Plan Review Details - Permit 08050185
Plan Review Stops For Permit 08050185
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-06-12 Cont ID  
Sent By jgomez Date 2008-06-12 Time 12:23 Rev Time 0.00
Received By jgomez Date 2008-06-12 Time 11:10 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-05-20 Cont ID  
Sent By jgomez Date 2008-05-20 Time 08:23 Rev Time 0.00
Received By jgomez Date 2008-05-20 Time 07:40 Sent To E
Notes
2008-05-20 09:59:49RESIDENTIAL (R3) NEW POOL CONSTRUCTION, BUILDING REVIEW
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1-CLEARLY SPECIFY HOW COMPLYING WITH THE RESIDENTIAL
 SWIMMING BARRIER REQUIREMENT SEC. R4101.17 OF 2004
 FLORIDA RESIDENTIAL CODE. NEED TO SPECIFY HOW IMPEDING
 ACCESS FROM THE HOME TO THE POOL AND HOW IMPEDING
 ACCESS FROM OUTSIDE TO THE POOL. NOTE PROVIDE ON PLANS
 STATES THAT ONLY ONE SAFETY FEATURE IS REQUIRED TO
 COMPLYWITH THIS SECTION.ONLY ONE FEATURE WILL NOT
 COMPLY WITH BOTH REQUIREMENTS OF PROVIDING ACCESS TO
 THE POOL FROM THE HOUSE OR FROM OUTSIDE. REVISE NOTE AS
 REQUIRED., INCLUDING CITING CORRECT CODE SECTION. USE
 2004 FLORIDA RESIDENTIAL CODE SECTION CITED ABOVE,
 WHICH IS THE ONE THAT CORRESPONDS TO THIS RESIDENTIAL
 POOL.
  
 ***NOTE: SEE ZONING COMMENTS REGARDING FENCE AROUND THE
 HOUSE.
  
 2- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW.
 VALUATION WAS UPDATEDTO $33,124(WHICH INCLUDES THE
 POOL, POOL SPA, POOL HEATER AND PAVERS)AS REQUIRED
 BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004.OWES
 $669.10WHICH IS THE TOTALFEE FOR THE PERMIT.
 CONTRACTOR DID NOT PAID THE PERMIT FEES AT TIME OF
 PERMIT APPLICATION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-05-20 Cont ID  
Sent By btrobaug Date 2008-05-20 Time 13:45 Rev Time 0.00
Received By btrobaug Date 2008-05-13 Time 11:17 Sent To I
Notes
2008-05-20 13:44:50 
  
 PROVISO
  
 THE DETAIL FOR THE EQUIPOTENTIAL BONDING MUST BE A WET
 SIGNATURE, SEALED AND DATED WITH THE CURRENT DATE THAT
 IT IS SEALED. PLEASE INCLUDE TWO COPIES OF SAME WHEN
 RESUBMITTING FOR OTHER COMMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2008-05-14 Cont ID  
Sent By mperson Date 2008-05-14 Time 14:42 Rev Time 0.00
Received By mperson Date 2008-05-14 Time 14:42 Sent To B
Notes
2008-05-14 14:44:55**CONTRACTOR INFORMATION ONLY**
 NOTE: GAS PERMIT REQUIRED. LICENSED GAS OR PLUMBING
 CONTRACTOR TO SUBMIT PLANS WITH PERMIT APPLICATION. ALL
 GAS INSPECTIONS TO BE COMPLETE BEFORE FINAL POOL
 INSPECTION.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-02-12 Cont ID  
Sent By adarroug Date 2009-02-12 Time 16:05 Rev Time 0.00
Received By adarroug Date 2009-02-12 Time 16:05 Sent To P
Notes
2009-02-12 16:05:30TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-01-13 Cont ID  
Sent By adarroug Date 2009-01-13 Time 10:08 Rev Time 0.00
Received By adarroug Date 2009-01-13 Time 10:08 Sent To P
Notes
2009-01-13 10:08:46TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-07-17 Cont ID  
Sent By adarroug Date 2008-07-17 Time 10:51 Rev Time 0.00
Received By adarroug Date 2008-07-17 Time 10:51 Sent To Z
Notes
2008-07-17 10:52:40TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-10 Cont ID  
Sent By adarroug Date 2008-06-10 Time 09:29 Rev Time 0.00
Received By adarroug Date 2008-06-10 Time 09:29 Sent To Z
Notes
2008-06-10 09:29:19TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-20 Cont ID  
Sent By btrobaug Date 2008-05-20 Time 11:25 Rev Time 0.00
Received By btrobaug Date 2008-05-07 Time 15:28 Sent To PC
Notes
2008-05-07 15:29:13TO "Z" BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-03-30 Cont ID  
Sent By lwagner Date 2009-03-30 Time 09:21 Rev Time 0.00
Received By lwagner Date 2009-03-30 Time 09:10 Sent To  
Notes
2009-03-30 09:21:59REVISION OK

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-02-03 Cont ID  
Sent By kstevens Date 2009-02-03 Time 11:46 Rev Time 0.00
Received By kstevens Date 2009-02-03 Time 11:46 Sent To  
Notes
2009-02-03 11:51:37DENIED
 REFERENCE:
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL REVISIONS TO A SIGNED, SEALED SET OF PLANS SHALL
 BE SIGNED, SEALED AND DATED BY THE ENGINEER OF RECORD.
 SECTION 106.1, FAC 61G15-23.002 & FS 471.025.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-05-14 Cont ID  
Sent By btrobaug Date 2008-05-20 Time 13:46 Rev Time 0.00
Received By mperson Date 2008-05-14 Time 14:40 Sent To G
Notes
2008-05-14 14:42:20****************PROVISO****************
 FBC-2004 SEC. 424.2.9, OR FBCR-2004 SEC.
 R4101.9 WATER SUPPLY, LOCAL ORD.
 #2853-95, BACKFLOW REQUIRED ON WATER
 SERVICE.(ADD TO NOTES)
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2008-07-23 Time   Rev Time 0.00
Received By   Date 2008-07-23 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2008-06-11 Cont ID  
Sent By choops Date 2008-06-11 Time 09:22 Rev Time 0.00
Received By choops Date 2008-06-11 Time 09:22 Sent To B
Notes
2008-06-11 09:23:45***FAILED - RESUB #1***
  
  
 REPEAT COMMENTS:
  
 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED POOL
 EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
 PLANS INDICATE DIMENSIONS TO EASEMENTS...WHAT
 EASEMENTS, DO YOU MEAN PROPERTY LINES?WHERE ARE THESE
 DIMENSIONS FROM...THE POOL EQUIPMENT?
  
 2)AS THE SURVEY DOES NOT SHOW AN EXISTING PERMANENT
 FENCE COMPLETELY SURROUNDING THE POOL, A FENCE PERMIT
 SHALL BE SUBMITTED CONCURRENTLY AND SHALL CONFORM TO
 THE MINIMUM STANDARDS PROVIDED BELOW.
  
 PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION, 94-304(D)(2)(B)+(C):
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
 "CHILD BARRIERS" DO NOT SATISFY THE ZONING REQUIREMENT
 FOR A PERMANENT FENCE ENCLOSURE.
  
  
 NEW COMMENTS:
  
 1)ALL PLANS/DIMENSIONS SHALL BE DONE WITH A PERMANENT
 UTENSIL (NOT PENCIL).
  
  
 NOTE:IF A PATIO OR PAVED AREA IS PROVIDED ADJACENT
 TO OR SURROUNDING A POOL, IT SHALL BE DESIGNED TO DRAIN
 AWAY FROM THE POOL, BUT NOT ONTO ADJACENT PROPERTIES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "B" - JG

Review Stop Z ZONING
Rev No 1 Status F Date 2008-05-09 Cont ID  
Sent By choops Date 2008-05-09 Time 13:16 Rev Time 0.00
Received By choops Date 2008-05-09 Time 13:16 Sent To E
Notes
2008-05-09 13:18:25***FAILED***
  
  
 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED POOL
 EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 2)AS THE SURVEY DOES NOT SHOW AN EXISTING PERMANENT
 FENCE COMPLETELY SURROUNDING THE POOL, A FENCE PERMIT
 SHALL BE SUBMITTED CONCURRENTLY AND SHALL CONFORM TO
 THE MINIMUM STANDARDS PROVIDED BELOW.
  
 PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION, 94-304(D)(2)(B)+(C):
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
  
 NOTE:IF A PATIO OR PAVED AREA IS PROVIDED ADJACENT
 TO OR SURROUNDING A POOL, IT SHALL BE DESIGNED TO DRAIN
 AWAY FROM THE POOL, BUT NOT ONTO ADJACENT PROPERTIES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720