTSIDE LEVEL?
 IT IS UNCLEAR WHAT THE DESIGN IS GOING TO BE AS SPILT
 SYSTEMS ARE ALSO LISTED ON EQUIPMENT SCHEDULE. PLEASE
 COORDINATE ALL AND SEE NOTES ABOVE WITH RESPECT TO
 MISSING DISCONNECTS, COORDINATION OF HEAT STRIPS, OVER
 CURRENT PROTECTIONS, GFI RECEPTACLES, LIGHTS ETC.
  
 40) NOTE: PLEASE SEE MISSING GFI DESIGNATIONS FOR
 GARAGE RECEPTACLES.
 210.8A2, 5
  
 41) NOTE: PLEASE SEE MISSING CONTROL FOR EXHAUST FAN ON
 FIRST FLOOR BATHROOM.
 FBC 106.1.2
  
 42) NOTE: PLEASE SEE ELECTRICAL RISER CLEARLY STATES
 THE FEEDERS AS NOTED WILL BE TYPICAL OF *FOUR* (4) YET
 THE PLANS ONLY SHOW THREE SPACES, THREE PANELS ETC.
 PLEASE CLEAR THIS UP AND COORDINATE.
  
 43) NOTE: BASED ON COMMENTS ABOVE ONE SET OF PLANS ARE
 BEING RETAINED BY THIS OFFICE.
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2008-06-26 Cont ID  
Sent By rchokshi Date 2008-06-26 Time 13:30 Rev Time 0.00
Received By rchokshi Date 2008-06-26 Time 13:24 Sent To  
Notes
2008-06-26 13:30:29FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT FENCE ETC., PLANS SHOWING
 SILT FENCE AROUND THE SITE & STORM CATCH BASIN DRAINS
 DURING CONSTRUCTION AND ALL DEMOLITION PHASE.HEIGHT
 OF FENCE SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST
 PARTICLES.
  
 2. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 3. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL
 CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING
 SERVICES, PHONE# 494-1040
  
 4. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 5. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE
 ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD.
  
 6. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS.
  
 7. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE.
  
 8. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
  
 9. PLEASE PROVIDE A COPY OF GEO-TECH REPORT&STORM
 WATER QUALITY CALCULATIONS. STORM WATER CALS MUST BE
 APPROVED FROM 100045TH STREET ENGINEERING SERVICES
 BEFORE WE APPROVED.
  
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-06-20 Cont ID  
Sent By mawillia Date 2008-06-20 Time 22:45 Rev Time 0.00
Received By mawillia Date 2008-06-20 Time 15:42 Sent To  
Notes
2008-06-20 16:36:48*****DENIED*****
  
  
 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 02.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FORM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 03.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 EMERGENCY RESPONSE TO THE SAID PROPERTY OR THE VICINITY
 THEREOF (INCLUDING STREETS, ALLEYS, FIRE LANES, ETC.)
 .
  
 04.ON SHEET A-1, WHAT IS THE DOOR NUMBER IS SCHEDULED
 FOR THE ROOM CONTAINING THE AIR HANDLER UNIT (A.H.U.)
 ?
  
 05.ON SHEET A-2, ROOM DOOR 215 LOCATED BETWEEN THE
 ELEVATOR AND THE FOYER IS LISTED AS LIVING ROOM. PLEASE
 EXPLAIN.
  
 06.ON SHEET A-2, ROOM DOOR 212 IS LISTED IN THE DOOR
 SCHEDULE AS BATHROOM.
  
 07.ON SHEET E-1 & E-2, REFERENCES ARE MADE TO SMOKE
 DETECTORS BEING USED IN THE DWELLING UNITS.PLEASE BE
 ADVISED THAT MOKE DETECTORS (SD) ARE TIED INTO A
 BUILDING'S FIRE ALARM SYSTEM, WHEREAS SMOKE ALARMS
 SOUND ONLY WITHIN AN INDIVIDUAL DWELLING UNIT AND SHALL
 NOT ACTUATE THE BUILDING FIRE ALARM SYSTEM.
  
 08.PROVIDE PRESCRIPTIVE STRENGHTS FOR THE STAIR
 HANDRAILS/GUARDRAILS.
  
 09.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 10.30.1.2.2- NO DWELLING UNIT OF A RESIDENTIAL
 OCCUPANCY SHALL HAVE ITS SOLE MEANS OF EGRESS PASS
 THROUGH ANY NONRESIDENTIAL OCCUPANCY IN THE SAME
 BUILDING.
  
 11.30.1.2.3- THE SEPARATION OF THE DWELLING UNITS
 OF THE RESIDENTIAL OCCUPANCY AND EXITS FROM THE
 NONRESIDENTIAL OCCUPANCY SHALL BE BY CONSTRUCTION
 HAVING A FIRE RESISTAIVE RATING OF NOT LESS THAN 1
 HOUR.
  
 12.30.3.3.2- SPECIFY THE INTERIOR FINISH FOR THE
 EXIT ENCLOSURE, LOBBIES AND CORRIDORS, AND OTHER SPACES
 IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 13.30.3.5.11 - SHOW THE LOCATION OF THE 2A10 BC RATED
 FIRE EXTINGUISHERS WHICH SATIFISFY THE 75' TRAVEL
 DISTANCE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-26 Cont ID  
Sent By rchokshi Date 2008-06-26 Time 13:31 Rev Time 0.00
Received By rchokshi Date 2008-05-23 Time 08:24 Sent To  
Notes
2008-05-29 11:44:25TO "COMM" BD#11
2008-05-23 08:29:42WAITING FOR "COMM"BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-06-19 Cont ID  
Sent By tgordon Date 2008-06-19 Time 09:05 Rev Time 2.30
Received By tgordon Date 2008-06-19 Time 09:05 Sent To  
Notes
2008-06-19 10:09:10PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE ARCHITECT OCTAVIO L. LIMA LICENSE WAS SUSPENDED
 ON 2-28-09. PLEASE CORRECT.
  
 2) THE ENERGY CALCULATION NEED TO INCLUDE BOTH
 APARTMENTS UNITS ON THE SECOND FLOOR, PER 2004 FBC
 13-101.2. ALSO SUBMIT SEPERATE ENERGY CALCULATIONS FOR
 THE FIRST FLOOR OFFICES, PER 1004 FBC 13-101.1.4.
  
 3) WHEN RESUBMITTING THE ENERGY CALCULATIONS FOR THE
 APARTMENTS USE THE REVISED FORM 600A-2004R (R=REVISED)
 PER 13-600.3.A.
  
 4) SEE RED LINE NOTES ON ENERGY CAL'S FOR MORE
 CORRECTIONS.
  
 5) THE COOLING LOAD CALCULATIONS FOR THE APARTMENT ARE
 CALLING FOR 20,650 TOTAL COOLING BTU'S, THE MECHANICAL
 PLAN EQUIPMENT SCHEDULE SHOWS 28,200 TOTAL COOLING
 BTU'S, THE PLANS CAN ONLY CALL FOR 15% MORE TOTAL
 COOLING BTU'S THAN THE COOLING LOAD CALCULATIONS, PER
 2004 FBC 13-607.1.ABC.1.1. A 2.5 TON SYSTEM IS TO LARGE
 PER COOLING LOAD CAL'S. PLEASE CORRECT.
  
 6) THE COOLING LOAD CALCULATIONS NEED TO INCLUDE BOTH
 APARTMENTS, AS ZONE ONE AND ZONE TWO, PER 2004 FBC
 13-607.1.ABC.1.
  
 7) PLAN A-2 ROOF PLAN SHOWS TWO A/C PACKAGE UNITS FOR
 THE APARTMENTS, PLAN AC-1 GROUND FLOOR SHOWS TWO
 CONDENSER UNITS FOR THE APARTMENTS, PACKAGE UNITS DO
 NOT REQUIRE CONDENSER UNITS, PLEASE CORRECT THE PLANS
 SO IT IS KNOWN WHAT TYPE OF A/C SYSTEMS ARE BEING
 INSTALLED, PER FBC 106.1.1.
  
 8) PLEASE SHOW THE SIZE OF THE SUPPLY AIR DUST GOING TO
 THE SECOND FLOOR FOYER ON PLAN AC-1, PER 2004 WPB AMEND
 106.3.5.4.
  
 9) PLEASE SHOW OUTSIDE AIR CALCULATIONS FOR OFFICE ON
 MECHANICAL PLAN, PER 2004 FBC/M 401.2. AND SHOW ON PLAN
 IF OBTAINED MECHANICALLY, PER 2004 FBC/M 401.5.
  
 10) PLAN AC-2 EQUIPMENT SCHEDULE NEED TO SHOW THE A/C
 SYSTEMS MANUFACTURER'S NAME.
  
 11) PLAN AC-2 EQUIPMENT SCHEDULE IS SHOWING THE EQUIP.
 EER, IT NEEDS TO SHOW THE SEER, PLEASE CORRECT PER 2004
 FBC 13-607.1.ACB.3.1.1.
  
 12) PLAN AC-2 EQUIPMENT SCHEDULE IS SHOWING SPLIT A/C
 SYSTEMS FOR THE APARTMENTS, OTHER PLANS SHOWED PACKAGE
 UNITS, PLEASE SEE NOTE 7 ABOVE. PLEASE CORRECT PER 2004
 FBC 106.3.5.1.4.
  
 13) SEE RED LINE NOTES ON MECHANICAL PLANS AC-1 AND
 AC-2 FOR NEEDED CORRECTIONS.
  
 14) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, SEE F.B.C. 106.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-06-11 Cont ID  
Sent By kstevens Date 2008-06-11 Time 17:45 Rev Time 0.00
Received By kstevens Date 2008-06-11 Time 17:44 Sent To  
Notes
2008-06-11 18:00:44DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT A-1 SUBMIT AN EXISTING FLOOR PLAN SO AS TO
 DETERMINE THE EXTENT OF WORK ON THE FIRST FLOOR.
 SECTION 106.1.2.
  
 2. SHT A-1 SUBMIT DETAILS FOR THE ACCESSIBLE DRINKING
 FOUNTAIN,THE ACCESSIBLE WATER CLOSET, THE ACCESSIBLE
 LAV, THE ACCESSIBLE TOILET ROOM & THE ACCESSIBLE SINK.
 . SECTIONS 11-4.15, 11-4.16, 11-4.19, 11-4.22 &
 11-4.24. (FORWARD APPROACH REQUIRED FOR SINK).
  
 3. SHT P1.1 THE DRINKING FOUNTAIN SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT FOR THE BATHROOM FIXTURES.
 SECTION 909.1.
  
 4. SHT P2 SANITARY RISER DIAGRAM. THE DRINKING FOUNTAIN
 AND THE SINK SHALL DISCHARGE DOWNSTREAM OF THE WET VENT
 FOR THE BATHROOM FIXTURES. SECTION 909.1.--THE WASH
 MACHINE FOR APT #1 IS REQUIRED TO HAVE A TRAP AND A
 STANDPIPE AND THE CLEANOUT SHALL BE LOCATED 4FT ABOVE
 THE FLOOR OR ACCESS. SECTIONS 708.9, 802.4 & 1002.1.
 --APT #1 KITCHEN SINK IS MISLABELED AS A LAV ON THE
 RISER DIAGRAM. PLEASE CORRELATE. SECTION 106.1.1.
  
 5. THIRD PLUMBING SHEET IS ALSO LABELED P2. PLEASE
 CLARIFY. SECTION 106.1.3.
  
 6. SECOND SHEET P2 DETAIL 5 SHOWS A 2 INCH STACK FOR
 THE WASH MACHINE. PER SECTION 406.3, A 3 INCH STACK IS
 REQUIRED.--DETAIL #6 THERMAL EXPANSION CONTROL IS
 REQUIRED FOR EACH WATER HEATER. PLEASE INDICATE METHOD.
 SECTION 607.3.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2008-06-04 Cont ID  
Sent By adavila Date 2008-06-04 Time 17:14 Rev Time 0.00
Received By adavila Date 2008-06-04 Time 17:13 Sent To  
Notes
2008-06-04 17:14:42PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PER THE SITE PLAN APPROVAL LETTER, PRIOR TO THE
 ISSUANCE OF THE BUILDING PERMIT FOR THE SECOND STORY
 ADDITION, THE APPLICANT SHALL PROVIDE THE PLANNING AND
 ZONING DEPARTMENT WITH A COPY OF THE APPROVED FLORIDA
 DEPARTMENT OF TRANSPORTATION (FDOT) PERMIT FOR THE TWO
 (2) ON-STREET PARKING SPACES IN FRONT OF THE PROPERTY.
 TO PRESENT, NO COPY OF THE APPROVED FDOT PERMIT HAS
 BEEN SUBMITTED TO THE PLANNING AND ZONING DEPARTMENT.
  
 2. PER THE SITE PLAN APPROVAL LETTER, THE FENCE/WALL
 SHALL NOT EXCEED SIX (6) FEET IN HEIGHT AS SHOWN ON THE
 SITE PLAN (SHEET AS-1) AND ELEVATIONS (SHEET A-4).
 GROUND FLOOR PLAN (SHEET A-1), SHOWS THE PROPOSED WALL
 TO BE 11 FEET IN HEIGHT.PLEASE NOTE THAT ALL
 WALLS/FENCES SHALL BE APPROVED ON A SEPARATE PERMIT.
  
 3. PURSUANT TO SECTION 94-442, LANDSCAPE PLANS SHALL BE
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 LANDSCAPE ARCHITECT.
  
 4. PLEASE NOTE THAT ALL SIGNS AND AWNINGS SHALL BE
 APPROVED ON A SEPARATE PERMIT.
  
 COMMENTS/QUESTIONS CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.