Plan Review Details - Permit 08050263
Plan Review Stops For Permit 08050263
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-08-12 Cont ID  
Sent By rmcdouga Date 2008-08-12 Time 14:30 Rev Time 0.00
Received By rmcdouga Date 2008-08-12 Time 14:29 Sent To  
Notes
2008-08-12 14:37:112004 FBC W/2007 REVISIONS
 LEVEL 3 ALTERATION AND REVISION
  
 DENIED BY BUILDING
  
 1) SEE COMMENTS FOR THE PREVIOUS REVIEW (COPY ATTACHED)
 , NONE OF WHICH HAVE BEEN ADDRESSED.
  
 2) VALUE OF THE WORK HAS BEEN INCREASED TO %31,255.00.
 ADDITIONAL FEES ARE DUE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-05-20 Cont ID  
Sent By rmcdouga Date 2008-05-20 Time 10:23 Rev Time 0.00
Received By rmcdouga Date 2008-05-20 Time 10:23 Sent To  
Notes
2008-05-20 12:15:242004 FBC W/2007 REVISIONS
 LEVEL 3 ALTERATIONS AND ADDITION
  
 DENIED BY BUILDING
  
 1) THE VALUE OF THE WORK LISTED ON THE APPLICATION IS
 LOW. PLEASE INCREASE THE VALUE FOR THE WORK ON THE
 APPLICATION. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE MATERIALS, LABOR, DESIGN FEES, OVERHEAD AND
 PROFIT AS WOULD BE CHARGED BY A CONTRACTOR. FBC 108.3*
 CITY AMENDMENTS.
  
 2)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 3) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED. (561) 233-5025
  
 4) ON SHEET A-1.1 UNDER THE WOOD TRUSS SECTION, PLEASE
 REVISE THE WIND SPEED TO 140 MPH. SEE FBC R FIGURE
 R301.2(4).
  
 5) UNDER GENERAL DESIGN CRITERIA ON SHEET A-1.1 PLEASE
 ADD 2007 AMENDMENTS TO APPLICABLE CODES.
  
 6) ON THE PLANS, SPECIFY THE DISTANCES TO THE PROPERTY
 LINES AND OTHER STRUCTURES AT THE ADDITION. SEE FBC R
 R302.1 EXTERIOR WALLS.
 EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM)
 SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE
 RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL
 NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM
 AN ADJACENT PROJECTION OR WALL.
  
 7) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR EXTERIOR
 WINDOWS, DOORS, STORM PANELS, ROOF COVERING AND TRUSS
 CONNECTORS AS REQUIRED BY DCA RULE 9B-72.
  
 8)FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 9) SUBMIT TWO COPIES OF A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY THE MOUNT TYPE,
 ANCHOR TYPE AND SPACING, SPANS, EDGE DISTANCE, GLASS
 SEPARATION, ETC. FROM THE PRODUCT APPROVAL THAT WILL BE
 USED. SEE ATTACHED SAMPLE INSTALLATION SCHEDULE. SEE
 R301.2.1.2 PROTECTION OF OPENINGS.
  
 10) SHOW COMPLIANCE WITH R317.1 TWO-FAMILY DWELLINGS.
 DWELLING UNITS IN TWO-FAMILY DWELLINGS SHALL BE
 SEPARATED FROM EACH OTHER BY WALL AND/OR FLOOR
 ASSEMBLIES HAVING NOT LESS THAN 1-HOUR FIRE -RESISTANCE
 RATING WHEN TESTED IN ACCORDANCE WITH ASTM E 119. FIRE
 -RESISTANCE-RATED FLOOR-CEILING AND WALL ASSEMBLIES
 SHALL EXTEND TO AND BE TIGHT AGAINST THE EXTERIOR WALL,
 AND WALL ASSEMBLIES SHALL EXTEND TO THE UNDERSIDE OF
 THE ROOF SHEATHING.
 R317.1.1 SUPPORTING CONSTRUCTION.
 WHEN FLOOR ASSEMBLIES ARE REQUIRED TO BE FIRE
 -RESISTANCE-RATED BY SECTION R317.1 , THE SUPPORTING
 CONSTRUCTION OF SUCH ASSEMBLIES SHALL HAVE AN EQUAL OR
 GREATER FIRE -RESISTIVE RATING.
 PROVIDE LISTED ASSEMBLY DETAILS.
  
 11) THE WINDOW AND DOOR SCHEDULE ON A-2.2 SPECIFIES
 STORM SHUTTERS ON ALL OPENINGS. SHOW COMPLIANCE WITH
 R310.4 BARS, GRILLS, COVERS AND SCREENS.
 BARS, GRILLS, COVERS, SCREENS OR SIMILAR DEVICES ARE
 PERMITTED TO BE PLACED OVER EMERGENCY ESCAPE AND RESCUE
 OPENINGS, BULKHEAD ENCLOSURES, OR WINDOWWELLS THAT
 SERVE SUCH OPENINGS, PROVIDED THE MINIMUM NET CLEAR
 OPENING SIZE COMPLIES WITH SECTIONS R310.1.1 TO
 R310.1.3 , AND SUCH DEVICES SHALL BE RELEASABLE OR
 REMOVABLE FROM THE INSIDE WITHOUT THE USE OF A KEY,
 TOOL OR FORCE GREATER THAN THAT WHICH IS REQUIRED FOR
 NORMAL OPERATION OF THE ESCAPE AND RESCUE OPENING. THE
 TEMPORARY INSTALLATION OR CLOSURE OF STORM SHUTTERS ,
 PANELS, AND OTHER APPROVED HURRICANE PROTECTION DEVICES
 SHALL BE PERMITTED ON EMERGENCY ESCAPE AND RESCUE
 OPENINGS DURING THE THREAT OF A STORM. SUCH DEVICES
 SHALL NOT BE REQUIRED TO COMPLY WITH THE OPERATIONAL
 CONSTRAINTS OF SECTION R310.1.4 . WHILE SUCH PROTECTION
 IS PROVIDED, AT LEAST ONE MEANS OF ESCAPE FROM THE
 DWELLING OR DWELLING UNIT SHALL BE PROVIDED. THE MEANS
 OF ESCAPE SHALL BE WITHIN THE FIRST FLOOR OF THE
 DWELLING OR DWELLING UNIT AND SHALL NOT BE LOCATED
 WITHIN A GARAGE WITHOUT A SIDE HINGED DOOR LEADING
 DIRECTLY TO THE EXTERIOR. OCCUPANTS IN ANY PART OF THE
 DWELLING OR DWELLING UNIT SHALL BE ABLE TO ACCESS THE
 MEANS OF ESCAPE WITHOUT PASSING THROUGH A LOCKABLE DOOR
 NOT UNDER THEIR CONTROL.
  
 12) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS.
 IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 )
 AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER.
  
 13) SHOW COMPLIANCE WITH R806.2 MINIMUM AREA.
 THE TOTAL NET FREE VENTILATING AREA SHALL NOT BE LESS
 THAN 1 TO 150 OF THE AREA OF THE SPACE VENTILATED
 EXCEPT THAT THE TOTAL AREA IS PERMITTED TO BE REDUCED
 TO 1 TO 300, PROVIDED AT LEAST 50 PERCENT AND NOT MORE
 THAN 80 PERCENT OF THE REQUIRED VENTILATING AREA IS
 PROVIDED BY VENTILATORS LOCATED IN THE UPPER PORTION OF
 THE SPACE TO BE VENTILATED AT LEAST 3 FEET (914 MM)
 ABOVE EAVE OR CORNICE VENTS WITH THE BALANCE OF THE
 REQUIRED VENTILATION PROVIDED BY EAVE OR CORNICE VENTS.
 AS AN ALTERNATIVE, THE NET FREE CROSS-VENTILATION AREA
 MAY BE REDUCED TO 1 TO 300 WHEN A VAPOR BARRIER HAVING
 A TRANSMISSION RATE NOT EXCEEDING 1 PERMIS INSTALLED
 ON THE WARM SIDE OF THE CEILING. SPECIFY THE SIZE AND
 SPACING OF THE ATTIC VENTS.
  
 14) SUBMIT ENERGY CALCULATION FORMS AS REQUIRED BY FBC
 13-600.
  
 15) SPECIFY THE INSULATION FOR THE EXTERIOR WALLS ON
 THE WALL SECTION. SEE FBC 13-600.
  
 16) THERE IS TWO DIFFERENT PLAN SHEET NUMBERED A-4.0.
 PLEASE CORRECT.
  
 17) UNDER GENERAL STRUCTURAL NOTE #1 ON SHEET A-4.0,
 PLEASE REVISE TO ASCE 7-02. SEE REFERENCED STANDARDS IN
 CHAPTER 43 OF 2004 FBC RESIDENTIAL.
  
 18) ON A-4.0 THE ROOF UPLIFT COMPONENT AND CLADDING
 PRESSURES ARE TOO LOW FOR EXPOSURE C WITH A 3:12 ROOF
 PITCH AND A 10 SQFT EFFECTIVE WIND AREA. SEE FBC R
 TABLE R301.2(2) AND R301.2(3).
  
 19) WALL SECTION 2 ON A-5.3 SPECIFIES A DOUBLE 2 X 8
 LEDGER W/ (2) 5/8" DIA. ANCHOR BOLTS AT 36" OC. PLEASE
 CLARIFY WHAT THEY WILL BE ANCHORED TO, AS THERE IS NO
 TIE BEAM SPECIFIED AT THIS LOCATION. ALSO SPECIFY THE
 LENGTH/ EMBED DEPTH FOR THE ANCHOR BOLTS.
  
 20) SPECIFY HOW THE WOOD BEAM (WD-1) SUPPORTING THE
 ROOF AT THE SECOND FLOOR BALCONY ON SHEET A-4.0 WILL BE
 CONNECTED TO THE STRUCTURE. R802.2.9.1 UPLIFT
 RESISTANCE. A CONTINUOUS LOAD PATH SHALL BE PROVIDED TO
 TRANSMIT THE UPLIFT FORCES FROM THE RAFTER OR TRUSS
 TIES TO THE FOUNDATION. FOR RAFTER CONSTRUCTION, STRAPS
 AND/OR CLIPS SHALL EXTEND SUCH THAT THE TOP NAIL IS
 WITHIN 1 INCH OF THE TOP OF THE RAFTER, OR SHALL BE
 WRAPPED AROUND THE TOP OF THE RAFTER WITH ONE OR MORE
 NAILS INSTALLED ON THE OPPOSITE SIDE OF THE RAFTER.
  
 21) SPECIFY THE CONNECTORS FOR THE ENDS OF THE DOUBLE 2
 X 12 RIDGE BEAM. FBC 106.1* CITY AMENDMENTS
  
 22) SPECIFY THE SIZE OF THE CEILING JOISTS OVER THE
 SECOND FLOOR BATH ROOM AND BALCONY. FBC 106.1* CITY
 AMENDMENTS
  
 23) SPECIFY RING SHANK NAILS FOR ROOF SHEATHING ON
 A-5.1 AS REQUIRED BY R803.2.3.1 SHEATHING FASTENINGS.
 WOOD STRUCTURAL PANEL SHEATHING SHALL BE FASTENED TO
 ROOF FRAMING WITH 8D RING-SHANK NAILS AT 6 INCHES ON
 CENTER AT EDGES AND 6 INCHES ON CENTER AT INTERMEDIATE
 FRAMING. WHERE ROOF FRAMING WITH A SPECIFIC GRAVITY,
 0.42 < G < 0.49 IS USED, SPACING OF RING-SHANK
 FASTENERS SHALL BE 4 INCHES ON CENTER IN NAILING ZONE 3
 FOR 130 MPH OR GREATER DESIGN WIND SPEEDS IN ACCORDANCE
 WITH FIGURE R803.2.3.1 .
  
 24) SPECIFY TWO LAYERS OF UNDERLAYMENTR905.3.3.1 LOW
 SLOPE ROOFS.
 FOR ROOF SLOPES FROM TWO AND ONE-HALF UNITS VERTICAL IN
 12 UNITS HORIZONTAL (2? :12), UP TO FOUR UNITS VERTICAL
 IN 12 UNITS HORIZONTAL (4:12), UNDERLAYMENT SHALL BE A
 MINIMUM OF TWO LAYERS UNDERLAYMENT APPLIED AS FOLLOWS:
  
 1.STARTING AT THE EAVE, A 19-INCH (483 MM) STRIP
 OF UNDERLAYMENT SHALL BE APPLIED PARALLEL WITH THE EAVE
 AND FASTENED SUFFICIENTLY IN PLACE.
 2.STARTING AT THE EAVE, 36-INCH-WIDE (914 MM)
 STRIPS OF UNDERLAYMENT FELT SHALL BE APPLIED,
 OVERLAPPING SUCCESSIVE SHEETS 19 INCHES (483 MM), AND
 FASTENED SUFFICIENTLY IN PLACE.
  
 25) PLEASE SUBMIT A RESPONSE LETTER WITH THE
 RESUBMITTAL, SPECIFYING HOW THE COMMENTS HAVE BEEN
 ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-07-29 Cont ID  
Sent By btrobaug Date 2008-07-29 Time 15:45 Rev Time 0.00
Received By btrobaug Date 2008-07-29 Time 15:26 Sent To M
Notes
2008-07-29 15:44:36 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER
 1AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THESE COMMENTS ARE FROM THE PREVIOUS REVIEW WITH NO
 RESPONSE AND HAVE NOT BEEN CORRECTED. PROVIDE A WRITTEN
 RESPONSE, REMOVE OLD AND VOIDED SHEETS AND PROVIDE ONE
 COPY OF THE OLD PLANS WHEN RESUBMITTING
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED. ADJUST THE VALUE AT THE PERMIT CLERK'S DESK,
 AND PAY THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 2} PER FS 489 A LICENSED CONTRACTOR IS REQUIRED TO
 APPLY FOR THIS PERMIT. ***UNLESS THE BUILDING IS NOT
 RENTED OR SOLD FOR AT LAEST ONE YEAR AFTER CO.
  
 3} INDICATE THE MAST AND CONDUCTOR SIZES ON THE RISER
 DIAGRAM, SHEET E-1.0. 215.5 2005 NEC.
  
 4} NOTE #1, SHEET E-1.0 INCORRECTLY REVERENCES FBC 2004
 (REVISED 2003), SEE REFERENCED STANDARDS 2007
 REVUSIONS.
  
 5} THE SMOKE DETECTOR CONNECTION DETAIL (ALSO SEE THE
 DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 NFPA-72,
 CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID
 CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE
 LOCATIONS OF THE SOUNDING DEVICES) DETAIL INDICATES
 KITCHEN OR BATH CIRCUIT FEED, SEE 210.12 FOR AFCI
 REQUIREMENTS.
  
 6} PANEL "B" HAS CIRCUITS MISLABELED AS "A".
  
 7} LOCATE AND INDICATE A DISCONNECTING MEANS FOR THE
 WATER HEATER. SEE 422.16 NEC FOR CORD AND PLUG
 RESTRICTIONS, AND 422.31(B) FOR HARDWIRE REQUIREMENTS.
  
 8} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14,RECEPTACLE PER 210.63.
  
 9} 210.11(C)(1) SMALL-APPLIANCE BRANCH CIRCUITS IN
 ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY
 OTHER PARTS OF THIS SECTION, TWO OR MORE 20-AMPERE
 SMALL-APPLIANCE BRANCH CIRCUITS SHALL BE PROVIDED FOR
 ALL RECEPTACLE OUTLETS SPECIFIED BY 210.52(B).
  
 10} 21.52(C)(1) WALL COUNTER SPACES A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT EACH WALL COUNTER SPACE THAT IS
 300 MM (12 IN.) OR WIDER. RECEPTACLE OUTLETS SHALL BE
 INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE
 THAN 600 MM (24 IN.) MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE.
  
 NEW COMMENT:
  
 11} } THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-05-15 Cont ID  
Sent By btrobaug Date 2008-05-15 Time 15:33 Rev Time 0.00
Received By btrobaug Date 2008-05-14 Time 16:00 Sent To P
Notes
2008-05-14 17:06:50 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER
 1AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED. ADJUST THE VALUE AT THE PERMIT CLERK'S DESK,
 AND PAY THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 2} PER FS 489 A LICENSED CONTRACTOR IS REQUIRED TO
 APPLY FOR THIS PERMIT.
  
 3} INDICATE THE MAST AND CONDUCTOR SIZES ON THE RISER
 DIAGRAM, SHEET E-1.0. 215.5 2005 NEC.
  
 4} NOTE #1, SHEET E-1.0 INCORRECTLY REVERENCES FBC 2004
 (REVISED 2003), SEE REFERENCED STANDARDS 2007
 REVUSIONS.
  
 5} THE SMOKE DETECTOR CONNECTION DETAIL (ALSO SEE THE
 DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 NFPA-72,
 CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID
 CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE
 LOCATIONS OF THE SOUNDING DEVICES) DETAIL INDICATES
 KITCHEN OR BATH CIRCUIT FEED, SEE 210.12 FOR AFCI
 REQUIREMENTS.
  
 6} PANEL "B" HAS CIRCUITS MISLABELED AS "A".
  
 7} LOCATE AND INDICATE A DISCONNECTING MEANS FOR THE
 WATER HEATER. SEE 422.16 NEC FOR CORD AND PLUG
 RESTRICTIONS, AND 422.31(B) FOR HARDWIRE REQUIREMENTS.
  
 8} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14,RECEPTACLE PER 210.63.
  
 9} 210.11(C)(1) SMALL-APPLIANCE BRANCH CIRCUITS IN
 ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY
 OTHER PARTS OF THIS SECTION, TWO OR MORE 20-AMPERE
 SMALL-APPLIANCE BRANCH CIRCUITS SHALL BE PROVIDED FOR
 ALL RECEPTACLE OUTLETS SPECIFIED BY 210.52(B).
  
 10} 21.52(C)(1) WALL COUNTER SPACES A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT EACH WALL COUNTER SPACE THAT IS
 300 MM (12 IN.) OR WIDER. RECEPTACLE OUTLETS SHALL BE
 INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE
 THAN 600 MM (24 IN.) MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-15 Cont ID  
Sent By adarroug Date 2008-07-15 Time 16:53 Rev Time 0.00
Received By adarroug Date 2008-07-15 Time 16:53 Sent To Z
Notes
2008-07-15 16:53:31TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-20 Cont ID  
Sent By rmcdouga Date 2008-05-20 Time 15:25 Rev Time 0.00
Received By rmcdouga Date 2008-05-12 Time 14:28 Sent To  
Notes
2008-05-12 14:28:54TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-07-30 Cont ID  
Sent By tgordon Date 2008-07-30 Time 09:33 Rev Time 0.45
Received By tgordon Date 2008-07-30 Time 09:33 Sent To P
Notes
2008-07-30 09:37:46PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) AS NOTED IN LAST REVIEW 5-12-08. PLEASE READ THE
 OWNER/BUILDER DISCLOSURE STATEMENT THAT YOU SIGNED. YOU
 MAY ONLY IMPROVE A ONE-FAMILY OR TWO-FAMILY RESIDENCE,
 YOUR RESIDENCE IT THREE FAMILY AND NEEDS A LICENSE
 CONTRACTOR TO APPLY FOR THE PERMIT, PER FS 489.
  
 2) AS NOTED IN LAST REVIEW 5-12-08. THE VALUE ON THE
 PERMIT MUST BE ADJUSTED TO THE FAIR MARKET VALUE
 (REPLACEMENT VALUE) WITH ALL MATERIALS AND LABOR. IF
 THE VALUE IS NOT ADJUSTED THEN THE CITY WILL NEED TO
 ADJUST IT USING THE MARSHALL & SWIFT NATIONAL VALUATION
 SERVICE, PER 2004 WPB AMEND. 108.3.
  
 3) AS NOTED IN LAST REVIEW 5-12-08. PLEASE SUBMIT
 MECHANICAL PLANS FOR REVIEW AS MECHANICAL PERMIT
 #08050266 HAS BEEN APPLIED FOR. SEE 2004 WPB AMEND.
 106.3.5.4 (10).
  
 4) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-101.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-05-12 Cont ID  
Sent By tgordon Date 2008-05-12 Time 15:33 Rev Time 0.40
Received By tgordon Date 2008-05-12 Time 15:33 Sent To Z
Notes
2008-05-12 15:50:14PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) PLEASE READ THE OWNER/BUILDER DISCLOSURE STATEMENT
 THAT YOU SIGNED. YOU MAY ONLY IMPROVE A ONE-FAMILY OR
 TWO-FAMILY RESIDENCE, YOUR RESIDENCE IT THREE FAMILY
 AND NEEDS A LICENSE CONTRACTOR TO APPLY FOR THE PERMIT,
 PER FS 489.
  
 2) THE VALUE ON THE PERMIT MUST BE ADJUSTED TO THE FAIR
 MARKET VALUE (REPLACEMENT VALUE) WITH ALL MATERIALS AND
 LABOR. IF THE VALUE IS NOT ADJUSTED THEN THE CITY WILL
 NEED TO ADJUST IT USING THE MARSHALL & SWIFT NATIONAL
 VALUATION SERVICE, PER 2004 WPB AMEND. 108.3.
  
 3) PLEASE SUBMIT MECHANICAL PLANS FOR REVIEW AS
 MECHANICAL PERMIT #08050266 HAS BEEN APPLIED FOR. SEE
 2004 WPB AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-08-01 Cont ID  
Sent By mperson Date 2008-08-01 Time 10:31 Rev Time 0.00
Received By mperson Date 2008-08-01 Time 10:31 Sent To B
Notes
2008-08-01 10:39:21PLUMBING PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW
 COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW
 COMMENTS.
 NOTE: NONE OF THE PREVIOUS PLUMBING REVIEW COMMENTS
 FROM 05/16/08 WERE ADDRESSED AND THERE WAS NO COMMENT
 RESPONSE FROM THE DESIGNER.
  
 1. VALUE ON THE PERMIT APPLICATION APPEARS LOW. THE
 VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL COST OF
 LABOR AND MATERIALS. VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF A NATIONAL CONSTRUCTION
 COST ANALYSIS (MARSHALL-SWIFT) . ADJUST THE VALUE AT
 THE PERMIT CLERK'S DESK AND PAY THE DIFFERENCE IN FEES
 PRIOR TO RESUBMITTING. PER (W.P.B. AS AMENDED) SECTION
 108.3 BUILDING PERMIT VALUATION.
  
 2. PLEASE READ THE OWNER/BUILDER DISCLOSURE STATEMENT
 THAT YOU SIGNED. YOU MAY ONLY IMPROVE A ONE-FAMILY OR
 TWO-FAMILY RESIDENCE. YOUR RESIDENCE HAS THREE-FAMILY
 AND NEEDS A LICENSED CONTRACTOR TO APPLY FOR THE
 PERMIT. PER F.S. 489.
  
 3. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
  
 4. SHEET A-2.1 FIRST FLOOR DEMO PLAN INDICATES THE TWO
 EXISTING WATER HEATERS BEING RELOCATED, HOWEVER SHEET
 A-2.2 PROPOSED FLOOR PLAN HAS NO INDICATION OF WHERE
 THE WATER HEATERS ARE BEING RELOCATED. PLEASE CLEARLY
 INDICATE WHERE THE WATER HEATERS ARE BEING RELOCATED
 AND WHAT THE TYPE IS OF THE WATER HEATER (GAS OR
 ELECTRIC). PER FBC-2004 PLUMBING SECTION 501.1 SCOPE.
  
 5. SHEETS A-2.1 OR A-2.2 HAVE NO INDICATION OF
 EXISTING OR PROPOSED AUTOMATIC CLOTHES WASHER
 CONNECTIONS. PER FBC-2004 PLUMBING TABLE 403.1 MINIMUM
 NUMBER OF REQUIRED PLUMBING FIXTURES (R-3), 1 AUTOMATIC
 CLOTHES WASHER CONNECTOR PER DWELLING UNIT IS REQUIRED.
 PLEASE CLEARLY INDICATE THIS ON THE RESUBMITTAL. IF THE
 AUTOMATIC CLOTHES WASHER IS PROPOSED PLEASE ADD TO THE
 REQUIRED SANITARY ISOMETRIC RISER DIAGRAM.
 NOTE: THE WASHING MACHINE MUST COMPLY WITH THE
 FOLLOWING.
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING.
  
 **THE FOLLOWING IS A NEW COMMENT**
  
 6. SEE ATTACHED NOTICE FS 553.80(2)(B) REGUARDING FOUR
 (4) TIMES THE FEE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-05-16 Cont ID  
Sent By mperson Date 2008-05-16 Time 08:27 Rev Time 0.00
Received By mperson Date 2008-05-16 Time 08:27 Sent To B
Notes
2008-05-16 09:59:58PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. VALUE ON THE PERMIT APPLICATION APPEARS LOW. THE
 VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL COST OF
 LABOR AND MATERIALS. VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF A NATIONAL CONSTRUCTION
 COST ANALYSIS (MARSHALL-SWIFT) . ADJUST THE VALUE AT
 THE PERMIT CLERK'S DESK AND PAY THE DIFFERENCE IN FEES
 PRIOR TO RESUBMITTING. PER (W.P.B. AS AMENDED) SECTION
 108.3 BUILDING PERMIT VALUATION.
  
 2. PLEASE READ THE OWNER/BUILDER DISCLOSURE STATEMENT
 THAT YOU SIGNED. YOU MAY ONLY IMPROVE A ONE-FAMILY OR
 TWO-FAMILY RESIDENCE. YOUR RESIDENCE HAS THREE-FAMILY
 AND NEEDS A LICENSED CONTRACTOR TO APPLY FOR THE
 PERMIT. PER F.S. 489.
  
 3. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
  
 4. SHEET A-2.1 FIRST FLOOR DEMO PLAN INDICATES THE TWO
 EXISTING WATER HEATERS BEING RELOCATED, HOWEVER SHEET
 A-2.2 PROPOSED FLOOR PLAN HAS NO INDICATION OF WHERE
 THE WATER HEATERS ARE BEING RELOCATED. PLEASE CLEARLY
 INDICATE WHERE THE WATER HEATERS ARE BEING RELOCATED
 AND WHAT THE TYPE IS OF THE WATER HEATER (GAS OR
 ELECTRIC). PER FBC-2004 PLUMBING SECTION 501.1 SCOPE.
  
 5. SHEETS A-2.1 OR A-2.2 HAVE NO INDICATION OF
 EXISTING OR PROPOSED AUTOMATIC CLOTHES WASHER
 CONNECTIONS. PER FBC-2004 PLUMBING TABLE 403.1 MINIMUM
 NUMBER OF REQUIRED PLUMBING FIXTURES (R-3), 1 AUTOMATIC
 CLOTHES WASHER CONNECTOR PER DWELLING UNIT IS REQUIRED.
 PLEASE CLEARLY INDICATE THIS ON THE RESUBMITTAL. IF THE
 AUTOMATIC CLOTHES WASHER IS PROPOSED PLEASE ADD TO THE
 REQUIRED SANITARY ISOMETRIC RISER DIAGRAM.
 NOTE: THE WASHING MACHINE MUST COMPLY WITH THE
 FOLLOWING.
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2008-07-29 Cont ID  
Sent By btrobaug Date 2008-07-29 Time 15:52 Rev Time 0.00
Received By mcruz Date 2008-07-29 Time 11:27 Sent To E
Notes
2008-07-29 11:56:46***ZONING - FAILED***
  
 ***REPEAT COMMENTS FROM 5/13/08***
  
 1.PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2.PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 3.AS THE ACCESSORY STRUCTURE ALREADY EXCEEDS THE
 MAXIMUM ALLOWABLE SQUARE FOOTAGE, NO ADDITIONS SHALL BE
 PERMITTED.PER SECTION 94-304 OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE TOTAL FLOOR AREA OF
 ALL ROOFED ACCESSORY BUILDINGS ON A PROPERTY SHALL NOT
 EXCEED 75 PERCENT OF THE GROSS FLOOR AREA OF 1,000
 SQUARE FEET.
  
 4.INDICATE THE SETBACK DIMENSIONS FROM ANY EXTERIOR
 IMPROVEMENTS TO ALL ADJACENT PROPERTY LINES.NOTE: PER
 SECTION 94-304 OF THE ZLDR:
  
 -- ACCESSORY STRUCTURE SETBACKS FOR SINGLE
 FAMILY/SMALL LOT (SF11) RESIDENTIAL DISTRICT IS AS
 FOLLOWS:
 --FRONT: 25 FEET
 --SIDE: FIVE FEET FROM LOT LINES.
 --CORNER: SAME AS REQUIRED FOR PRINCIPAL STRUCTURE.
 --REAR: FIVE FEET MINIMUM OR 15 FEET FROM THE
 CENTERLINE OF THE ALLEY TO A GARAGE FACING THE ALLEY,
 WHICHEVER IS GREATER.
  
 5.PROVIDE HEIGHT DIMENSIONS ON THE ELEVATIONS (SHEET
 A-3.0) FROM GRADE TO THE MIDPOINT OF THE ROOF'S PITCH.
  
 6.PROVIDE HEIGHT DIMENSIONS FROM A\C EQUIPMENT (IF
 ANY) TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDR, MECHANICAL EQUIPMENT NAY NOT
 PROJECT MORE THAN FOUR (4) INTO A REQUIRED SETBACK.
  
 7.PER SECTION 94-513(C)(3) OF THE ZLDRS, IF A MINOR
 USE NON-CONFORMITY (MINOR USE NON-CONFORMITY MEANS A
 RESIDENTIAL USE IN A RESIDENTIAL DISTRICT AT A HIGHER
 DENSITY THAN IS PERMITTED) IS ABANDONED FOR A PERIOD OF
 MORE THAN 180 CONSECUTIVE DAYS, SUCH USE SHALL
 THEREAFTER CONFORM TO THE STANDARDS OF THE ZONING
 DISTRICT IN WHICH IT LIES (IN THIS CASE SF11).
  
 AS THE STRUCTURE HAS NO EXISTING ROOF AND HAS NOT BEEN
 HABITABLE FOR SOME TIME, PROVIDE PROOF THAT THE
 BUILDING HAS BEEN OCCUPIED WITHIN THE PAST 180 DAYS,
 OTHERWISE THE STRUCTURE SHALL LOSE IT'S NON-CONFORMING
 USE STATUS AS TWO (2) UNIT APARTMENT.
  
 NOTE:AS THE ACCESSORY STRUCTURE IS NONCONFORMING WITH
 REGARD TO THE MINIMUM SETBACK REQUIREMENTS; PER SECTION
 94-513 OF THE ZLDR, NON-CONFORMING STRUCTURES OR
 BUILDINGS SHALL NOT IMPROVED, CONSTRUCTED, ENLARGED, OR
 ALTERED IN ANY MANNER TO CREATE A NEW NONCONFORMITY OR
 TO INCREASE AN EXISTING NONCONFORMITY.NO REPLACED
 WALL OR ROOF OVERHANG SHALL BE REBUILT ANY CLOSER TO
 THE PROPERTY LINE THAN WAS ORIGINALLY CONSTRUCTED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME AT:(561) 822-1444 OR (561) 805-6720 OR
 [email protected]
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT

Review Stop Z ZONING
Rev No 1 Status F Date 2008-05-13 Cont ID  
Sent By choops Date 2008-05-13 Time 08:56 Rev Time 0.00
Received By choops Date 2008-05-13 Time 08:56 Sent To E
Notes
2008-05-13 10:04:52***FAILED******ZONING = SF11***
  
  
 1)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 2)AS THE ACCESSORY STRUCTURE ALREADY EXCEEDS THE
 MAXIMUM ALLOWABLE SQUARE FOOTAGE OF 1,000 SQUARE FEET,
 NO ADDITIONS SHALL BE PERMITTED.PURSUANT TO SECTION
 94-304 OF THE ZLDRS:THE TOTAL FLOOR AREA OF ALL
 ROOFED ACCESSORY BUILDINGS ON A PROPERTY SHALL NOT
 EXCEED 75 PERCENT OF THE GROSS FLOOR AREA OF THE
 PRIMARY STRUCTURE WITH A MAXIMUM FLOOR AREA OF 1,000
 SQUARE FEET.
  
 3)INDICATE SETBACK DIMENSIONS FROM ANY PROPOSED
 EXTERIOR IMPROVEMENTS TO ALL ADJACENT PROPERTY LINES.
 NOTE:PURSUANT TO SECTION 94-304 OF THE CITY'S ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDRS):
  
 ACCESSORY STRUCTURE SETBACKS.
 FRONT: 25 FEET.
 SIDE: FIVE FEET FROM THE LOT LINES.
 CORNER: SAME AS REQUIRED FOR PRINCIPAL STRUCTURE.
 REAR: FIVE FEET MINIMUM OR 15 FEET FROM THE CENTERLINE
 OF THE ALLEY TO A GARAGE DOOR FACING THE ALLEY,
 WHICHEVER IS GREATER.
  
 4)PROVIDE A HEIGHT DIMENSION ON THE ELEVATIONS
 (SHEET A-3.0) FROM GRADE TO THE MIDPOINT OF THE ROOF'S
 PITCH.
  
 5)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT (IF ANY) TO ALL PROPERTY LINES.AS PER
 SECTION 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT
 MAY NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED
 SETBACK.
  
 6)PURSUANT TO SECTION 94-513(C)(3) OF THE ZLDRS:IF
 A MINOR USE NONCONFORMITY (MINOR USE NONCONFORMITY
 MEANS A RESIDENTIAL USE IN A RESIDENTIAL DISTRICT AT A
 HIGHER DENSITY THAN IS PERMITTED) IS ABANDONED FOR A
 PERIOD OF MORE THAN 180 CONSECUTIVE DAYS, SUCH USE
 SHALL THEREAFTER CONFORM TO THE STANDARDS OF THE ZONING
 DISTRICT IN WHICH IT LIES (SF11).
  
 AS THE STRUCTURE HAS NO EXISTING ROOF AND HAS NOT BEEN
 HABITABLE FOR SOME TIME, PROVIDE PROOF THAT THE
 BUILDING HAS BEEN OCCUPIED WITHIN THE PAST 180 DAYS,
 OTHERWISE THE STRUCTURE SHALL LOOSE IT'S NONCONFORMING
 USE AS A TWO (2) UNIT APARTMENT.
  
  
 NOTE:AS THE ACCESSORY STRUCTURE IS NONCONFORMING WITH
 REGARD TO MINIMUM SETBACK REQUIREMENTS; PURSUANT TO
 SECTION 94-513 OF THE ZLDRS: NONCONFORMING STRUCTURES
 OR BUILDINGS SHALL NOT BE IMPROVED, CONSTRUCTED,
 ENLARGED, OR ALTERED IN ANY MANNER TO CREATE A NEW
 NONCONFORMITY OR TO INCREASE AN EXISTING NONCONFORMITY,
 BUT MAY BE IMPROVED, CONSTRUCTED, ENLARGED, OR ALTERED
 AS LONG AS NO NEW NONCONFORMITY IS CREATED OR AN
 EXISTING NONCONFORMITY INCREASED.NO REPLACED WALL OR
 ROOF OVERHANG SHALL BE REBUILT ANY CLOSER TO THE
 PROPERTY LINE THAN WAS ORIGINALLY CONSTRUCTED.
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - SF RACK