Plan Review Stops For Permit 08050605 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2008-07-23 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2008-07-23 |
Time |
14:03 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2008-07-23 |
Time |
14:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2008-06-12 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-06-12 |
Time |
16:15 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2008-06-12 |
Time |
08:44 |
Sent To |
|
|
Notes |
2008-06-12 08:51:52 | BUILDING REVIEW COMMENTS | | | | | | | | | | | | PLEASE SHOW COMPLIANCE WITH FBC, R4101.17 (BARRIER | | REQUIREMENTS). | | | | | | | | THANK YOU, | | LUIS MARTINEZ | | 561-805-6710 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2008-09-03 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-09-03 |
Time |
12:57 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-09-03 |
Time |
12:57 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2008-08-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-08-25 |
Time |
10:28 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-08-25 |
Time |
10:28 |
Sent To |
PC |
|
Notes |
2008-08-25 10:33:34 | SUBMITTED DOCUMNETS NEED TO COORIDNATE. CALLED AND | | SPOKE WITH RICH WADE. WILL BRING IN UPDATED SHEETS TO | | PLACE IN SETS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2008-07-16 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-07-16 |
Time |
10:34 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-07-16 |
Time |
10:34 |
Sent To |
P |
|
Notes |
2008-07-16 10:34:29 | ** DENIEDREVIEW ** | | | | | | 1) NOTE:PLEASE SEE THE NEW ELECTRICAL PLAN PROVIDED | | ON 8 1/2 BY 11 DOES NOT CORRELATE WITH PLANS. FOR | | EXAMPLE: PLEASE SEE PLANS WHICH ARE DONE BY THE | | ENGINEER REQUIRES A NEW 50AMP FEED FOR THE NEW AQUA | | LOGIC PANEL YET THE SEPARATE PLAN SUBMITTED INDICATES A | | NEW 30AMP FEED. 240.4, 310.16, 408.4 ETC, FBC 106.1.1 | | FOR CLARITY AND COORDINATION OF PLANS. | | PLEASE SEE THE ENGINEERED PLANS ARE MISSING AN | | EQUIPMENT GROUNDING CONDUCTOR TO THE NEW PANEL.250.122 | | PLEASE SEE ENGINEERS PLANS CALL FOR 3-#8 CONDUCTORS TO | | POOL PUMP IN A 1/2 INCH CONDUIT. PLEASE SEE TABLES IN | | APPENDIX *C* FOR CONDUIT FILL. THIS IS NOT PERMITTED. | | | | PLEASE ADJUST AND COORDINATE PLANS. | | | | | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2008-05-29 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2008-07-08 |
Time |
09:37 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-05-29 |
Time |
12:19 |
Sent To |
P |
|
Notes |
2008-05-29 12:19:26 | ** DENIEDREVIEW ** | | | | 1) NOTE: PLEASE SUBMIT THE RISER DIAGRAM SHOWING THE | | FEEDERS AND THE SIZE OF THE OVER CURRENT PROTECTION | | FROM THE SERVICE PANEL/EQUIPMENT. | | PLEASE KNOW THE BASE HOUSE PLANS WHICH ARE IN FOR | | REVIEW BY THIS OFFICE DOES NOT CONTAIN ANY POOL SUB | | PANEL, FEED FOR POOL PANEL, BREAKER, LOADS ETC FIGURED | | FOR THE NEW SUB PANEL. | | PLEASE SUBMIT RISER, LOADS CALCULATIONS FOR ADDED LOADS | | ETC. | | 220.83, 240.4, 310.16, 225.31-225.39. | | | | 2) NOTE: PLEASE SEE ZONING COMMENTS AS THIS WILL | | DEFINITELY AFFECT THE ELECTRICAL EQUIPMENT, LOCATION | | ETC. | | FBC 106.1.2 FOR COORDINATION. | | | | 3) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING | | CONDUCTOR FROM SOURCE TO NEW SUB PANEL. | | 250.50, 250.32. | | | | 4) NOTE: PLEASE SHOW THE *AQUA LOGIC* PANEL ON RISER. | | WILL THIS UNIT BE CONTROLLING ANY HIGH VOLTAGE | | SYSTEMS? | | FBC 106.1.2 | | | | 5) NOTE: PLEASE KNOW THE WORDING ADDED TO PLANS FOR | | INFORMATION REGARDING THE FLORIDA BUILDING COMMISSION | | AND ADOPTION OF RULES ETC FOR THE EQUAL POTENTIAL GRID | | IS NOT REQUIRED TO BE ON PLANS. ONLY THE DETAIL FOR THE | | INSTALLATION NEEDS TO BE ON PLANS. PLEASE SHOW LAYOUT. | | 680.26 | | | | ** IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF | | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT | | HESITATE IN CONTACTING THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
N |
Date |
2008-07-16 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-07-16 |
Time |
14:33 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2008-07-16 |
Time |
14:33 |
Sent To |
B |
|
Notes |
2008-07-16 14:35:56 | CONTRACTOR INFORMATION | | NOTE: A GAS IS PERMIT REQUIRED FOR THE POOL HEATER. A | | LICENSED GAS OR PLUMBING CONTRACTOR SHALL SUBMIT PLANS | | WITH PERMIT APPLICATION. ALL GAS INSPECTIONS TO BE | | COMPLETE BEFORE FINAL POOL INSPECTION. | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2008-05-30 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-05-30 |
Time |
16:12 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2008-05-30 |
Time |
16:12 |
Sent To |
B |
|
Notes |
2008-05-30 16:14:59 | GAS PLAN REVIEW: | | DENIED: | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | 1. REFERENCE PLUMBING COMMENT #3 AND COMPLY. | | | | END OF COMMENTS: | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2008-09-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-09-22 |
Time |
16:14 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-09-22 |
Time |
16:14 |
Sent To |
E |
|
Notes |
2008-09-22 16:14:55 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2008-09-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-09-17 |
Time |
11:39 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-09-17 |
Time |
11:39 |
Sent To |
Z |
|
Notes |
2008-09-17 11:40:30 | TO "Z" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2008-08-28 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-08-28 |
Time |
13:42 |
Rev Time |
0.00 |
Received By |
tgordon |
Date |
2008-08-28 |
Time |
13:42 |
Sent To |
E |
|
Notes |
2008-08-28 13:42:32 | TO "ELECT" D.P. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2008-08-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-08-14 |
Time |
14:20 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-08-14 |
Time |
14:20 |
Sent To |
E |
|
Notes |
2008-08-14 14:20:40 | TO "DPALMER" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2008-07-03 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-07-03 |
Time |
17:51 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-07-03 |
Time |
17:51 |
Sent To |
Z |
|
Notes |
2008-07-03 17:51:53 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-06-12 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2008-06-12 |
Time |
08:52 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2008-05-21 |
Time |
14:51 |
Sent To |
|
|
Notes |
2008-05-21 14:52:28 | TO "Z" BOX |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2008-07-16 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-07-16 |
Time |
14:28 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2008-07-16 |
Time |
14:28 |
Sent To |
G |
|
Notes |
2008-07-16 14:32:37 | ****************PROVISO**************** | | PER FLORIDA STATUTES 489.105 (3)(M) THE REQUIRED | | BACKFLOW PREVENTER FOR THE POTABLE WATER SUPPLY SHALL | | BE INSTALLED BY A LICENSED PLUMBING CONTRACTOR NOT THE | | POOL CONTRACTOR. | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2008-05-30 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-05-30 |
Time |
16:00 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2008-05-30 |
Time |
16:00 |
Sent To |
G |
|
Notes |
2008-05-30 16:12:46 | PLUMBING PLAN REVIEW: | | DENIED: | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | 1. SHEET 2, PIPING SCHEMATIC: CLEARLY INDICATE THE | | "AQUA LOGIC W/SALT CHLORINATOR" LOCATION ON THE PIPING | | SCHEMATIC. PER (W.P.B. AS AMENDED) SECTION 106.1.1 | | INFORMATION ON CONTRUCTION DOCUMENTS. | | | | 2.SHEET 2: PLEASE CORRELATE AND CLEARLY INDICATE THE | | VENT PIPE SIZE AS BEING 1-1/2" ON THE MAIN DRAIN DETAIL | | AND PIPING SCHEMATIC AS IT IS BEING INDICATED AS SUCH | | IN THE "ATMOSPHERIC VENT DETAIL". PER (W.P.B. AS | | AMENDED) SECTION 106.1.1 INFORMATION ON CONSTRUCTION | | DOCUMENTS. | | | | 3. CLEARLY INDICATE WHICH MODEL POOL HEATER IS BEING | | USED ON THE RESUBMITTED POOL HEATER MANUFACTURE SHEET. | | NOTE: THERE ARE SIX DIFFERENT MODELS BEING INDICATED ON | | THIS SUBMITTAL. PER (W.P.B. AS AMENDED) SECTION 106.1.2 | | ADDITIONAL DATA. | | | | ********IMPORTANT INFORMATION******** | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | END OF COMMENTS: | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | PHONE= (561) 805-6730 | | FAX= (561) 805-6731 | | E-MAIL= [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
P |
Date |
2008-10-10 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2008-10-10 |
Time |
08:47 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2008-10-10 |
Time |
08:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
2008-09-21 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2008-09-21 |
Time |
15:11 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2008-09-21 |
Time |
15:10 |
Sent To |
I |
|
Notes |
2008-09-21 15:11:01 | ***ZONING FAILED*** | | | | 1. PLEASE PROVIDE ALL RESPONSES IN WRITING. | | | | 2. AS THE PROPOSED FENCE/WALL/GATE MAY ENCROACH INTO A | | UTILITY EASEMENT, EASEMENT CONSENT FORMS ARE REQUIRED | | FROM THE FOLLOWING UTILITY COMPANIES: | | | | WEST PALM BEACH PUBLIC UTILITIES DEPARTMENT | | 200 2ND STREET | | CITY HALL, 1ST FLOOR | | WEST PALM BEACH, FL 33401 | | (561)822-1300 | | | | FLORIDA POWER AND LIGHT | | 810 CHARLOTTE AVE | | WEST PALM BEACH, FL 33401 | | (561)697-8000 | | | | FLORIDA PUBLIC UTILITIES | | 401 SOUTH DIXIE HWY | | WEST PALM BEACH, FL 33402 | | (561)832-2461 | | | | BELL SOUTH | | 2021 SOUTH MILITARY TRAIL | | WEST PALM BEACH, FL 33415 | | (561)439-9110 | | | | COMCAST | | 1401 NORTHPOINT PKWY | | WEST PALM BEACH, FL 33407 | | (561)655-3842 - RESIDENTIAL | | (561)227-4261 - COMMERCIAL | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | CONTACT ME. | | | | MAGGIE CRUZ, ASSOCIATE PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: (561) 822-1444 OR (561) 805-6720 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2008-07-08 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2008-07-08 |
Time |
09:37 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2008-07-08 |
Time |
09:37 |
Sent To |
E |
|
Notes |
2008-07-08 09:38:55 | ***APPROVED - RESUB #1*** | | | | PROVISO:PLANT MATERIALS USED SHALL BE EQUAL TO OR | | BETTER THAN FLORIDA DEPARTMENT OF AGRICULTURE NUMBER 1 | | NURSERY GRADE STANDARD. | | | | NOTE:THE EXISTING PERMANENT FENCE MUST COMPLETELY | | RESTRICT ACCESS TO THE POOL AREA AND COMPLY WITH | | SECTION 94-304(D)(2)(B)+(C) OF THE ZLDRS: | | B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE | | OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT | | ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF | | THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED. | | BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN | | HEIGHT ABOVE GRADE. | | C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE | | THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND | | SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR | | WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF | | GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL | | SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH | | WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT | | SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A | | 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE, | | AT THE PROPERTY LINE, TO ENSURE PRIVACY. | | | | | | | | | | SENT TO "E" - DP |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2008-05-28 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2008-05-28 |
Time |
11:27 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2008-05-28 |
Time |
11:27 |
Sent To |
E |
|
Notes |
2008-05-28 11:34:00 | ***FAILED*** | | | | | | 1)THE POOL EQUIPMENT AT IT'S PROPOSED LOCATION DOES | | NOT MEET THE MINIMUM SETBACK REQUIREMENTS AS REQUIRED | | BY SECTION 94-305 THE CITY OF WEST PALM BEACH ZONING | | AND LAND DEVELOPMENT REGULATIONS (ZLDRS):MECHANICAL | | EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A | | REQUIRED SETBACK. | | | | THE REQUIRED REAR SETBACK FOR THIS PROPERTY IS 11.9 | | FEET (10% OF THE LOT DEPTH), WITH THE ALLOWABLE 4' | | ENCROACHMENT FOR MECHANICAL EQUIPMENT, THIS YIELDS A | | MINIMUM REAR SETBACK OF 7.9 FEET TO THE POOL EQUIPMENT. | | PLANS SHALL INDICATE COMPLIANCE. | | | | 2)IN CONJUCTION WITH THE ADDITION PERMIT, THIS | | PROPERTY'S IMPROVEMENTS NOW EXCEED 50% OF THE | | STRUCTURE'S VALUE, MEASURED WITHIN A 12 MONTH PERIOD. | | PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND | | DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF THE | | PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE | | (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY | | APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE | | WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF | | THE ZLDRS. | | | | | | NOTE:THE EXISTING PERMANENT FENCE MUST COMPLETELY | | RESTRICT ACCESS TO THE POOL AREA AND COMPLY WITH | | SECTION 94-304(D)(2)(B)+(C) OF THE ZLDRS: | | B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE | | OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT | | ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF | | THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED. | | BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN | | HEIGHT ABOVE GRADE. | | C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE | | THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND | | SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR | | WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF | | GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL | | SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH | | WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT | | SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A | | 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE, | | AT THE PROPERTY LINE, TO ENSURE PRIVACY. | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | ZONING TECHNICIAN (561)805-6720 |
|
|