Plan Review Details - Permit 08050605
Plan Review Stops For Permit 08050605
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-07-23 Cont ID  
Sent By lmartine Date 2008-07-23 Time 14:03 Rev Time 0.00
Received By lmartine Date 2008-07-23 Time 14:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-12 Cont ID  
Sent By mperson Date 2008-06-12 Time 16:15 Rev Time 0.00
Received By lmartine Date 2008-06-12 Time 08:44 Sent To  
Notes
2008-06-12 08:51:52BUILDING REVIEW COMMENTS
  
  
  
  
  
 PLEASE SHOW COMPLIANCE WITH FBC, R4101.17 (BARRIER
 REQUIREMENTS).
  
  
  
 THANK YOU,
 LUIS MARTINEZ
 561-805-6710

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-09-03 Cont ID  
Sent By dpalmer Date 2008-09-03 Time 12:57 Rev Time 0.00
Received By dpalmer Date 2008-09-03 Time 12:57 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-08-25 Cont ID  
Sent By dpalmer Date 2008-08-25 Time 10:28 Rev Time 0.00
Received By dpalmer Date 2008-08-25 Time 10:28 Sent To PC
Notes
2008-08-25 10:33:34SUBMITTED DOCUMNETS NEED TO COORIDNATE. CALLED AND
 SPOKE WITH RICH WADE. WILL BRING IN UPDATED SHEETS TO
 PLACE IN SETS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-07-16 Cont ID  
Sent By dpalmer Date 2008-07-16 Time 10:34 Rev Time 0.00
Received By dpalmer Date 2008-07-16 Time 10:34 Sent To P
Notes
2008-07-16 10:34:29** DENIEDREVIEW **
  
  
 1) NOTE:PLEASE SEE THE NEW ELECTRICAL PLAN PROVIDED
 ON 8 1/2 BY 11 DOES NOT CORRELATE WITH PLANS. FOR
 EXAMPLE: PLEASE SEE PLANS WHICH ARE DONE BY THE
 ENGINEER REQUIRES A NEW 50AMP FEED FOR THE NEW AQUA
 LOGIC PANEL YET THE SEPARATE PLAN SUBMITTED INDICATES A
 NEW 30AMP FEED. 240.4, 310.16, 408.4 ETC, FBC 106.1.1
 FOR CLARITY AND COORDINATION OF PLANS.
 PLEASE SEE THE ENGINEERED PLANS ARE MISSING AN
 EQUIPMENT GROUNDING CONDUCTOR TO THE NEW PANEL.250.122
 PLEASE SEE ENGINEERS PLANS CALL FOR 3-#8 CONDUCTORS TO
 POOL PUMP IN A 1/2 INCH CONDUIT. PLEASE SEE TABLES IN
 APPENDIX *C* FOR CONDUIT FILL. THIS IS NOT PERMITTED.
  
 PLEASE ADJUST AND COORDINATE PLANS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-05-29 Cont ID  
Sent By choops Date 2008-07-08 Time 09:37 Rev Time 0.00
Received By dpalmer Date 2008-05-29 Time 12:19 Sent To P
Notes
2008-05-29 12:19:26** DENIEDREVIEW **
  
 1) NOTE: PLEASE SUBMIT THE RISER DIAGRAM SHOWING THE
 FEEDERS AND THE SIZE OF THE OVER CURRENT PROTECTION
 FROM THE SERVICE PANEL/EQUIPMENT.
 PLEASE KNOW THE BASE HOUSE PLANS WHICH ARE IN FOR
 REVIEW BY THIS OFFICE DOES NOT CONTAIN ANY POOL SUB
 PANEL, FEED FOR POOL PANEL, BREAKER, LOADS ETC FIGURED
 FOR THE NEW SUB PANEL.
 PLEASE SUBMIT RISER, LOADS CALCULATIONS FOR ADDED LOADS
 ETC.
 220.83, 240.4, 310.16, 225.31-225.39.
  
 2) NOTE: PLEASE SEE ZONING COMMENTS AS THIS WILL
 DEFINITELY AFFECT THE ELECTRICAL EQUIPMENT, LOCATION
 ETC.
 FBC 106.1.2 FOR COORDINATION.
  
 3) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR FROM SOURCE TO NEW SUB PANEL.
 250.50, 250.32.
  
 4) NOTE: PLEASE SHOW THE *AQUA LOGIC* PANEL ON RISER.
 WILL THIS UNIT BE CONTROLLING ANY HIGH VOLTAGE
 SYSTEMS?
 FBC 106.1.2
  
 5) NOTE: PLEASE KNOW THE WORDING ADDED TO PLANS FOR
 INFORMATION REGARDING THE FLORIDA BUILDING COMMISSION
 AND ADOPTION OF RULES ETC FOR THE EQUAL POTENTIAL GRID
 IS NOT REQUIRED TO BE ON PLANS. ONLY THE DETAIL FOR THE
 INSTALLATION NEEDS TO BE ON PLANS. PLEASE SHOW LAYOUT.
 680.26
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2008-07-16 Cont ID  
Sent By mperson Date 2008-07-16 Time 14:33 Rev Time 0.00
Received By mperson Date 2008-07-16 Time 14:33 Sent To B
Notes
2008-07-16 14:35:56CONTRACTOR INFORMATION
 NOTE: A GAS IS PERMIT REQUIRED FOR THE POOL HEATER. A
 LICENSED GAS OR PLUMBING CONTRACTOR SHALL SUBMIT PLANS
 WITH PERMIT APPLICATION. ALL GAS INSPECTIONS TO BE
 COMPLETE BEFORE FINAL POOL INSPECTION.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-05-30 Cont ID  
Sent By mperson Date 2008-05-30 Time 16:12 Rev Time 0.00
Received By mperson Date 2008-05-30 Time 16:12 Sent To B
Notes
2008-05-30 16:14:59GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. REFERENCE PLUMBING COMMENT #3 AND COMPLY.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-09-22 Cont ID  
Sent By adarroug Date 2008-09-22 Time 16:14 Rev Time 0.00
Received By adarroug Date 2008-09-22 Time 16:14 Sent To E
Notes
2008-09-22 16:14:55TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-09-17 Cont ID  
Sent By adarroug Date 2008-09-17 Time 11:39 Rev Time 0.00
Received By adarroug Date 2008-09-17 Time 11:39 Sent To Z
Notes
2008-09-17 11:40:30TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-08-28 Cont ID  
Sent By tgordon Date 2008-08-28 Time 13:42 Rev Time 0.00
Received By tgordon Date 2008-08-28 Time 13:42 Sent To E
Notes
2008-08-28 13:42:32TO "ELECT" D.P.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-08-14 Cont ID  
Sent By adarroug Date 2008-08-14 Time 14:20 Rev Time 0.00
Received By adarroug Date 2008-08-14 Time 14:20 Sent To E
Notes
2008-08-14 14:20:40TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-03 Cont ID  
Sent By adarroug Date 2008-07-03 Time 17:51 Rev Time 0.00
Received By adarroug Date 2008-07-03 Time 17:51 Sent To Z
Notes
2008-07-03 17:51:53TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-12 Cont ID  
Sent By lmartine Date 2008-06-12 Time 08:52 Rev Time 0.00
Received By lmartine Date 2008-05-21 Time 14:51 Sent To  
Notes
2008-05-21 14:52:28TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-07-16 Cont ID  
Sent By mperson Date 2008-07-16 Time 14:28 Rev Time 0.00
Received By mperson Date 2008-07-16 Time 14:28 Sent To G
Notes
2008-07-16 14:32:37****************PROVISO****************
 PER FLORIDA STATUTES 489.105 (3)(M) THE REQUIRED
 BACKFLOW PREVENTER FOR THE POTABLE WATER SUPPLY SHALL
 BE INSTALLED BY A LICENSED PLUMBING CONTRACTOR NOT THE
 POOL CONTRACTOR.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-05-30 Cont ID  
Sent By mperson Date 2008-05-30 Time 16:00 Rev Time 0.00
Received By mperson Date 2008-05-30 Time 16:00 Sent To G
Notes
2008-05-30 16:12:46PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET 2, PIPING SCHEMATIC: CLEARLY INDICATE THE
 "AQUA LOGIC W/SALT CHLORINATOR" LOCATION ON THE PIPING
 SCHEMATIC. PER (W.P.B. AS AMENDED) SECTION 106.1.1
 INFORMATION ON CONTRUCTION DOCUMENTS.
  
 2.SHEET 2: PLEASE CORRELATE AND CLEARLY INDICATE THE
 VENT PIPE SIZE AS BEING 1-1/2" ON THE MAIN DRAIN DETAIL
 AND PIPING SCHEMATIC AS IT IS BEING INDICATED AS SUCH
 IN THE "ATMOSPHERIC VENT DETAIL". PER (W.P.B. AS
 AMENDED) SECTION 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 3. CLEARLY INDICATE WHICH MODEL POOL HEATER IS BEING
 USED ON THE RESUBMITTED POOL HEATER MANUFACTURE SHEET.
 NOTE: THERE ARE SIX DIFFERENT MODELS BEING INDICATED ON
 THIS SUBMITTAL. PER (W.P.B. AS AMENDED) SECTION 106.1.2
 ADDITIONAL DATA.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2008-10-10 Cont ID  
Sent By mcruz Date 2008-10-10 Time 08:47 Rev Time 0.00
Received By mcruz Date 2008-10-10 Time 08:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2008-09-21 Cont ID  
Sent By mcruz Date 2008-09-21 Time 15:11 Rev Time 0.00
Received By mcruz Date 2008-09-21 Time 15:10 Sent To I
Notes
2008-09-21 15:11:01***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. AS THE PROPOSED FENCE/WALL/GATE MAY ENCROACH INTO A
 UTILITY EASEMENT, EASEMENT CONSENT FORMS ARE REQUIRED
 FROM THE FOLLOWING UTILITY COMPANIES:
  
 WEST PALM BEACH PUBLIC UTILITIES DEPARTMENT
 200 2ND STREET
 CITY HALL, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 (561)822-1300
  
 FLORIDA POWER AND LIGHT
 810 CHARLOTTE AVE
 WEST PALM BEACH, FL 33401
 (561)697-8000
  
 FLORIDA PUBLIC UTILITIES
 401 SOUTH DIXIE HWY
 WEST PALM BEACH, FL 33402
 (561)832-2461
  
 BELL SOUTH
 2021 SOUTH MILITARY TRAIL
 WEST PALM BEACH, FL 33415
 (561)439-9110
  
 COMCAST
 1401 NORTHPOINT PKWY
 WEST PALM BEACH, FL 33407
 (561)655-3842 - RESIDENTIAL
 (561)227-4261 - COMMERCIAL
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2008-07-08 Cont ID  
Sent By choops Date 2008-07-08 Time 09:37 Rev Time 0.00
Received By choops Date 2008-07-08 Time 09:37 Sent To E
Notes
2008-07-08 09:38:55***APPROVED - RESUB #1***
  
 PROVISO:PLANT MATERIALS USED SHALL BE EQUAL TO OR
 BETTER THAN FLORIDA DEPARTMENT OF AGRICULTURE NUMBER 1
 NURSERY GRADE STANDARD.
  
 NOTE:THE EXISTING PERMANENT FENCE MUST COMPLETELY
 RESTRICT ACCESS TO THE POOL AREA AND COMPLY WITH
 SECTION 94-304(D)(2)(B)+(C) OF THE ZLDRS:
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
  
  
  
 SENT TO "E" - DP

Review Stop Z ZONING
Rev No 1 Status F Date 2008-05-28 Cont ID  
Sent By choops Date 2008-05-28 Time 11:27 Rev Time 0.00
Received By choops Date 2008-05-28 Time 11:27 Sent To E
Notes
2008-05-28 11:34:00***FAILED***
  
  
 1)THE POOL EQUIPMENT AT IT'S PROPOSED LOCATION DOES
 NOT MEET THE MINIMUM SETBACK REQUIREMENTS AS REQUIRED
 BY SECTION 94-305 THE CITY OF WEST PALM BEACH ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDRS):MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A
 REQUIRED SETBACK.
  
 THE REQUIRED REAR SETBACK FOR THIS PROPERTY IS 11.9
 FEET (10% OF THE LOT DEPTH), WITH THE ALLOWABLE 4'
 ENCROACHMENT FOR MECHANICAL EQUIPMENT, THIS YIELDS A
 MINIMUM REAR SETBACK OF 7.9 FEET TO THE POOL EQUIPMENT.
 PLANS SHALL INDICATE COMPLIANCE.
  
 2)IN CONJUCTION WITH THE ADDITION PERMIT, THIS
 PROPERTY'S IMPROVEMENTS NOW EXCEED 50% OF THE
 STRUCTURE'S VALUE, MEASURED WITHIN A 12 MONTH PERIOD.
 PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF THE
 PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDRS.
  
  
 NOTE:THE EXISTING PERMANENT FENCE MUST COMPLETELY
 RESTRICT ACCESS TO THE POOL AREA AND COMPLY WITH
 SECTION 94-304(D)(2)(B)+(C) OF THE ZLDRS:
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720