Plan Review Details - Permit 08050015
Plan Review Stops For Permit 08050015
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-05-06 Cont ID  
Sent By shill Date 2008-05-06 Time 18:41 Rev Time 0.00
Received By shill Date 2008-05-06 Time 18:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-05-05 Cont ID  
Sent By shill Date 2008-05-05 Time 15:40 Rev Time 0.00
Received By shill Date 2008-05-05 Time 15:40 Sent To  
Notes
2008-05-05 15:47:03****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.DESIGN PRESSURES ARE TOO LOW, PLEASE SEE FBC
 R301.2.(2).PLEASE REVISE INSTALLATION SCHEDULE.
  
 2.A 2 1/2" EDGE DISTANCE REQUIRES USING A FACTOR OF
 .75 FOR ANCHOR SPACING, SEE SHEET 8 OF THE PRODUCT
 APPROVAL.9" SPACING IS SPECIFIED ON THE INSTALLATION
 SCHEDULE; THIS IS FOR 3" EDGE DISTANCE.PLEASE
 REVISE.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-05 Cont ID  
Sent By shill Date 2008-05-05 Time 15:47 Rev Time 0.00
Received By shill Date 2008-05-02 Time 10:21 Sent To  
Notes
2008-05-02 10:21:59TO "MISC" BOX#1