Plan Review Details - Permit 08050493
Plan Review Stops For Permit 08050493
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-10-20 Cont ID  
Sent By shill Date 2008-10-20 Time 16:27 Rev Time 0.00
Received By shill Date 2008-10-20 Time 16:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-08-18 Cont ID  
Sent By shill Date 2008-08-18 Time 08:36 Rev Time 0.00
Received By shill Date 2008-08-18 Time 08:36 Sent To  
Notes
2008-08-18 08:39:08****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1.THE REMOVAL INSTRUCTIONS STATE TO CUT ALL ROPES.
 SEE FBC3105.4.2.1, QUICK RELEASE REQUIRED.IT APPEARS
 THAT THE INSTRUCTIONS REQUIRE TWICE AS MUCH WORK AS IS
 ACTUALLY REQUIRED; AREN'T ONLY THE ROPES PERPENDICULAR
 TO THE FRAME REQUIRED TO BE CUT?PLEASE REVISE.
  
 PLEASE INCORPORATE THIS CHANGE INTO THE REMOVAL
 INSTRUCTIONS.INSTRUCTIONS SHOULD BE CLEAR; STEP ONE
 STILL STATES "CUT ALL ROPES".
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-05-30 Cont ID  
Sent By shill Date 2008-05-30 Time 16:25 Rev Time 0.00
Received By shill Date 2008-05-30 Time 16:25 Sent To  
Notes
2008-05-30 16:28:40****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.THE REMOVAL INSTRUCTIONS STATE TO CUT ALL ROPES.
 SEE FBC3105.4.2.1, QUICK RELEASE REQUIRED.IT APPEARS
 THAT THE INSTRUCTIONS REQUIRE TWICE AS MUCH WORK AS IS
 ACTUALLY REQUIRED; AREN'T ONLY THE ROPES PERPENDICULAR
 TO THE FRAME REQUIRED TO BE CUT?PLEASE REVISE.
  
 2.PROVIDE A LETTER FROM THE OWNER WHICH ACKNOWLEDGES
 THEIR RESPONSIBILITY TO HAVE THE AWNING COVER REMOVED
 PRIOR TO ANY WIND EVENT WITH PROJECTED WIND SPEEDS OF
 75MPH OR GREATER.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-10-15 Cont ID  
Sent By adarroug Date 2008-10-15 Time 10:53 Rev Time 0.00
Received By adarroug Date 2008-10-15 Time 10:53 Sent To Z
Notes
2008-10-15 10:53:34TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-08-04 Cont ID  
Sent By adarroug Date 2008-08-04 Time 09:05 Rev Time 0.00
Received By adarroug Date 2008-08-04 Time 09:05 Sent To B
Notes
2008-08-04 09:05:43TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-23 Cont ID  
Sent By adarroug Date 2008-07-23 Time 10:42 Rev Time 0.00
Received By adarroug Date 2008-07-23 Time 10:42 Sent To Z
Notes
2008-07-23 10:42:23TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-30 Cont ID  
Sent By shill Date 2008-05-30 Time 16:28 Rev Time 0.00
Received By shill Date 2008-05-19 Time 15:12 Sent To  
Notes
2008-05-19 15:13:07TO "Z" BOX

Review Stop Z ZONING
Rev No 3 Status P Date 2008-10-17 Cont ID  
Sent By adavila Date 2008-10-17 Time 13:44 Rev Time 0.00
Received By adavila Date 2008-10-17 Time 10:34 Sent To I
Notes
2008-10-17 13:44:15PER ERIC SCHNEIDER, PRINCIPAL PLANNER.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2008-08-01 Cont ID  
Sent By adavila Date 2008-08-01 Time 13:15 Rev Time 0.00
Received By adavila Date 2008-07-29 Time 13:15 Sent To  
Notes
2008-08-01 13:16:25PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. THE SURVEY SUBMITTED IS FROM 2004 AND DOES NOT
 REFLECT THE LATEST APPROVED PLANS FOR THE SUBJECT
 PROPERTY.SUBMIT TWO (2) COPIES OF A SURVEY LESS THAN
 A YEAR OLD, AND AN UPDATED SITE PLAN SHOWING THE
 RELATIONSHIP OF THE PROPOSED AWNINGS WITH THE EXISTING
 BUILDING AND THE SURROUNDING PROPERTY LINES.SITE PLAN
 SHALL ALSO SHOW THE LOCATION OF THE COLUMNS IN RELATION
 TO THE PARKING SPACES.
  
 2. REPEAT COMMENT - INDICATE SETBACK DIMENSIONS FROM
 PROPOSED AWNINGS TO ALL SURROUNDING PROPERTY LINES.
  
 A. THE SUBMITTED SURVEY DOES NOT CLEARLY SHOW THE
 SETBACK DIMENSIONS FROM THE PROPERTY LINES TO THE
 COLUMNS OF THE AWNINGS.SOME NOTES INDICATE 5 FEET TO
 THE POLES, WHILE OTHERS INDICATE 3 FEET TO THE POLES.
 PLEASE CLARIFY.
 B. PLEASE NOTE THAT THE COLUMNS SHALL BE SET BACK A
 MINIMUM OF 5 FEET FROM THE PROPERTY LINES PURSUANT TO
 SECTION 94-145 OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS ("ZLDRS").
  
 3. ACCORDING TO THE LATEST APPROVED LANDSCAPE PLANS,
 TREES ARE TO BE PLANTED ALONG THE WEST PROPERTY LINE
 AND ON THE TERMINAL LANDSCAPE ISLAND ON THE NORTHEAST
 CORNER OF THE BUILDING.THE PROPOSED AWNING SHALL NOT
 PRESENT ANY CONFLICT WITH THE EXISTING AND PROPOSED
 LANDSCAPING.
  
 4. PLEASE CLARIFY THE USE OF THE PARKING SPACES ALONG
 THE WEST PROPERTY LINE AND THE NORTH BUILDING FACADE.
 PREVIOUS PLANS APPROVED FOR THE SUBJECT PROPERTY DO NOT
 SHOW 90 DEGREE PARKING SPACES ALONG THE WEST PROPERTY
 LINE.IF THESE PARKING SPACES WILL BE USED AS CUSTOMER
 OR EMPLOYEE PARKING, THE PARKING SPACES SHALL COMPLY
 WITH THE ZONING AND LAND DEVELOPMENT REGULATIONS.
 PLEASE REVISE.
  
 5. IT APPEARS THAT THE COLUMNS OF THE AWNINGS ARE
 ENCROACHING INTO THE DRIVE AISLE.NO STRUCTURES SHALL
 ENCROACH INTO ANY DRIVE AISLE.PLEASE REVISE.
  
 6. PLEASE SHOW THE LOCATION OF THE PROPERTY LINE ON THE
 ELEVATION.PLEASE NOTE THAT THE AWNING MAY NOT PROJECT
 MORE THAN 3 FEET INTO ANY SETBACK PER SECTION
 94-305(B)(2).
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-05-27 Cont ID  
Sent By choops Date 2008-05-27 Time 09:36 Rev Time 0.00
Received By choops Date 2008-05-27 Time 09:36 Sent To B
Notes
2008-05-27 09:41:56***FAILED***
  
  
 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED AWNINGS
 TO ALL SURROUNDING PROPERTY LINES.
  
 NOTE:PLANS SHALL SHOW COMPLIANCE WITH THE MINIMUM
 FIVE (5) FOOT SIDE AND REAR SETBACK REQUIREMENTS FOUND
 IN SECTION 94-145 OF THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS.
  
 2)PROVIDE A DETAIL OF HOW THE STRUCTURAL POSTS
 CORRELATE WITH THE EXISTING PARKING SPACES.
 POSTS/AWNINGS SHALL NOT INTERFERE WITH PARKING OR THE
 OPENING OF DOORS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "B" - MISC. 2