Plan Review Details - Permit 08040848
Plan Review Stops For Permit 08040848
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2008-06-11 Cont ID  
Sent By shill Date 2008-05-01 Time 17:28 Rev Time 0.00
Received By shill Date 2008-05-01 Time 17:28 Sent To  
Notes
2008-05-01 17:29:13****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 ____1.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN
 PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE
 DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A
 DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ARCHITECT
 OR ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED SEALED ORIGINALS FAC61G15, FAC61G1 16.
  
 ____2.PROVIDE A COPY OF THE CONDO ASSOCIATION
 APPROVAL.
  
 _XX_3.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT, FBC*106.TWO SETS REQUIRED.
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 ____4.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 ____5.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC
 R310.
  
 _XX_6.PROVIDE A FLOOR PLAN SHOWING WHERE THE
 SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH
 CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 3
 ABOVE.
  
 ____8.REVISE EXPOSURE CATEGORY OR EXPLAIN RATIONALE
 FOR EXPOSURE B.NOTE THAT THE DEFINITION FOR EXPOSURE
 C HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC
 R301.2.1.4.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-08-18 Cont ID  
Sent By shill Date 2008-08-18 Time 13:00 Rev Time 0.00
Received By shill Date 2008-08-18 Time 13:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-06-11 Cont ID  
Sent By shill Date 2008-06-11 Time 14:27 Rev Time 0.00
Received By shill Date 2008-06-11 Time 14:27 Sent To  
Notes
2008-06-11 14:30:15****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 4.THE LANGUAGE FOR THE ANCHORS YOU HAVE SPECIFIED ON
 THE INSTALLATION SCHEDULE DOES NOT MATCH THE
 DESCRIPTION FOR ANCHORS ON THE PRODUCT APPROVAL, SEE
 SHEET 7.PLEASE CLARIFY WHICH ANCHOR YOU ARE USING.
  
 THE INSTALLATION SCHEDULE STATES MAXISET, THE PRODUCT
 APPROVAL ANCHOR SCHEDULE SPECIFIES TO ITW.PLEASE
 CORRELATE.
  
 NEW COMMENT:
  
 2.SEE OPENING 3, CLARIFY SPAN.HOW CAN THIS HAVE A
 HEIGHT OF 122" BUT A SPAN OF 75"; SPAN IS TO BE BLADE
 LENGTH?PLEASE CHECK ALL AND REVISE ANCHOR SPACING AS
 NEEDED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-05-15 Cont ID  
Sent By shill Date 2008-05-15 Time 11:48 Rev Time 0.00
Received By shill Date 2008-05-15 Time 11:48 Sent To  
Notes
2008-05-15 11:58:05****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 1.RE: PREVIOUS COMMENT #3, INSTALLATION SCHEDULE, TWO
 SETS REQUIRED. PLEASE PROVIDE TWO SETS.CONTRACTORS
 ARE TO PROVIDE TWO COMPLETE COLLATED SETS OF DOCUMNTS
 FOR PERMIT ISSUANCE.ONLY ONE SET OF THE INSTALLATION
 SCHEDULE WAS PROVIDED; EACH SHEET STAPLED TO A FLOOR
 PLAN.
  
 2.DESIGN PRESSURES HAVE NOT BEEN DECLARED ON ONE OF
 THE SHEETS; ARE YOU USING THE SAME FOR THE ENTIRE JOB?
  
 3.SEE OPENING 9.A SPAN OF 116, DESIGN PRESSURE
 70.6, C2/C4 SHOULD HAVE ANCHOR SPACING OF 6IN/4IN (NOT
 10IN/6IN AS SPECIFIED) IF YOU ARE USING THE TAPCON
 CIRCLED ON THE PRODUCT APPROVAL.
  
 4.THE LANGUAGE FOR THE ANCHORS YOU HAVE SPECIFIED ON
 THE INSTALLATION SCHEDULE DOES NOT MATCH THE
 DESCRIPTION FOR ANCHORS ON THE PRODUCT APPROVAL, SEE
 SHEET 7.PLEASE CLARIFY WHICH ANCHOR YOU ARE USING.
  
 5.ITEMS ARE CIRCLED ON THE PRODUCT APPROVAL WHICH DO
 NOT CORRELATE WITH THE JOB.PLEASE PROVIDE INFORMATION
 SPECIFIC TO THIS JOB ONLY.
  
 PLEASE CONTACT ME IF YOU NEED ASSISTANCE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-05-15 Cont ID  
Sent By shill Date 2008-05-01 Time 11:58 Rev Time  
Received By shill Date   Time   Sent To  
Notes
2008-05-15 11:59:02****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 ____1.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN
 PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE
 DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A
 DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ARCHITECT
 OR ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED SEALED ORIGINALS FAC61G15, FAC61G1 16.
  
 ____2.PROVIDE A COPY OF THE CONDO ASSOCIATION
 APPROVAL.
  
 _XX_3.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT, FBC*106.TWO SETS REQUIRED.
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 ____4.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 ____5.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC
 R310.
  
 _XX_6.PROVIDE A FLOOR PLAN SHOWING WHERE THE
 SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH
 CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 3
 ABOVE.
  
 ____8.REVISE EXPOSURE CATEGORY OR EXPLAIN RATIONALE
 FOR EXPOSURE B.NOTE THAT THE DEFINITION FOR EXPOSURE
 C HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC
 R301.2.1.4.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-08-12 Cont ID  
Sent By adarroug Date 2008-08-12 Time 16:46 Rev Time 0.00
Received By adarroug Date 2008-08-12 Time 16:46 Sent To B
Notes
2008-08-12 16:47:09TO "SHILL 'DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-06 Cont ID  
Sent By adarroug Date 2008-06-06 Time 16:06 Rev Time 0.00
Received By adarroug Date 2008-06-06 Time 16:06 Sent To B
Notes
2008-06-06 16:06:22TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-14 Cont ID  
Sent By adarroug Date 2008-05-14 Time 11:30 Rev Time 0.00
Received By adarroug Date 2008-05-14 Time 11:30 Sent To B
Notes
2008-05-14 11:30:49TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-01 Cont ID  
Sent By shill Date 2008-05-01 Time 17:29 Rev Time 0.00
Received By shill Date 2008-05-01 Time 15:31 Sent To  
Notes
2008-05-01 15:31:55TO "MISC" BOX#1