2008-05-23 14:55:54 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST. |
| REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| |
| 1- SPECIFY HOW COMPLYING WITH THE EGRESS REQUIREMENTS |
| OF SEC. R310.4OF 2004 RESIDENTIAL CODE IF ALL |
| OPENINGS ARE GOING TO HAVE SHUTTERS.NEED AT LEAST ONE |
| MEANS OF EGRESS WHEN SHUTTERS ARE UP. |
| |
| 2-TRANSPARENTSHUTTERS: |
| A) SHUTTERS DRAWINGSSUBMITTED FORTRANSPARENT |
| SHUTTERSNEED TO BE REVISED. ACCORDING TO FLORIDA |
| PRODUCT APPROVALFL6417THEAPPROVED DRAWING IS |
| #03-155-1343B (SEE ATTACHED COPY). DRAWING SUBMITTED |
| WAS #03-155-1343A.ANCHOR SCHEDULE IS DIFFERENT ON |
| THIS DRAWINGS. THEREFORE NEED TO USE THE DRAWINGSTHAT |
| WEREAPPROVED WITHTHE PRODUCT APPROVAL. AND REVISE |
| ANCHOR SCHEDULE AS REQUIRED. |
| |
| B)ENGINEER WIND LOADS FOR WALL COMPONENTS & |
| CLADDINGSUBMITTED IS ONLY GOOD FORTRIBUTARY AREA OF |
| 20S.F..THERE ARE SOME OPENINGS THAT ARE SMALLER THAN |
| 20S.F. AND DESIGN PRESSURES ARE HIGHER. PROVIDE THE |
| DESIGN PRESSURES FOR OPENINGS SMALLER THAN 20S.F. |
| (THIS APPLIES TO ROLLDOWN SHUTTERS TOO). |
| |
| ***NOTE: SEPARATE ENGINEER CALCULATIONS ARE NOT |
| REQUIRED.CONTRACTOR MAY USE COMPONENT AND CLADDING |
| WIND LOAD TABLESR301.2(2)ANDR301.2(3) OF 2004 |
| FLORIDA RESIDENTIAL CODE AS A REFERENCE TO DETERMINE |
| THE DESIGN PRESSURES. |
| |
| C) PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE |
| ATTACHED SAMPLE OR PROVIDE ANY OTHER METHODTHAT |
| PROVIDESALL THE INFORMATION REQUIREDON THE SAMPLE |
| PROVIDED. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 TO |
| VERIFY COMPLIANCE WITH THE PRODUCT APPROVALPROPOSED |
| INSTALLATION ANDDESIGN CRITERIA OF SEC. R301 2004 |
| FLORIDA RESIDENTIAL CODE. (THIS APPLIES TO ROLL DOWN |
| SHUTTERS ALSO). |
| |
| 3-ROLL DOWN SHUTTERS: |
| A) CLARIFY WHY SUBMITTINGENGINEER'SPRODUCT |
| APPROVAL APPROVAL LETTER.THIS LETTER IS NOT REQUIRED, |
| BUT IF CONTRACTOR WANTS TO SUBMITT LETTER, THEN IT |
| NEEDS TO BE REVISED.THE MAXIMUM DESIGN PRESSURES ARE |
| INCORRECT.THERE ARE SOME OPENINGS THAT ARE SMALLER |
| THAN THE 20 S.F. TRIBUTARY AREASPECIFIED BY THE OTHER |
| ENGINEER WHO PROVIDED THE DESIGN PRESSURES. SEE ITEM |
| 2(B) ABOVE. ALSO,THE ANCHOR MINIMUM EDGE DISTANCE |
| OF 3/4" NEEDS TO BE REVISED AS REQUIRED ON SHEET 05 OF |
| 11. SEE TYPICAL EDGE DISTANCEIN WOOD NOTE. IT |
| REQUIRES 1-1/4"EDGE DISTANCE. OTHERWISE A REDUCTION |
| FACTOR IS REQUIRED. |
| ALSO, CLARIFY WHATDOES THE ENGINEER MEANS BY SHUTTER |
| TO BE INSTALLED "TO EXISTING DADE COUNTY PINE HOST |
| STRUCTURE",SINCE THIS PROPERTY ISNOT LOCATED IN |
| DADE COUNTY AND THE PRODUCT APPROVAL IS NOT A DADE |
| COUNTY NOA EITHER. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |