Plan Review Stops For Permit 08040811 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2008-08-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2008-08-08 |
Time |
13:23 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2008-08-08 |
Time |
13:23 |
Sent To |
|
|
Notes |
2008-08-08 13:26:20 | NEW PRODUCT APPROVALS WERE SUBMITTED FOR ONE HOUR FIRE | | RATED GLASS BLOCK ASSEMBLY. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2008-06-24 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2008-06-24 |
Time |
09:38 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2008-06-24 |
Time |
09:38 |
Sent To |
|
|
Notes |
2008-06-23 16:57:32 | BUILDING PROVISO | | | | SUBMIT TWO COPIES OF THE LISTING INFORMATION FOR THE | | ONE HOUR FIRE RATED GLASS BLOCK SYSTEM THAT IS REQUIRED | | ON THE ZERO LOT LINE, BEFORE INSTALLATION. THE PRODUCT | | APPROVAL SUBMITTED IS FOR A SILICONE SYSTEM. FBC | | 106.1.2* CITY AMENDMENTS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2008-05-06 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2008-05-06 |
Time |
17:58 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2008-05-06 |
Time |
07:11 |
Sent To |
|
|
Notes |
2008-05-06 17:37:51 | 2004 FBC W/2007 REVISIONS | | NEW SINGLE FAMILY DWELLING | | | | DENIED BY BUILDING | | | | 1)FBC R401.4AREA OF QUESTIONABLE | | SOIL.SUBMIT A GEOTECHNICAL REPORT | | TO VERIFY THE SAFE BEARING CAPACITY OF | | THE SOIL. | | | | 2) THE NAIL SIZE FOR ROOF SHEATHING SPECIFIED IN THE | | SCHEDULE ON SHEET D-1 IS FOR AN 8D COMMON NAIL. THE | | PLANS SPECIFY 10D NAILS ON A-5.0. FBC R803.2.3.1 OF | | 2006 REVISIONS TO 2004 FBC RESIDENTIAL CODE REQUIRES 8D | | RING-SHANK NAILS. | | | | 3) THE TYPICAL WALL SECTION ON D-1 SHOWS AN 18" X 16" | | FOOTING AND THE SCHEDULE ON A-1.0 SPECIFIES A 16" X 16" | | FOOTING. PLEASE CLARIFY. FBC 106.1.1* CITY AMENDMENTS | | | | 4)THE NAILING SCHEDULE FOR PNEUMATIC FASTENERS ON | | SPECIFIES A SPACING OF 16" OC FOR DOOR AND GARAGE DOOR | | BUCKS. DETAIL 8 ON D-1 AND 2 ON D-2 SPECIFY 12" OC. | | PLEASE CORRECT. FBC 106.1.1* CITY AMENDMENTS | | | | 5) NOTE: SOME OF THE FASTENERS LISTED IN THE SCHEDULE | | ARE NOT PNEUMATIC FASTENERS. | | | | 6) SUBMIT THE LISTING INFORMATION FOR THE ONE HOUR FIRE | | RATED GLASS BLOCK SYSTEM THAT IS REQUIRED ON THE ZERO | | LOT LINE. THE PRODUCT APPROVAL SUBMITTED IS FOR A | | SILICONE SYSTEM. FBC 106.1.2* CITY AMENDMENTS | | | | 7) THE LARGE GLASS BLOCK OPENING ON THE PLANS EXCEEDS | | THE MAXIMUM OPENING SIZE OF 6' X 6' ALLOWED BY THE | | PRODUCT APPROVAL. DCA RULE 9B-72 | | | | 8) THE DOOR SCHEDULE ON A-2.0 SPECIFIES AN OXXO DOOR | | FOR THE 9' X 8' SLIDING GLASS DOOR. THE FLOOR PLAN AND | | ELEVATIONS SHOW A THREE PANEL DOOR. PLEASE CLARIFY. | | | | 9) WINDOWS #7 AND #5 IN THE SCHEDULE ON A-2.0 WILL BE | | REQUIRED TO USE GLASS TYPES B OR D FROM THE PRODUCT | | APPROVALS IN ORDER TO MEET THE REQUIRED OPENING | | PRESSURES. FBC TABLES R301.2(2) AND R301.2(3). | | | | 10) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED | | TO SECURE THE ROOF TILES. THE HACIENDA TILE SELECTED IN | | THE PRODUCT APPROVAL HAS A REQUIRED AERODYNAMIC UPLIFT | | MOMENT OF 37 PER TABLE 6 OF THE EVALUATION REPORT. IF | | ADHESIVE IS USED, SUBMIT PRODUCT APPROVALS. FBC R 905.3 | | AND FBC 106.1.1* CITY AMENDMENTS | | | | 11) A SEPARATE PERMIT WILL BE REQUIRED FOR THE | | DRIVEWAY/APPROACH. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2008-10-15 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-10-15 |
Time |
14:17 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-10-15 |
Time |
14:16 |
Sent To |
PC |
|
Notes |
2008-10-15 14:17:06 | | | | | REMOVED POOL PANEL./WRT. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2008-06-12 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-06-12 |
Time |
11:40 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-06-12 |
Time |
10:05 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2008-05-02 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-05-02 |
Time |
15:04 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-05-02 |
Time |
12:15 |
Sent To |
M |
|
Notes |
2008-05-02 15:04:02 | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER | | 1AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE AHU CIRCUITS IN PANEL "A"ARE RATED AT 5000 W | | WITH 60 AMP OCP IN VIOLATION OF 310.16. THESE 5000W | | LOADS DO NOT CORRELATE WITH THE MANUFACTURERS | | SPECIFICATIONS ON SHEET M-1, CORRELATE SAME. | | | | 2} THE CIRCUIT (1,3) PANEL "B" FOR CONDENSER #1 @50 | | AMPS EXCEEDS THE MANUFACTURERS MAX FUSE SIZE ON SHEET | | M-1 | | | | 3} THERE IS A JACUZZI IN THE MASTER BATH THAT IS NOT IN | | THE PANEL SCHEDULE PER 408.4. | | | | 4} INDICATE COMPLIANCE WITH 680.43(A)(1-4) FOR | | RECEPTACLES FOR THE JACUZZI. | | | | 5} THE LOAD CALCULATION MUST REFLECT THE CHANGES FROM | | THE AHU AND JACUZZI. 220. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2009-02-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2009-02-27 |
Time |
10:25 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2009-02-27 |
Time |
10:25 |
Sent To |
Z |
|
Notes |
2009-02-27 10:25:55 | TO "Z" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2008-10-10 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-10-10 |
Time |
09:07 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-10-10 |
Time |
09:07 |
Sent To |
E |
|
Notes |
2008-10-10 09:08:10 | TO "BTROBAUG" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2008-08-07 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-08-07 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-08-07 |
Time |
15:26 |
Sent To |
B |
|
Notes |
2008-08-07 15:26:58 | TO "RMCDOUGAL" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2008-07-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-07-01 |
Time |
09:54 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-07-01 |
Time |
09:54 |
Sent To |
Z |
|
Notes |
2008-07-01 09:54:46 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2008-06-10 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-06-10 |
Time |
10:34 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-06-10 |
Time |
10:34 |
Sent To |
Z |
|
Notes |
2008-06-10 10:34:59 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-05-06 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2008-05-06 |
Time |
18:04 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2008-05-01 |
Time |
08:16 |
Sent To |
|
|
Notes |
2008-05-01 08:16:16 | TO "SFR" "Z" |
|
|
Review Stop |
L |
LANDSCAPING |
Rev No |
1 |
Status |
P |
Date |
2009-03-02 |
|
|
Cont ID |
|
Sent By |
rkussner |
Date |
2009-03-02 |
Time |
12:19 |
Rev Time |
0.00 |
Received By |
rkussner |
Date |
2009-03-02 |
Time |
09:29 |
Sent To |
Z |
|
Notes |
2009-03-02 12:21:41 | ***LANDSCAPE REVIEW PASSED WITH THE FOLLOWING PROVISO. | | | | 1. PROVIDE REQUIRED STREET TREES TO BE CONSISTENT WITH | | THE BALANCE OF STREET. | | | | 2. GRAVEL SHALL BE CONTAINED AND KEPT AWAY FROM TREES | | AND SHRUB BEDS. | | | | 3. HARDSCAPE ELEMENTS (DECKS, POOLS, DRIVES, ETC.) | | SHALL BE ACCURATELY SHOWN ON PLAN. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2008-05-02 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-05-02 |
Time |
15:56 |
Rev Time |
0.45 |
Received By |
tgordon |
Date |
2008-05-02 |
Time |
15:56 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2008-06-19 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-06-19 |
Time |
09:09 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2008-06-19 |
Time |
09:09 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2008-05-02 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-05-02 |
Time |
09:48 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2008-05-02 |
Time |
09:48 |
Sent To |
E |
|
Notes |
2008-05-02 11:19:35 | PLUMBING PLAN REVIEW: | | DENIED: | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | 1. SHEET A-1.0 SANITARY RISER DIAGRAM: PER FBC-2004 | | PLUMBING SECTION 406.3 WASTE CONNECTIONS. THE AUTOMATIC | | CLOTHES WASHER FIXTURE DRAIN SHALL CONNECT TO A BRANCH | | DRAIN OR DRAINAGE STACK A MINIMUM OF 3 INCHES (76MM) IN | | DIAMETER. | | | | 2. SHEET A-1.0 SANITARY RISER DIAGRAM: BATHROOM #2 | | DOES NOT REFLECT THE FLOOR PLAN ON SHEET A-2.0. THE | | FLOOR PLAN ON SHEET A-2.0 INDICATES ONE SHOWER FOR THIS | | BATHROOM HOWEVER THE ISOMETRIC ON SHEET A-1.0 IS | | INDICATING TWO SHOWERS. ALSO THE LAVATORY TRAP ON SHEET | | A-1.0 ISOMETRIC IS BEING INDICATED IN THE WRONG ROOM. | | PLEASE CORRECT THE ISOMETRIC ON SHEET A-1.0 FOR | | BATHROOM #2 TO REFLECT THE FLOOR PLAN ON SHEET A-2.0. | | PER FBC-2004 PLUMBING SECTION 701.1 SCOPE. | | | | 3. SHEET A-2.0 FLOOR PLAN GARAGE: PLEASE PROVIDE A | | DETAIL ON HOW THE GAS WATER HEATER WILL BE PROTECTED | | FROM PHISICAL DAMAGE FROM VEHICLE IMPACT. PER FBC-2004 | | FUEL GAS SECTION 303.4 PROTECTION FROM PHYSICAL | | DAMAGE. | | | | 4. SHEET D-2PLUMBING NOTES: STATES THE FOLLOWING | | "MINIMUM SLOPE SHALL BE 1/8" PER FOOT". PLEASE CLEARLY | | INDICATE THE MINIMUM SLOPE OF HORIZONTAL DRAINAGE | | PIPING SHALL BE PER FBC-2004 W/07 REVISIONS PLUMBING | | TABLE 704.1. 2-1/2" OR LESS SHALL BE 1/4" PER FOOT | | SLOPE, 3" TO 6" SHALL BE 1/8" PER FOOT SLOPE AND 8" OR | | LARGER SHALL BE 1/16" PER FOOT SLOPE. | | | | ********IMPORTANT INFORMATION******** | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION | | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | NOTE: THERE IS ONLY ONE CORRECTED DRAWING | | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS | | EXAMINER FOR REFERENCE FOR THE | | RESUBMITTAL. | | | | END OF COMMENTS: | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | PHONE= (561) 805-6730 | | FAX= (561) 805-6731 | | E-MAIL= [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2008-07-02 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2008-07-02 |
Time |
10:49 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2008-07-02 |
Time |
10:49 |
Sent To |
PC |
|
Notes |
2008-07-02 10:50:05 | ***APPROVED - RESUB #2*** | | | | NOTE:PLANT MATERIALS USED SHALL BE EQUAL TO OR | | BETTER THAN FLORIDA DEPARTMENT OF AGRICULTURE NUMBER 1 | | NURSERY GRADE STANDARD. | | | | NOTE:THE REQUIRED IRRIGATION SYSTEM SHALL BE | | PROVIDED IN THE YARD AREA AND ANY SWALE/PARKWAY AREA, | | IF APPLICABLE. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2008-06-11 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2008-06-11 |
Time |
09:50 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2008-06-11 |
Time |
09:50 |
Sent To |
E |
|
Notes |
2008-06-11 09:59:23 | ***FAILED - RESUB #1*** | | | | | | REPEAT COMMENT: | | | | 1)PLEASE SUBMIT A LANDSCAPE PLAN SHOWING COMPLIANCE | | WITH SECTIONS 94-442 AND 94-445 OF THE CITY'S ZONING | | AND LAND DEVELOPMENT REGULATIONS (ZLDRS). | | | | THE SUBMITTED PLAN DOES NOT PROVIDE SUFFICIENT | | SHADE/FLOWER/FRUIT TREES, AND MANY OF THE LANDSCAPE | | CALCULATIONS ARE INACCURATE.PLEASE SEE LANDSCAPE PLAN | | WITH NOTED CORRECTIONS/CALCULATIONS...TOTAL LOT AREA | | NOT CORRECT, REQUIRED SHADE TREES NOT CORRECT, VARIOUS | | OTHER CALCULATIONS NOT CORRECT...PLANS SHALL REFLECT | | CORRECT CALCULATIONS AND AN ADDITIONAL SHADE TREE SHALL | | BE PROVIDED. | | | | NOTE:FOR SINGLE-FAMILY DWELLING UNITS, AT LEAST ONE | | SHADE, FLOWERING OR FRUIT TREE SHALL BE PLANTED FOR | | EACH 1,200 SQUARE FEET OF OPEN SPACE OR PORTION | | THEREOF. FOR SINGLE-FAMILY DWELLING UNITS, AT LEAST ONE | | SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE FEET OF OPEN | | SPACE OR PORTION THEREOF. | | | | NOTE:PLANT MATERIALS USED PURSUANT TO THE PROVISIONS | | OF THIS SECTION SHALL BE EQUAL TO OR BETTER THAN | | FLORIDA DEPARTMENT OF AGRICULTURE NUMBER 1 NURSERY | | GRADE STANDARD. | | | | NOTE:THE REQUIRED IRRIGATION SYSTEM SHALL BE | | PROVIDED IN THE YARD AREA AND ANY SWALE/PARKWAY AREA, | | IF APPLICABLE. | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | ZONING TECHNICIAN (561)805-6720 | | | | | | | | | | SENT TO "E" - BT |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2008-05-01 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2008-05-01 |
Time |
13:46 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2008-05-01 |
Time |
13:46 |
Sent To |
E |
|
Notes |
2008-05-01 13:53:27 | ***FAILED*** | | | | | | 1)PLEASE SUBMIT A LANDSCAPE PLAN SHOWING COMPLIANCE | | WITH SECTIONS 94-442 AND 94-445 OF THE CITY'S ZONING | | AND LAND DEVELOPMENT REGULATIONS (ZLDRS). | | | | 2)PURSUANT TO SECTION 94-482 OF THE ZLDRS: REQUIRED | | OFF-STREET PARKING SPACES FOR LESS THAN FOUR | | RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE | | PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED | | PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE | | LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT | | YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN | | THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH, | | NONDUSTING SURFACE IN COMPLIANCE WITH SUBSECTION | | 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO | | PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS | | ARTICLE. | | | | PLEASE INDICATE DIMENSIONS AND SQUARE FOOTAGE OF ALL | | IMPERMEABLE SURFACES LOCATED WITHIN THE FRONT YARD | | (FROM FRONT PROPERTY LINE TO THE FRONT BUILDING | | FACADE). | | | | 3)THE "MEAN ROOF HEIGHT FROM GRADE" AS SHOWN ON THE | | LEFT SIDE ELEVATION (SHEET A-4.0) DOES NOT MATCH THE | | OTHER ROOF HEIGHT DIMENSIONS GIVEN.PLEASE CLARIFY. | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | ZONING TECHNICIAN (561)805-6720 | | | | | | | | | | SENT TO "E" - SF RACK |
|
|