Plan Review Stops For Permit 08040794 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2008-06-18 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-06-18 |
Time |
16:12 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-06-16 |
Time |
11:29 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2008-05-09 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-05-09 |
Time |
18:03 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-05-09 |
Time |
15:36 |
Sent To |
PC |
|
Notes |
2008-05-09 18:02:54 | BUILDING PLAN REVIEW | | PERMIT: 08040794 | | ADD: 301 N.OLIVE AVE | | CONT: THE WEITZ COMPANY | | TEL: (561)687-4809 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | 5-9-08 | | REVIEW: 1ST | | ACTION: DENIED | | | | 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | 2)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) | | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | BUILDING WITH THE 2007 SUPPLEMENTS. | | | | 3)A DESIGN PROFESSIONAL THAT IS REGISTERED TO | | PRACTICE UNDER CHAPTER 481 OR 471 OF THE FLORIDA | | STATUTES SHALL AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND | | DATE TO SAID DRAWINGS AND SPECIFICATIONS PER 106.1 FBC | | 2004 | | | | ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME, ADDRESS, | | AND LICENCE NUMBER ON EACH SHEET THAT BEARS THEIR SEAL | | PER | | 61G15-23.002(2) | | | | 4)PROVIDE ENGINEERED AND ARCHITECTURAL DRAWINGS | | SPECIFIC TO THE PROJECT AND SHOW IN DETAIL HOW THEY | | WILL MEET THE REQUIREMENTS OF THE 2004 FBC. SHOW THE | | INTERIOR ELEVATION DETAILS OF THE ELEVATORS: THE | | INTERIOR ELEVATION DRAWINGS SHALL MEET THE REQUIREMENTS | | OF THE SECTION 3007. THE PLANS SUBMITTED ARE MISSING | | THE ORIGINAL SEAL AND SIGNATURE OF THE ARCHITECT AND | | ENGINEER AND THEY DO NOT SHOW ANY DETAILS OF THE | | ELEVATOR INTERIOR.PER FLORIDA STATUTES, 481.229 | | EXEMPTIONS FROM ARCHITECTURAL LICENSURE ONLY APPLY TO | | 1FAMILY AND 2FAMILY RESIDENCES (R3) NOT MULTI-FAMILY | | (R2) OR BUILDINGS OVER $25,000, THEREFORE, DRAWINGS ARE | | REQUIRED TO BE DRAWN BY A LICENSED DESIGN PROFESSIONAL. | | SEE 471.003 FOR MORE INFORMATION. | | | | 5)FBC 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | (561)805-6726 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2009-10-13 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2009-10-13 |
Time |
14:55 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2009-10-13 |
Time |
13:31 |
Sent To |
PC |
|
Notes |
2009-10-13 14:58:52 | | | | | ADD CARD READER CIRCUIT./WRT. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2008-10-14 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-10-14 |
Time |
08:47 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-10-08 |
Time |
08:04 |
Sent To |
|
|
Notes |
2008-10-08 08:07:36 | | | | | SENT TO CAPTAIN WENNERGREN AS THIS REVISION AFFECTS THE | | SPRINKLER SYSTEM./WRT. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2008-06-11 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-06-11 |
Time |
14:25 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-06-11 |
Time |
13:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2008-05-02 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-05-02 |
Time |
11:11 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-05-01 |
Time |
15:41 |
Sent To |
|
|
Notes |
2008-05-01 17:26:45 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1AS | | AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK | | MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002 | | FAC. | | | | 2} THE FEEDERS (#1) INDICATED FOR THE 1000 AMP | | DISCONNECT "EM" ARE NOT COMPLIANT WITH 310.16, @3/0 CU. | | SAME FOR FEEDER ON THE 800 AMP BREAKER FROM THE | | GENERATOR. | | | | 3} THE #10 FEEDERS ON THE SECONDARY SIDE OF TRANSFORMER | | T-18 DO NOT COMPLY WITH 310.16 AND 450.4(A), TABLE | | 450.3(B)@ 125%. | | | | 4} MCC-CH INDICATES IT HAS 600 AMP MAINS AND ALSO | | INDICATES MLO. CORRELATE SAME. | | | | 5} PANEL EM HAS A 400 AMP BREAKER FEEDING MCC-CH, SEE | | COMMENT #4. | | | | 6} INDICATE A BRANCH CIRCUIT AND PANEL DESIGNATION PER | | 620.24 BRANCH CIRCUIT FOR HOISTWAY PIT LIGHTING AND | | RECEPTACLE(S). | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2008-10-10 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-10-10 |
Time |
15:02 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-10-10 |
Time |
15:02 |
Sent To |
E |
|
Notes |
2008-10-10 15:03:21 | REVISION #2 AND #3 DATED 8/15/08. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2008-06-12 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-06-12 |
Time |
15:39 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-06-12 |
Time |
15:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2008-05-09 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-05-09 |
Time |
14:29 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-05-09 |
Time |
14:29 |
Sent To |
|
|
Notes |
2008-05-09 14:42:15 | ***DENIED*** | | | | 1) PLEASE SEE ELECTRICAL COMMENT #1 AND COMPLY. | | | | 2) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003 | | EDITION. | | | | 3) WORK TO COMPLY WITH ASME A17.1, SAFETY CODE FOR | | ELEVATORS AND ESCALATORS. | | | | 4) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE | | SPRINKLER AND FIRE ALARM REMODEL. | | | | 5) EMERGENCY WARNING SIGNS ARE REQUIRED IN ELEVATOR | | LOBBY. | | | | 6) PLEASE PROVIDE SECTION OF NFPA 72 THAT DOES NOT | | REQUIRE SHAFT HEAT DETECTOR TO BE TIED INTO FIRE | | ALARM. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2009-10-06 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2009-10-05 |
Time |
09:56 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2009-10-05 |
Time |
09:55 |
Sent To |
|
|
Notes |
2009-10-06 09:56:19 | GAVE TO BILL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2008-09-30 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-09-30 |
Time |
09:40 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-09-30 |
Time |
09:40 |
Sent To |
E |
|
Notes |
2008-09-30 09:40:28 | TO "BTROBAUG" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2008-06-05 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-06-05 |
Time |
09:25 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-06-05 |
Time |
09:25 |
Sent To |
|
|
Notes |
2008-06-05 09:27:52 | TO "BOB"#14 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-06-05 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-05-09 |
Time |
09:24 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-04-30 |
Time |
11:30 |
Sent To |
|
|
Notes |
2008-04-30 11:32:08 | TO "BOB"#6 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
N |
Date |
2008-06-06 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-06-06 |
Time |
11:36 |
Rev Time |
0.20 |
Received By |
tgordon |
Date |
2008-06-06 |
Time |
11:36 |
Sent To |
|
|
Notes |
2008-06-06 11:38:02 | NO MECHANICAL PLANS SUBMITTED, AND NO | | MECHANICAL PERMIT NUMBER APPLIED FOR AT | | THIS TIME. | | | | ALL MECHANICAL CONDITIONS ARE EXISTING. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2008-05-02 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-05-02 |
Time |
13:33 |
Rev Time |
0.45 |
Received By |
tgordon |
Date |
2008-05-02 |
Time |
13:33 |
Sent To |
|
|
Notes |
2008-05-02 13:38:35 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) PLEASE SHOW ON PLANS COMPLIANCE WITH 2004 FBC | | 3003.1.4 VENTING. | | WHERE STANDBY POWER IS CONNECTED TO ELEVATORS, THE | | MACHINE ROOM VENTILATION OR AIR CONDITIONING SHALL BE | | CONNECTED TO THE STANDBY POWER SOURCE. | | | | ** IF THIS REQUIRERMENT IS EXISTING PLEASE STATE SO ON | | PLAN, IF NOT EXISTING PLEASE PROVIDE REQUIRED | | INFORMATION. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2008-05-01 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2008-05-01 |
Time |
10:18 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2008-05-01 |
Time |
10:18 |
Sent To |
|
|
Notes |
2008-05-01 10:18:59 | *ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE | | VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE | | IMPROVEMENT VALUE. |
|
|