Plan Review Details - Permit 08050395
Plan Review Stops For Permit 08050395
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-06-09 Cont ID  
Sent By rmcdouga Date 2008-06-09 Time 10:42 Rev Time 0.00
Received By rmcdouga Date 2008-06-09 Time 10:42 Sent To  
Notes
2008-06-09 10:44:20BUILDING PROVISO
 THE WALL SHEATHING IS REQUIRED TO BE INSPECTED BY THE
 CITY BUILDING INSPECTOR BEFORE IS IS COVERED WITH LATH
 AND STUCCO.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-05-23 Cont ID  
Sent By rmcdouga Date 2008-05-23 Time 15:54 Rev Time 0.00
Received By rmcdouga Date 2008-05-23 Time 15:54 Sent To  
Notes
2008-05-23 15:54:202004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATIONS
  
 DENIED BY BUILDING
  
 1) THE NAME OF THE PERSON RESPONSIBLE FOR THE DRAWING
 IS REQUIRED ON EACH SHEET. SEE FBC 106.3.4.3* CITY
 AMENDMENTS.
  
 2) THE FLOOR PLAN DOES NOT SPECIFY WHICH DOORS AND
 WINDOWS ARE BEING REPLACED. THE PLAN APPEARS TO SHOW
 ONE OF THE WINDOWS IN BED ROOM #2 BEING REPLACED BY A
 DOOR. PLEASE CLEARLY INDICATE THE DOORS AND WINDOWS
 THAT WILL BE REPLACED. FBC 106.1.1* CITY AMENDMENTS
  
 3)SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 EXTERIOR DOORS. DCA RULE 9B-72
  
 4) THE DRYWALL SCREW SPACING INFORMATION FOR THE FIELD
 IS MISSING FROM THE BOTTOM OF THE INTERIOR WALL SECTION
 DRAWING.
  
 5) THE EXISTING WALL SHEATHING WILL NEED TO BE
 INSPECTED BY THE BUILDING INSPECTOR AFTER THE ALUMINUM
 SIDING IS REMOVED AND BEFORE IT IS COVERED.
  
 7) ASTM C 926 REQUIRES THE STUCCO TO BE 7/8" THICK.
 PLEASE REVISE PLAN.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-05-19 Cont ID  
Sent By btrobaug Date 2008-05-19 Time 11:53 Rev Time 0.00
Received By btrobaug Date 2008-05-19 Time 11:06 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-29 Cont ID  
Sent By adarroug Date 2008-05-29 Time 12:56 Rev Time 0.00
Received By adarroug Date 2008-05-29 Time 12:56 Sent To M
Notes
2008-05-29 12:56:38TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-23 Cont ID  
Sent By rmcdouga Date 2008-05-23 Time 15:54 Rev Time 0.00
Received By rmcdouga Date 2008-05-15 Time 11:44 Sent To  
Notes
2008-05-15 11:44:35TO "SFR" "E"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-05-30 Cont ID  
Sent By tgordon Date 2008-05-30 Time 08:06 Rev Time 0.20
Received By tgordon Date 2008-05-30 Time 08:06 Sent To P
Notes
2008-05-30 08:07:00*** PROVISO ***
 1) A MECHANICAL (A/C) PERMIT WILL BE REQUIRED FOR THE
 BATHROOM EXHAUST FAN.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-05-15 Cont ID  
Sent By tgordon Date 2008-05-15 Time 12:18 Rev Time 0.25
Received By tgordon Date 2008-05-15 Time 12:18 Sent To E
Notes
2008-05-15 12:20:39*** PROVISO ***
 1) A MECHANICAL (A/C) PERMIT WILL BE REQUIRED FOR THE
 BATHROOM EXHAUST FAN.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-06-09 Cont ID  
Sent By mperson Date 2008-06-09 Time 08:54 Rev Time 0.00
Received By mperson Date 2008-06-09 Time 08:54 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-05-20 Cont ID  
Sent By mperson Date 2008-05-20 Time 08:10 Rev Time 0.00
Received By mperson Date 2008-05-20 Time 08:10 Sent To B
Notes
2008-05-20 09:00:08PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. BEING HOW THE SUBMITTED FLOOR PLAN IS NOT TO
 MIMIMUM 1/8 SCALE. PER (W.P.B. AS AMENDED) SECTION
 106.1.3 QUALITY OF BUILDING PLANS. CLEARLY INDICATE THE
 SIZE OF THE PROPOSED SHOWER COMPLIANT WITH FBC-2004
 PLUMBING SECTION 417.4 SHOWER COMPARTMENTS. MINIMUM OF
 900 SQUARE INCHES OF INTERIOR CROSS-SECTIONAL AREA
 REQUIRED.
  
 2. THE SUBMITTED SANITARY PLUMBING ISOMETRIC IS
 INDICATING A FUTURE LAV, HOWEVER THE FLOOR PLAN HAS NO
 INDICATION OF THIS FUTURE LAVS LOCATION. CLEARLY
 INDICATE THE LOCATION OF THIS FUTURE LAV ON THE
 RESUBMITTED FLOOR PLAN. PER (W.P.B. AS AMENDED) SECTION
 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS AND
 FBC-2004 PLUMBING SECTION 701.1 SCOPE.
  
 3. NOTE: PER THE SUBMITTED SANITARY PLUMBING ISOMETRIC
 IT APPEARS THAT THE FUTURE LAV IS IN THE NEW BATHROOM
 BY THE SHOWER, HOWEVER IT ALSO APPEARS THAT THERE IS
 NOT ENOUGH ROOM FOR THE LAV COMPLIANT WITH FBC-2004
 PLUMBING SECTION 405.3.1, LAVATORY SHALL NOT BE SET
 CLOSER THAN 15 INCHES FROM ITS CENTER TO ANY SIDE WALL,
 PARTITION, VANITY OR ANY OTHER OBSTRUCTION. PLEASE
 CLARIFY THIS ON THE RESUBMITTAL.
  
 4. THE SANITARY PLUMBING ISOMETRIC IS INDICATING THE
 SHOWER BEING VENTED BY A HORIZONTAL DRY VENT.
 HORIZONTAL DRY VENTS ARE NOT COMPLIANT PER FBC-2004
 PLUMBING SECTION 905.3 VENT CONNECTION TO DRAINAGE
 SYSTEM. NOTE: FUTURE FIXTURES MAY NEVER BE INSTALLED,
 IF THE LAV WAS NOT INDICATED AS A FUTURE LAV THIS WOULD
 BE COMPLIANT.
  
 5. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
 *THE PRINTED AND SIGNED NAME OF THE PERSON TAKING THE
 RESPONSIBILITY OF THE SANITARY PLUMBING ISOMETRIC
 REQUIRED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved