Plan Review Details - Permit 08050512
Plan Review Stops For Permit 08050512
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-06-11 Cont ID  
Sent By jgomez Date 2008-06-11 Time 17:00 Rev Time 0.00
Received By jgomez Date 2008-06-11 Time 17:00 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-06-04 Cont ID  
Sent By jgomez Date 2008-06-04 Time 14:03 Rev Time 0.00
Received By jgomez Date 2008-06-04 Time 14:03 Sent To PC
Notes
2008-06-04 14:04:07RESIDENTIAL (R3)DOORS AND WINDOWS REPLACEMENT,
 BUILDING REVIEW SECOND CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- PROVIDE 2 COMPLETE COPIES OF PRODUCT APPROVALS AS
 REQUIRED BY DCA RULE 9B-72 FOR:
 A) WINDOWS AS SHOWN ON FLOOR PLAN.(REPEAT
 COMMENT).
 FLOOR PLANSHOWS 5 DOUBLE HUNG WINDOWS.PRODUCT
 APPROVAL SUBMITTED NOA 03-0701.02 IS FOR
 SIDELITE/TRANSOM WINDOW ONLY.PROVIDE 2 COPIES OF
 CORRECT PRODUCT APPROVAL.
 B) FRENCH DOORS AS SHOWN ON FLOOR PLAN.NEED 2
 COPIES. ONLY ONE WAS SUBMITTED.
  
 ***NOTE: CLARIFY WHY SUBMITTING PRODUCT APPROVALS FOR
 MULLIONS IF FLOOR PLAN DOESN'T SHOW ANY WINDOWS OR
 DOORS MULLED TOGETHER.
  
 2- A) ENGINEER TO PROVIDE CALCULATIONS FOR DESIGN
 PRESSURES FOR WINDOW 101.ACCORDING TO SITE PLAN
 DRAWING. THIS WINDOW IS LOCATED ON THE END ZONE.SEE
 TABLE R301.2(2) AND FIGURE R301.2(8) OF 2004 FLORIDA
 RESIDENTIAL CODE AND REVISE AS REQUIRED. (REPEAT
 COMMENT).
  
 B) REVISE WOOD FRAME HEADER/SILL DETAIL:NOTE
 RELATING TO TOP HEADER BUCK SPECIFIES 1" X 3" P.T. WOOD
 BUCK CONT. WITH 1/4" X 2-1/4"WOOD SCREWS SPACED MAX.
 24" O.C..WOOD SCREWS CAN'T BE USED TO ATTACH TO
 CONCRETE BLOCK. REVISE AS REQUIRED. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004. (REPEAT COMMENT).
  
 3-OWES $80.36 FOR UPDATED VALUATION AS REQUIRED BY
 SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
 NOTE: ADDITIONAL RESUBMITTAL FEES WILL BE ASSESSED
 ALSO.
  
 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BYSEC. 713.13 FLORIDA STATUTE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-05-20 Cont ID  
Sent By jgomez Date 2008-05-20 Time 10:54 Rev Time 0.00
Received By jgomez Date 2008-05-20 Time 10:54 Sent To PC
Notes
2008-05-20 13:35:51RESIDENTIAL (R3)DOORS AND WINDOWS REPLACEMENT,
 BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- PROVIDE 2 COMPLETE COPIES OF PRODUCT APPROVALS AS
 REQUIRED BY DCA RULE 9B-72 FOR:
 A) WINDOWS AS SHOWN ON PLANS.
 B) FRENCH DOORS AS SHOWN ON PLANS.
 C) SHUTTERS (SEE ITEM #4).
  
 ***INFORMATION SUBMITTED IS NOT A PRODUCT APPROVAL.
  
 2- A) ENGINEER TO PROVIDE CALCULATIONS FOR DESIGN
 PRESSURES FOR WINDOW 101.ACCORDING TO SITE PLAN
 DRAWING. THIS WINDOW IS LOCATED ON THE END ZONE.SEE
 TABLE R301.2(2) AND FIGURE R301.2(8) OF 2004 FLORIDA
 RESIDENTIAL CODE AND REVISE AS REQUIRED.
  
 B) REVISE WOOD FRAME HEADER/SILL DETAIL:NOTE
 RELATING TO TOP HEADER BUCK SPECIFIES 1" X 3" P.T. WOOD
 BUCK CONT. WITH 1/4" X 2-1/4"WOOD SCREWS SPACED MAX.
 24" O.C..WOOD SCREWS CAN'T BE USED TO ATTACH TO
 CONCRETE BLOCK. REVISE AS REQUIRED. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW IF INCLUDING WINDOWSAND DOORS REMOVAL,
 INSTALLATION OF 5 DOUBLE HUNG "ANDERSEN" WINDOW AND ONE
 PAIR OFFRENCH DOORS AND ENGINEERING SUBMITTED.NEED
 TO UPDATE VALUATION TO INCLUDE ALL THESE ITEMS. SEC.
 108.3 CITY AMENDMENTS TO FBC 2004.
  
 4- IF DOORS AND WINDOWS DON'T HAVE IMPACT GLASS, THEN
 NEED TO PROVIDEPRODUCT APPROVAL FOR STORM SHUTTERS AS
 REQUIRED BY SEC. R301.2.1.2 OF 2004 FLORIDA RESIDENTIAL
 CODE.ALSO,PROVIDECOMPLETE INSTALLATION SCHEDULE.
 SEE ATTACHED SAMPLE OF INSTALLATION SCHEDULE.ALSO,
 CLEARLY MARK ON SHUTTERS DRAWINGS SPECIFIC MOUNTING
 CONDITIONS (EG: WALL MOUNTED, BUILT OUT, ETC)AND
 SPECIFIC ANCHOR TYPE AND SPACING TO BE USED.SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004 TO VERIFY
 COMPLIANCE WITH SEC. R301 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 5- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BYSEC. 713.13 FLORIDA STATUTE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-10 Cont ID  
Sent By adarroug Date 2008-06-10 Time 10:16 Rev Time 0.00
Received By adarroug Date 2008-06-10 Time 10:16 Sent To B
Notes
2008-06-10 10:16:48TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-03 Cont ID  
Sent By adarroug Date 2008-06-03 Time 09:44 Rev Time 0.00
Received By adarroug Date 2008-06-03 Time 09:44 Sent To B
Notes
2008-06-03 09:44:37TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-20 Cont ID  
Sent By jgomez Date 2008-05-20 Time 14:14 Rev Time 0.00
Received By jgomez Date 2008-05-20 Time 14:14 Sent To  
Notes
***NONE***