Plan Review Details - Permit 08050091
Plan Review Stops For Permit 08050091
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-12-26 Cont ID  
Sent By lmartine Date 2008-12-26 Time 11:46 Rev Time 0.00
Received By lmartine Date 2008-12-26 Time 11:46 Sent To  
Notes
2008-12-26 11:47:18PRODUCT APPROVAL REVISIONS ARE OK LM

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-07-08 Cont ID  
Sent By amorse Date 2008-07-08 Time 15:55 Rev Time 0.00
Received By amorse Date 2008-07-08 Time 15:55 Sent To PC
Notes
2008-07-08 16:05:46 
  
 PASSED
  
 1)GLASS BLOCK INSTALLED COMPLYING WITH SECTION 2110
 FBC (FIRE-RATED) IS EXEMPT FROM IMPACT PROTECTION PER
 CITY MEMO FROM THE BUILDING OFFICIAL.
  
 2)PLEASE PROVIDE REVISIONS FOR FIXED WINDOW #4, THE
 SIZE EXCEEDS THE MAXIMUM ALLOWABLE SIZE OF 32 SQUARE
 FEET PER THE PRODUCT APPROVAL, THIS PROVISO WILL BE
 ADDED TO THE PERMIT SET.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-06-20 Cont ID  
Sent By amorse Date 2008-06-20 Time 17:43 Rev Time 0.00
Received By amorse Date 2008-06-20 Time 17:43 Sent To PC
Notes
2008-06-20 18:05:02 
  
  
 DENIED
  
 THE FOLLOWING COMMENT WERE NOT ADDRESSED IN 1ST REVIEW
  
 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $851.56 FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
  
 5)WINDOW TYPE #4 REQUIRES 2X4 MULLION AS STATED ON
 SCHEDULE BUT NO PRODUCT APPROVAL WAS SUBMITTED.
 *********THE CHANGE THAT IS REQUIRED WAS TO ADD A
 PRODUCT APPROVAL FOR 2X4 MULLIONS TO THE SUBMITTAL ,
 PLEASE SEE THAT THE 1X4 MULLION FOR 100" OPENING WIDTH
 AND A 108" OPENING HEIGHT WILL ONLY WORK FOR A DESIGN
 PRESSURE OF 22 PSF OR LESS PER PAGE 5 OF THE MULLION
 PRODUCT APPROVAL********
  
 NEW COMMENTS
  
 1)THE PRODUCT APPROVALS FOR THE SINGLE HUNG AND FIXED
 WINDOWS WERE NOT RESUBMITTED, PERMIT APPLICATION
 PACKAGE MUST BE COMPLETE FOR FINAL STAMPING AND PERMIT
 ISSUANCE
  
 2)GLASS BLOCK PRODUCT APPROVALS ONLY MEET THE SMALL
 MISSILE IMPACT REQUIREMENTS, OPENINGS WITHIN THE FIRST
 30 FEET FROM GRADE MUST MEET LARGE MISSILE IMPACT
 CRITERIA PER 1609.1.4 FBC, THE SILICONE SET BLOCK MEETS
 THIS REQUIREMENT OR SHUTTERS WILL BE REQUIRED AND THE
 PRODUCT APPROVALS SUBMITTED
  
 3)ONLY ONE COPY OF LANDSCAPE PLAN AND SOIL REPORT
 WERE SUBMITTED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-05-10 Cont ID  
Sent By amorse Date 2008-05-10 Time 12:09 Rev Time 0.00
Received By amorse Date 2008-05-10 Time 12:09 Sent To PC
Notes
2008-05-10 12:44:58 
  
 DENIED
  
 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $851.56 FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
  
 3)ZONING REQUIRES A LANDSCAPE PLAN, PLEASE ADD A
 DRAINAGE PLAN PER R401.3 FBC RES. THAT SHOWS DRAINAGE
 AWAY FROM BUILDING AND PROPERTY LINES
  
 4)WINDOW #6 IN WINDOW SCHEDULE HAS H36 AS 53 1/8"
 WIDE THIS WINDOW IS 26 1/2" WIDE AND ALSO DOES NOT MEET
 EGRESS REQUIREMENTS WITH ONLY 4.93 SQ. FT. CLEAR
 OPENING AREA. SGD WILL MEET THE EGRESS REQUIREMENTS FOR
 THIS ROOM.
  
 5)WINDOW TYPE #4 REQUIRES 2X4 MULLION AS STATED ON
 SCHEDULE BUT NO PRODUCT APPROVAL WAS SUBMITTED.
  
 6)CLARIFY TOP OF BEAM ELEVATION FOR FOYER AND FRONT
 PORCH, ROOF PLAN ON A-5.0 SHOWS 9'-4" BUT CEILING
 ELEVATION IS 14'-4" AS IS DETAIL 5 ON D-1
  
 7)PROVIDE MIN ROOF SHEATHING ATTACHMENT PER
 R803.2.3.1 FBC RES. MINIMUM 8D RING SHANK NAILS
  
 8)SUBMIT ENGINEERED TRUSS DRAWINGS THAT COMPLY WITH
 R802.10.1 FBC WITH PERMIT APPLICATION OR BEFORE
 INSTALLATION THAT HAVE BEEN REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD
  
 9)PROVIDE GLASS TYPE FOR SLIDING GLASS DOORS WITH
 PANELS 48" IN WIDTH (DOOR "T" AND "U"), PLEASE NOTE
 THAT TYPE "A" (MIN) GLASS WILL MEET DESIGN PRESSURES
 FOR ALL THE PANEL SIZES BELOW 48" BUT DO NOT MEET THE
 REQUIRED PRESSURE FOR THE LARGER PANELS
  
 10)PLEASE NOTE THAT A GAS PERMIT WILL BE REQUIRED,
 SEE ATTACHED INFORMATION NEEDED FOR GAS PERMIT
  
 11)APPROACH PERMIT WILL BE REQUIRED PLEASE NOTE THAT
 NO CONTRACTOR HAS SIGNED ON TO PERMIT AND NO PERMIT
 NUMBER HAS BEEN GENERATED, APPROCH PERMITS REQUIRE
 ENGINEERING REVIEW
  
 REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS OF
 NEW DRAWINGS WITH REVISIONS AND INCLUDE 1 COPY OF THE
 OLD PAGES ONLY FOR REFERENCE. PLEASE RE-SUBMIT ANY
 PAGES WITH THE IMPACT FEE STAMP. ALL OUT DATED OR NON
 REQUIRED PRODUCT APPROVALS CAN BE REMOVED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-06-13 Cont ID  
Sent By rkussner Date 2008-07-24 Time 17:43 Rev Time 0.00
Received By btrobaug Date 2008-06-13 Time 09:16 Sent To M
Notes
2008-07-09 12:42:04 
  
  
 PROVISO
  
 9B-3.0472 CARBON MONOXIDE PROTECTION.
  
 (1) EVERY BUILDING FOR WHICH A PERMIT FOR NEW
 CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A
 FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE,
 OR AN ATTACHED GARAGE SHALL HAVE AN OPERATIONAL CARBON
 MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM
 USED FOR SLEEPING PURPOSES.
  
 (2) IN NEW CONSTRUCTION, ALARMS SHALL RECEIVE THEIR
 PRIMARY POWER FROM THE BUILDING WIRING WHEN SUCH WIRING
 IS SERVED FROM THE LOCAL POWER UTILITY. SUCH ALARMS
 SHALL HAVE BATTERY BACK UP.
  
 (3) COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE
 LISTED OR LABELED BY A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
  
 SPECIFIC AUTHORITY 553.885(2) FS. LAW IMPLEMENTED
 553.72, 553.73(2), (3), (7), (9), 553.885(2) FS.
 HISTORY?NEW 11-18-07
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-05-07 Cont ID  
Sent By btrobaug Date 2008-05-07 Time 11:35 Rev Time 0.00
Received By btrobaug Date 2008-05-07 Time 07:42 Sent To P
Notes
2008-05-07 11:34:39 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER
 1AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
  
 1} THE AHU CIRCUITS IN PANEL "A"ARE RATED AT 5000 W
 WITH 60 AMP OCP IN VIOLATION OF 310.16. THESE 5000W
 LOADS DO NOT CORRELATE WITH THE MANUFACTURERS
 SPECIFICATIONS ON SHEET M-1, CORRELATE SAME.
  
 2} THE CIRCUIT (1,3) PANEL "B" FOR CONDENSER #1 @50
 AMPS EXCEEDS THE MANUFACTURERS MAX FUSE SIZE ON SHEET
 M-1
  
 3} SHOW COMPLIANCE WITH THE REQUIRED A/C DISCONNECTS
 PER 440.14. SEE 110.26.
  
 4} THERE IS A JACUZZI IN THE MASTER BATH THAT IS NOT IN
 THE PANEL SCHEDULE PER 408.4.
  
 5} INDICATE COMPLIANCE WITH 680.43(A)(1-4) FOR
 RECEPTACLES FOR THE JACUZZI.
  
 6} THE LOAD CALCULATION MUST REFLECT THE CHANGES FROM
 THE AHU AND JACUZZI. 220.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
2008-05-07 09:50:49 
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2009-04-09 Cont ID  
Sent By adarroug Date 2009-04-09 Time 08:47 Rev Time 0.00
Received By adarroug Date 2009-04-09 Time 08:47 Sent To Z
Notes
2009-04-09 08:47:58TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2009-03-27 Cont ID  
Sent By mcruz Date 2009-03-27 Time 08:57 Rev Time 0.00
Received By mcruz Date 2009-03-24 Time 08:57 Sent To  
Notes
2009-03-27 08:57:52PLACED IN Z BOX.

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-03-16 Cont ID  
Sent By shill Date 2009-03-16 Time 16:29 Rev Time 0.00
Received By shill Date 2009-03-16 Time 16:29 Sent To L
Notes
2009-03-16 16:29:44TO "Z" BOX/REV--FOR LANDSCAPE REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-02-27 Cont ID  
Sent By adarroug Date 2009-02-27 Time 10:18 Rev Time 0.00
Received By adarroug Date 2009-02-27 Time 10:18 Sent To Z
Notes
2009-02-27 10:18:46TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-12-24 Cont ID  
Sent By adarroug Date 2008-12-24 Time 10:26 Rev Time 0.00
Received By adarroug Date 2008-12-24 Time 10:26 Sent To B
Notes
2008-12-24 10:26:36TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-08-04 Cont ID  
Sent By adarroug Date 2008-08-04 Time 14:23 Rev Time 0.00
Received By adarroug Date 2008-08-04 Time 14:23 Sent To Z
Notes
2008-08-04 14:23:31TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-07-16 Cont ID  
Sent By adarroug Date 2008-07-16 Time 08:36 Rev Time 0.00
Received By adarroug Date 2008-07-16 Time 08:36 Sent To Z
Notes
2008-07-16 08:36:59TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-07-01 Cont ID  
Sent By adarroug Date 2008-07-01 Time 10:09 Rev Time 0.00
Received By adarroug Date 2008-07-01 Time 10:08 Sent To Z
Notes
2008-07-01 10:09:15TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-10 Cont ID  
Sent By adarroug Date 2008-06-10 Time 10:45 Rev Time 0.00
Received By adarroug Date 2008-06-10 Time 10:45 Sent To Z
Notes
2008-06-10 10:45:27TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-05-10 Time   Rev Time 0.00
Received By adarroug Date 2008-05-05 Time 16:43 Sent To  
Notes
2008-05-05 16:43:37TO "SFR" "Z"

Review Stop L LANDSCAPING
Rev No 6 Status P Date 2009-04-21 Cont ID  
Sent By rkussner Date 2009-04-21 Time 09:47 Rev Time 0.00
Received By rkussner Date 2009-04-21 Time 09:47 Sent To PC
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 5 Status F Date 2009-03-27 Cont ID  
Sent By rkussner Date 2009-03-27 Time 16:02 Rev Time 0.00
Received By rkussner Date 2009-03-27 Time 16:02 Sent To PC
Notes
2009-03-27 16:04:28***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO ALL COMMENTS IN WRITTEN FORMAT.
  
 THE COMMENTS MADE ON 3/17/09 HAVE NOT BEEN ADDRESSED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 4 Status F Date 2009-03-17 Cont ID  
Sent By rkussner Date 2009-03-17 Time 13:45 Rev Time 0.00
Received By rkussner Date 2009-03-17 Time 13:45 Sent To  
Notes
2009-03-17 13:49:51***LANDSCAPE REVIEW FAILED***
  
 1. PLEASE IDENTIFY THE TYPE OF TREE PROPOSED FOR THE
 RIGHT-OF-WAY AND THE SIZE. IT SHOULD BE SHOWN ON PLAN.
  
 2. A BARRIER SHALL BE PLACED BETWEEN THE GRAVEL AREA
 AND PLANTED AREAS.
  
 3. ALL HARDSCAPE SHALL BE ACCURATELY SHOWN ON THE
 LANDSCAPE PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 3 Status P Date 2009-03-02 Cont ID  
Sent By rkussner Date 2009-03-02 Time 11:31 Rev Time 0.00
Received By rkussner Date 2009-03-02 Time 09:27 Sent To Z
Notes
2009-03-02 12:17:56***LANDSCAPE REVIEW PASSED WITH PROVISO***
  
 1. AC UNITS SHALL BE SCREENED AND POOL EQUIPMENT.
  
 2. GRAVEL SHALL BE CONTAINED AND KEPT AWAY FROM TREES
 AND PLANT BEDS.
  
 3. PROVIDE REQUIRED STREET TREES TO BE CONSISTENT WITH
 BALANCE OF STREET.

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2008-08-06 Cont ID  
Sent By rkussner Date 2008-08-06 Time 18:16 Rev Time 0.00
Received By rkussner Date 2008-08-06 Time 18:16 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2008-07-24 Cont ID  
Sent By rkussner Date 2008-07-24 Time 17:44 Rev Time 0.00
Received By rkussner Date 2008-07-24 Time 17:44 Sent To  
Notes
2008-07-24 17:41:50TO TAKE CREDIT FOR UTILIZATION OF A MOISTURE SENSING
 CONTROLLER OTHER THAN RAINSWITCH, YOU MUST IDENTIFY THE
 EXACT EQUIPMENT TO BE USED.
  
 IF GRAVEL IS TO BE USED ON THE SIDE FO THE HOME, IT
 MUST BE LIMITED TO A 3 TO 4 FOOT WIDTH (THE TYPICAL
 WIDTH OF A PEDESTRIAN PATH) AND PROPERLY CONTAINED.
 GRAVEL MUST BE KEPT AWAY FROM ANY PROPOSED TREES,
 SHRUBS AND GROUND COVER.PLANT BEDS SHALL BE MULCHED.
  
 PROVIDE THE SIZE AND SPACING FOR ALL PROPOSED PLANT
 MATERIAL.
  
 THE HARDSCAPE ON THE SITE SHALL BE CONSISTENT WITH THE
 PLAN.
  
 NOTES SHALL BE INCLUDED ON THE PLAN WITH REFERENCE TO
 PLANT GRADE, DEPTH OF MULCH, IRRIGATION COVERAGE
 (INCLUDING RIGHT-OF-WAY).
  
 PROVIDE THE LOCATION OF ANY EXISTING OR PROPOSED STREET
 TREES.
  
 PROVIDE THE STREET ADDRESS ON THE PLAN.
  
  
 SHOULD YOU HAVE ANY QUESTIONS REGARDING THE LANDSCAPE
 COMMENTS, CONTACT ROBERT KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-06-13 Cont ID  
Sent By tgordon Date 2008-06-13 Time 13:49 Rev Time 0.30
Received By tgordon Date 2008-06-13 Time 13:49 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-05-06 Cont ID  
Sent By tgordon Date 2008-05-06 Time 11:07 Rev Time 1.00
Received By tgordon Date 2008-05-06 Time 11:07 Sent To Z
Notes
2008-05-06 11:44:51PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) COOLING LOAD CALCULATIONS (MANUAL J) WERE DONE ON A
 WORST CASE SCENARIO SHOWING THE GREAT ROOM EXPOSED
 WALLS FACING SOUTHWEST AND NORTHWEST, THE SURVEY SHOWS
 THE GREAT ROOM EXPOSED WALLS WILL BE FACING EAST AND
 SOUTH. COOLING LOAD CALCULATIONS MUST BE DONE TO THE
 SPECIFIC BUILDING TO BE ACCURATE. PER 2004 FBC
 13-607.1.ABC.1, PLEASE CORRECT.
  
 2) PLEASE SHOW THE JOB ADDRESS IN THE TITLE BLOCK OF
 THE MECHANICAL PLAN M-1, PER 2004 WPB AMEND. 106.1.3.
  
 3) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN, ON
 THEM, SEE W.P.B. AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-06-16 Cont ID  
Sent By jleech Date 2008-06-16 Time 08:07 Rev Time 0.00
Received By jleech Date 2008-06-16 Time 08:04 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-05-08 Cont ID  
Sent By jleech Date 2008-05-08 Time 10:10 Rev Time 0.00
Received By jleech Date 2008-05-08 Time 09:03 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2008-08-08 Cont ID  
Sent By mcruz Date 2008-08-08 Time 13:03 Rev Time 0.00
Received By mcruz Date 2008-08-08 Time 13:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2008-07-02 Cont ID  
Sent By choops Date 2008-07-02 Time 09:35 Rev Time 0.00
Received By choops Date 2008-07-02 Time 09:35 Sent To B
Notes
2008-07-02 09:52:07***FAILED - RESUB #2***
  
  
 REPEAT COMMENTS:
  
 1)TWO COPIES OF ALL PLANS SHALL BE SUBMITTED.ONE
 LANDSCAPE PLAN SUBMITTED IS CORRECT, ONE LANDSCAPE PLAN
 SUBMITTED IS INCORRECT.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS
 (ZLDRS).
  
 THE SUBMITTED PLAN DOES NOT PROVIDE SUFFICIENT
 SHADE/FLOWER/FRUIT TREES, AND MANY OF THE LANDSCAPE
 CALCULATIONS ARE INACCURATE.PLEASE SEE LANDSCAPE PLAN
 WITH NOTED CORRECTIONS/CALCULATIONS...TOTAL LOT AREA
 NOT CORRECT, REQUIRED SHADE TREES NOT CORRECT, VARIOUS
 OTHER CALCULATIONS NOT CORRECT...PLANS SHALL REFLECT
 CORRECT CALCULATIONS AND AN ADDITIONAL SHADE TREE SHALL
 BE PROVIDED.
  
 NOTE:FOR SINGLE-FAMILY DWELLING UNITS, AT LEAST ONE
 SHADE, FLOWERING OR FRUIT TREE SHALL BE PLANTED FOR
 EACH 1,200 SQUARE FEET OF OPEN SPACE OR PORTION
 THEREOF. FOR SINGLE-FAMILY DWELLING UNITS, AT LEAST ONE
 SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE FEET OF OPEN
 SPACE OR PORTION THEREOF.
  
 NOTE:PLANT MATERIALS USED PURSUANT TO THE PROVISIONS
 OF THIS SECTION SHALL BE EQUAL TO OR BETTER THAN
 FLORIDA DEPARTMENT OF AGRICULTURE NUMBER 1 NURSERY
 GRADE STANDARD.
  
 NOTE:THE REQUIRED IRRIGATION SYSTEM SHALL BE
 PROVIDED IN THE YARD AREA AND ANY SWALE/PARKWAY AREA,
 IF APPLICABLE.
  
  
 2)REMOVE OLD/INCORRECT SHEETS (SHEET A-4.0) FROM
 PACKET AND INSERT THE NEW SHEET A-4.0.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
 [email protected]
  
  
  
  
  
 SENT TO "B" - AM

Review Stop Z ZONING
Rev No 2 Status F Date 2008-06-11 Cont ID  
Sent By choops Date 2008-06-11 Time 10:31 Rev Time 0.00
Received By choops Date 2008-06-11 Time 10:31 Sent To E
Notes
2008-06-11 10:35:14***FAILED - RESUB #1***
  
  
 REPEAT COMMENT:
  
 1)PLEASE SUBMIT A LANDSCAPE PLAN SHOWING COMPLIANCE
 WITH SECTIONS 94-442 AND 94-445 OF THE CITY'S ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDRS).
  
 THE SUBMITTED PLAN DOES NOT PROVIDE SUFFICIENT
 SHADE/FLOWER/FRUIT TREES, AND MANY OF THE LANDSCAPE
 CALCULATIONS ARE INACCURATE.PLEASE SEE LANDSCAPE PLAN
 WITH NOTED CORRECTIONS/CALCULATIONS...TOTAL LOT AREA
 NOT CORRECT, REQUIRED SHADE TREES NOT CORRECT, VARIOUS
 OTHER CALCULATIONS NOT CORRECT...PLANS SHALL REFLECT
 CORRECT CALCULATIONS AND AN ADDITIONAL SHADE TREE SHALL
 BE PROVIDED.
  
 NOTE:FOR SINGLE-FAMILY DWELLING UNITS, AT LEAST ONE
 SHADE, FLOWERING OR FRUIT TREE SHALL BE PLANTED FOR
 EACH 1,200 SQUARE FEET OF OPEN SPACE OR PORTION
 THEREOF. FOR SINGLE-FAMILY DWELLING UNITS, AT LEAST ONE
 SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE FEET OF OPEN
 SPACE OR PORTION THEREOF.
  
 NOTE:PLANT MATERIALS USED PURSUANT TO THE PROVISIONS
 OF THIS SECTION SHALL BE EQUAL TO OR BETTER THAN
 FLORIDA DEPARTMENT OF AGRICULTURE NUMBER 1 NURSERY
 GRADE STANDARD.
  
 NOTE:THE REQUIRED IRRIGATION SYSTEM SHALL BE
 PROVIDED IN THE YARD AREA AND ANY SWALE/PARKWAY AREA,
 IF APPLICABLE.
  
  
 NEW COMMENT:
  
 1)THE "BUILDING HEIGHT FROM F.F" AND THE "MEAN ROOF
 HEIGHT FROM GRADE" MEASUREMENTS ARE NOT CORRECT AS
 SHOWN ON THE LEFT SIDE ELEVATION (SHEET A-4.0).PLEASE
 REVISE.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2008-07-24 Cont ID  
Sent By choops Date 2008-05-06 Time 13:40 Rev Time 0.00
Received By choops Date 2008-05-06 Time 13:40 Sent To E
Notes
2008-05-06 13:44:40***FAILED***
  
  
 1)LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL
 APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF THE
 CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS
 (ZLDRS).
  
 PLEASE SUBMIT A LANDSCAPE PLAN SHOWING COMPLIANCE WITH
 SECTIONS 94-442, 94-445, AND 94-448(2) OF THE ZLDRS.
  
 2)PURSUANT TO SECTION 94-482 OF THE ZLDRS: REQUIRED
 OFF-STREET PARKING SPACES FOR LESS THAN FOUR
 RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE
 PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED
 PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE
 LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT
 YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN
 THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH,
 NONDUSTING SURFACE IN COMPLIANCE WITH SUBSECTION
 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO
 PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS
 ARTICLE.
  
 PLEASE INDICATE SQUARE FOOTAGE OF ALL IMPERMEABLE
 SURFACES LOCATED WITHIN THE FRONT YARD (FROM FRONT
 PROPERTY LINE TO THE FRONT BUILDING FACADE).
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - SF RACK