Plan Review Details - Permit 08050054
Plan Review Stops For Permit 08050054
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-05-08 Cont ID  
Sent By jgomez Date 2008-05-08 Time 13:58 Rev Time 0.00
Received By jgomez Date 2008-05-08 Time 13:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-05-06 Cont ID  
Sent By jgomez Date 2008-05-06 Time 08:28 Rev Time 0.00
Received By jgomez Date 2008-05-06 Time 07:48 Sent To PC
Notes
2008-05-06 08:31:29RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- SHUTTERS SPAN SHOWN ON COLUMN #6 OF INSTALLATION
 SCHEDULE SUBMITTED IS THE SAME AS THE OPENING HEIGHT.
 THIS CAN'T BE SO IF THE EDGE DISTANCE ON COLUMN #8 IS
 3-1/2". REVISE AS REQUIRED.
  
 2- ANCHOR SPACING FOR OPENING #4 NEED TO BE REVISED
 SINCE PANEL SPAN IS OVER 8'-0" TO COMPLY WITH ITEM #1
 ABOVE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-06 Cont ID  
Sent By jgomez Date 2008-05-06 Time 11:26 Rev Time 0.00
Received By jgomez Date 2008-05-05 Time 09:28 Sent To  
Notes
2008-05-05 09:28:47TO "MISC" BOX#1