Plan Review Details - Permit 08050046
Plan Review Stops For Permit 08050046
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-06-04 Cont ID  
Sent By rmcdouga Date 2008-06-04 Time 08:06 Rev Time 0.00
Received By rmcdouga Date 2008-06-04 Time 08:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-05-13 Cont ID  
Sent By rmcdouga Date 2008-05-13 Time 09:54 Rev Time 0.00
Received By rmcdouga Date 2008-05-13 Time 09:54 Sent To  
Notes
2008-05-13 10:37:002004 FBC W/2007 REVISIONS
 SIGN
  
 DENIED BY BUILDING
  
 1) PLEASE CLARIFY THE LOCATION OF THE SIGN. IF IT IS
 LOCATED ON THE EXTERIOR OF THE BUILDING, SUBMIT SIGNED
 AND SEALED ENGINEERING FOR WINDLOADS OF 140 MPH (3
 SECOND GUST). SEE FBC 2606.5, 2606.6 AND CHAPTER 16.
  
 2) THE LOCATION OF THE SIGN CAN NOT INTERFERE WITH OR
 OBSTRUCT ANY OTHER ITEMS OR SYSTEMS SUCH AS STORM
 PANELS OR ADDRESS NUMBERING.
  
 3) THE NAME OF THE PERSON RESPONSIBLE FOR THE DESIGN IS
 REQUIRED ON THE DRAWINGS. FBC 106.1.3* CITY AMENDMENTS.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-06-03 Cont ID  
Sent By btrobaug Date 2008-06-03 Time 15:32 Rev Time 0.00
Received By btrobaug Date 2008-06-03 Time 15:22 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-05-12 Cont ID  
Sent By btrobaug Date 2008-05-12 Time 14:47 Rev Time 0.00
Received By btrobaug Date 2008-05-12 Time 14:31 Sent To B
Notes
2008-05-12 14:47:24 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-23 Cont ID  
Sent By adarroug Date 2008-05-23 Time 11:39 Rev Time 0.00
Received By adarroug Date 2008-05-23 Time 11:39 Sent To Z
Notes
2008-05-23 11:40:08TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-13 Cont ID  
Sent By rmcdouga Date 2008-05-13 Time 09:54 Rev Time 0.00
Received By rmcdouga Date 2008-05-02 Time 15:44 Sent To  
Notes
2008-05-02 15:45:30TO "Z" BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2008-06-03 Cont ID  
Sent By mflis Date 2008-06-03 Time 08:12 Rev Time 0.00
Received By mflis Date 2008-06-02 Time 15:18 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-05-09 Cont ID  
Sent By mflis Date 2008-05-09 Time 08:23 Rev Time 0.00
Received By mflis Date 2008-05-09 Time 08:23 Sent To E
Notes
2008-05-09 08:25:14ZONING REVIEW: FAILED
  
 * PLEASE PROVIDE PLAN OR SURVEY OR BUILDING, INDICATING
 LOCATION OF LEASE SPACE WITHIN BUILDING, TO SCALE
 * ON ELEVATION, PLEASE INDICATE CLEARANCE OF SIGN FROM
 SIDEWALK LEVEL TO BOTTOM OF SIGN
  
 MATT FLIS - 822-1445