Plan Review Stops For Permit 08040841 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2008-12-31 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-12-31 |
Time |
09:17 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-12-31 |
Time |
09:17 |
Sent To |
|
|
Notes |
2008-12-31 09:17:29 | FLOATING DOCK SHOPS | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2008-12-10 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-12-10 |
Time |
14:41 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-12-10 |
Time |
14:41 |
Sent To |
|
|
Notes |
2008-12-10 14:50:25 | REVISION | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2008-10-07 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-10-07 |
Time |
08:47 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-10-07 |
Time |
08:47 |
Sent To |
|
|
Notes |
2008-10-07 10:36:01 | ****CORRECTIONS**** | | ****REVISION (ADDITION OF GANGWAY, CALCULATIONS)**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1. EITHER EVERY SHEET IS TO BE SIGNED, SEALED, AND | | DATED OR AN INDEX SHEET USED, FAC61G15-23.002. THE | | COVER SHEET IS SIGNED AND SEALED BUT THE INDEX SHEET IS | | NOT, AND ALSO DOES NOT INCLUDE THE TITLE BLOCK | | INFORMATION REQUIRED. SOME OF THE DOCUMENTS IN THE BOOK | | ARE SIGNED AND SEALED BUT THE SIGNATURE IS A PHOTOCOPY | | (MUST BE ORIGINAL). | | | | 2. PROVIDE THE ADDITIONAL VALUE FOR THE GANGWAY. AS YOU | | ARE CHANGING (INCREASING) THE SCOPE OF WORK FROM PIERS | | TO PIERS AND THE GANGWAY FOR PIER #1, PLEASE INCLUDE | | ADDITIONAL VALUE. | | | | 3. SEE SHEET G2; LIVE LOAD DESIGN CRITERIA IS 60PSF | | DOCKS, 85PSF GANGWAYS, AND 100PSF FOR PIERS. | | CALCULATIONS FOR 40PSF, 50PSF LIVE LOAD WERE SUBMITTED; | | APPEARS TO BE FOR DOCKS. PLEASE REVISE TO COMPLY WITH | | THE LIVE LOADS ON THE PLAN, FBC TABLE 1607.1, FBC 10. | | | | | | | | | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2008-09-18 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-09-18 |
Time |
09:20 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-09-18 |
Time |
09:20 |
Sent To |
|
|
Notes |
2008-09-18 09:25:32 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1. PLEASE PROVIDE TWO ORIGINAL SETS OF PERMIT | | DOCUMENTS. ONLY ONE SET WAS SUBMITTED. | | | | 2. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR | | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS | | FS471. PLEASE INCLUDE ALL INFORMATION REQUIRED BY | | FAC61G15-23.002 (NAME AND LICENSE NUMBER OF THE PERSON | | SEALING THE DOCUMENT). | | | | 3. PLEASE HAVE THE ENGINEER OF RECORD FOR THE STRUCTURE | | (CH2MHILL) REVIEW ALL REVISIONS/SUBMITTALS. THIS CAN BE | | DONE WITH A SHOP DRAWING REVIEW STAMP OR LETTER. | | | | 4. PLEASE SUBMIT AS A REVISION (CHANGING THE SCOPE OF | | WORK, REVISION TO THE RECORD SET). | | | | 5. PROVIDE THE ADDITIONAL VALUE FOR THE GANGWAY. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2008-06-18 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-06-18 |
Time |
10:29 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-06-17 |
Time |
18:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2008-05-08 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-05-08 |
Time |
16:50 |
Rev Time |
|
Received By |
shill |
Date |
2008-05-07 |
Time |
14:57 |
Sent To |
|
|
Notes |
2008-05-08 17:12:47 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1.GOVERNING CODE SHOULD INCLUDE 2007 | | REVISIONS/SUPPLEMENTS; PLEASE REVISE, G2. | | | | 2.G2, 60PSF DECLARED FOR GANGWAYS.PLEASE SEE FBC | | TABLE 1607.1, ASCE7.FOR ALL USES INVOLVING EXITING IN | | THE FLORIDA BUILDING CODE AND ASCE7, 100PSF IS | | REQUIRED.THE ASCE DESIGN OF MARINE FACILITES FOR THE | | BERTHING, MOORING, AND REPAIR OF VESSELS STATES: "PIERS | | LIMITED TO PEDESTRIAN USE . . . SHOULD BE DESIGNED FOR | | A MINIMUM OF 100PSF."THE FACT THAT THE TEXT GOES ON | | TO SAY THAT GANGWAYS SHOULD BE DESIGNED TO 60 - 100PSF | | IS ACKNOWLEDGED.HOWEVER, PLEASE EXPLAIN THE LOGIC OF | | THE REQUIREMENT OF 100PSF FOR THE PIER, BUT ONLY 85 (AS | | DISCUSSED) FOR THE GANGWAYS WHEN THE GANGWAYS SERVE THE | | SAME OCCUPANT LOAD AS THE PIER.THE ENGINEER WHO | | WROTE THE BOOK, JOHN GAYTHWAITE PE, STATES (VIA EMAIL) | | THAT PIERS AND GANGWAYS WITH OPEN ACCESS SHOULD BE | | DESIGNED FOR 100PSF. | | | | PLEASE FEEL FREE TO CONTACT ME TO DISCUSS THIS MATTER | | IF THE ENGINEER FOR THE PROJECT, CH2M HILL, DOES NOT | | AGREE WITH THE 100PSF REQUIREMENT.ANY FURTHER | | DOCUMENTATION TO SUPPPORT THE DESIGNOF 85PSF PROPOSED | | WOULD BE CONSIDERED. | | | | 3.FOR ALL FUTURE PERMITS, ISSUED PERMITS, AND | | SUBMITTALS RELATED TO THIS PROJECT, PLEASE HAVE THE | | ENGINEER FOR THE PROJECT, CH2M HILL, REVIEW THE PLANS | | AND SUBMITTALS PRIOR TO SUBMISSION TO THE CITY (OR, IN | | THE CASE OF THE PIER PERMIT, PROVIDE AS A SUBMITTAL TO | | AVOID PERMITTING DELAYS). THIS CAN BE DONE WITH A SHOP | | DRAWING REVIEW STAMP OR A LETTER.THIS IS REQUIRED FOR | | ALL ITEMS CURRENTLY IN PROCESS, IS A PROVISO ITEM FOR | | THE PASSED BUILDING REVIEW FOR THE PIERS. | | | | 4.PLEASE CLARIFY LIVE LOAD DESIGN CRITERIA FOR THE | | FLOATING DOCKS FBC*106.3.5.1.1(8). | | | | 5.DECLARE AN ANTICIPATED OCCUPANT LOAD, | | FBC*106.3.5.1.1(7).THIS STRUCTURE SERVES AS A MEANS | | OF EGRESS, BUT NO INFORMATION REGARDING ANTICIPATED USE | | WAS PROVIDED.IN DETERMINING LIVE LOAD REQUIREMENTS, | | THIS INFORMATION WOULD BE USEFUL. | | | | 6.LOCATION OF GUARDS IS NOT CLEAR. PLEASE SHOW | | LOCATION AND DESIGN CRITERIA OF GUARDRAILS AND | | HANDRAILS, FBC1607, FBC1009, FBC1012, FBC11-4.8. | | | | 7.THE PERMIT FOR THE PIERS STATED THAT THE RAILS AND | | GANGWAY WERE "BY OTHERS" AND THEREFORE NOT INCLUDED | | WITHIN THE SCOPE OF THAT PERMIT.THIS PERMIT | | APPLICATION STATES THAT IT IS FOR FLOATING DOCKS.DOES | | THIS INCLUDE THE GANGWAYS AND GUARD/HAND RAILS?THE | | PERMIT CAN BE ISSUED WITH SHOPS/ENGINEERING SUBMITTED | | PRIOR TO INSTALLATION. | | | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2008-06-19 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-06-17 |
Time |
06:43 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-06-17 |
Time |
13:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2008-05-06 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-05-06 |
Time |
10:08 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-05-05 |
Time |
14:48 |
Sent To |
|
|
Notes |
2008-05-05 17:12:35 | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS,NFPA | | 303 2000,2005 NEC, NFPA-72 2002, NFPA-101 2003, 2004 | | FBC CHAPTER 1AS AMENDED AND FOUND NONCOMPLIANT WITH THE | | FOLLOWING: | | | | 1} THE STANDARD REFERENES ON SHEET G-2, APPLICABLE | | CODES SECTION, SHOULD BE CHANGED TO THE ABOVE EDITIONS | | AS THAY ARE CURRENTLY IN EFFECT. | | | | 2} NFPA 303 ARTICLE 3.3.1 | | A BENCH MARK INDICATING THE ELECTRICAL DATUM PLANE OF | | THE LAND AREA SHALL BE PERMANENTLY LOCATED ON SHORE IN | | THE MARINA OR BOATYARD.INDICATE THE LOCATION OF SAME. | | | | 3} 555.2(3) (3) THE ELECTRICAL DATUM PLANE FOR FLOATING | | PIERS AND LANDING STAGES THAT ARE (A) INSTALLED TO | | PERMIT RISE AND FALL RESPONSE TO WATER LEVEL, WITHOUT | | LATERAL MOVEMENT, AND (B) THAT ARE SO EQUIPPED THAT | | THEY CAN RISE TO THE DATUM PLANE ESTABLISHED FOR (1) OR | | (2), IS A HORIZONTAL PLANE 762 MM (30 IN.) ABOVE THE | | WATER LEVEL AT THE FLOATING PIER OR LANDING STAGE AND A | | MINIMUM OF 305 MM (12 IN.) ABOVE THE LEVEL OF THE | | DECK. | | 555.9 ELECTRICAL CONNECTIONS | | ALL ELECTRICAL CONNECTIONS SHALL BE LOCATED AT LEAST | | 305 MM (12 IN.) ABOVE THE DECK OF A FLOATING PIER. ALL | | ELECTRICAL CONNECTIONS SHALL BE LOCATED AT LEAST 305 MM | | (12 IN.) ABOVE THE DECK OF A FIXED PIER BUT NOT BELOW | | THE ELECTRICAL DATUM PLANE.INDICATE COMPLIANCE WITH | | THESE ARTICLES FOR THE JUNCTION BOX AND LUMINAIRE | | CONNECTIONS.SHEET EP1.02 HAS NO DIMENSIONS FROM THE | | WATERLINE. | | | | 4} INDICATE THE CABLE DESIGNATION FOR THE "FLEX CABLE" | | SHOWN ON SHEET EP1.02. SEE ARTICLE 555.13(A)(2)FOR TYPE | | ALLOWED. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2009-04-14 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-04-14 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-04-14 |
Time |
15:26 |
Sent To |
|
|
Notes |
2009-04-14 15:26:17 | *****SUBMITTAL***** | | | | | | DEE LAMB OF WHITING -TURNER CONTRACTING COMPANY WAS | | ALLOWED TO INSTALL ADDRESS LABELS TO THE CITY'S FILED | | SET OF PLANS. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2008-06-19 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2008-06-19 |
Time |
14:28 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2008-06-19 |
Time |
14:25 |
Sent To |
|
|
Notes |
2008-06-19 14:28:46 | 1. SEPARATE PLANS AND PERMITS REQUIRED FOR STANDPIPE | | SYSTEM PLANNED FOR THE LOCATION. | | | | 2. NFPA 303 IS THE STANDARD TO BE UTILIZED FOR CODE | | COMPLAINCE. | | | | 3. ALL WORK IS SUBKECT TO FEILD INSPECTION AND | | APPROVAL. | | | | 4. STANDPIPE EQUIPMENT SHALL BE PROPERLY SUPPORTED AND | | RESTRAINED. | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | 804-4709 PHONE | | 804-4774 FAX |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2008-05-20 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2008-05-20 |
Time |
13:11 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2008-05-20 |
Time |
13:03 |
Sent To |
|
|
Notes |
2008-05-20 13:11:20 | 1. PREVIOUS PLAN REVIEW COMMENTS PROVIDED FOR PERMIT | | 08040176 "FIXED PIER" PORTION OF THE PLANS ARE NOT | | CLEARLY ADDRESSED WITH THIS SUBMITTAL PACKAGE UNDER A | | SEPARATE PERMIT 08040841. | | | | 2. THE PLANS MUST DEMONSTRATE COMPLIANCE WITH NFPA 303 | | AND ENOUGH DETAILS SHALL BE PROVIDED FOR THIS TO | | OCCUR. | | | | 3. THE PREVIOUS LETTER WRITTEN BY TALOR ENGINEERING | | DOES NOT CLARIFY THE MOST RECENT COMMENTS PROVIDED BY | | THIS DEPARTMENT FOR DRAWINGS UNDER PERMIT 08040176 AND | | MUST BE DOCUMENTED ON FUTURE PLANS WHEN SUBMITTED. | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | 804-4724 PHONE | | 804-4774 FAX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2009-04-10 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2009-04-10 |
Time |
13:10 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2009-04-10 |
Time |
13:10 |
Sent To |
FIRE |
|
Notes |
2009-04-10 13:11:25 | TO "F" BOX/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2008-12-23 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-12-23 |
Time |
16:19 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-12-23 |
Time |
16:19 |
Sent To |
B |
|
Notes |
2008-12-23 16:19:54 | TO "SHILL" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2008-11-07 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-11-07 |
Time |
09:07 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-11-07 |
Time |
09:07 |
Sent To |
B |
|
Notes |
2008-11-07 09:07:53 | TO "SHILL" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2008-09-23 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-09-23 |
Time |
10:44 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-09-23 |
Time |
10:43 |
Sent To |
B |
|
Notes |
2008-09-23 10:44:19 | TO "SHILL" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2008-06-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-06-16 |
Time |
09:45 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-06-16 |
Time |
09:45 |
Sent To |
|
|
Notes |
2008-06-16 09:46:16 | TO "COMM" BD#60 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-05-20 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-05-20 |
Time |
18:03 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-05-01 |
Time |
14:30 |
Sent To |
|
|
Notes |
2008-05-01 14:31:12 | TO "COMM" BD#56--EXPEDITED-- |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2008-06-18 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-06-18 |
Time |
12:35 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-06-18 |
Time |
12:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2008-05-19 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-05-19 |
Time |
11:37 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-05-19 |
Time |
11:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2008-05-15 |
|
|
Cont ID |
|
Sent By |
astelly |
Date |
2008-05-15 |
Time |
15:33 |
Rev Time |
0.00 |
Received By |
astelly |
Date |
2008-05-15 |
Time |
15:33 |
Sent To |
|
|
Notes |
|
|