Plan Review Details - Permit 08040794
Plan Review Stops For Permit 08040794
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-06-18 Cont ID  
Sent By mjacobs Date 2008-06-18 Time 16:12 Rev Time 0.00
Received By mjacobs Date 2008-06-16 Time 11:29 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-05-09 Cont ID  
Sent By mjacobs Date 2008-05-09 Time 18:03 Rev Time 0.00
Received By mjacobs Date 2008-05-09 Time 15:36 Sent To PC
Notes
2008-05-09 18:02:54BUILDING PLAN REVIEW
 PERMIT: 08040794
 ADD: 301 N.OLIVE AVE
 CONT: THE WEITZ COMPANY
 TEL: (561)687-4809
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 5-9-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 3)A DESIGN PROFESSIONAL THAT IS REGISTERED TO
 PRACTICE UNDER CHAPTER 481 OR 471 OF THE FLORIDA
 STATUTES SHALL AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND
 DATE TO SAID DRAWINGS AND SPECIFICATIONS PER 106.1 FBC
 2004
  
 ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME, ADDRESS,
 AND LICENCE NUMBER ON EACH SHEET THAT BEARS THEIR SEAL
 PER
 61G15-23.002(2)
  
 4)PROVIDE ENGINEERED AND ARCHITECTURAL DRAWINGS
 SPECIFIC TO THE PROJECT AND SHOW IN DETAIL HOW THEY
 WILL MEET THE REQUIREMENTS OF THE 2004 FBC. SHOW THE
 INTERIOR ELEVATION DETAILS OF THE ELEVATORS: THE
 INTERIOR ELEVATION DRAWINGS SHALL MEET THE REQUIREMENTS
 OF THE SECTION 3007. THE PLANS SUBMITTED ARE MISSING
 THE ORIGINAL SEAL AND SIGNATURE OF THE ARCHITECT AND
 ENGINEER AND THEY DO NOT SHOW ANY DETAILS OF THE
 ELEVATOR INTERIOR.PER FLORIDA STATUTES, 481.229
 EXEMPTIONS FROM ARCHITECTURAL LICENSURE ONLY APPLY TO
 1FAMILY AND 2FAMILY RESIDENCES (R3) NOT MULTI-FAMILY
 (R2) OR BUILDINGS OVER $25,000, THEREFORE, DRAWINGS ARE
 REQUIRED TO BE DRAWN BY A LICENSED DESIGN PROFESSIONAL.
 SEE 471.003 FOR MORE INFORMATION.
  
 5)FBC 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-10-13 Cont ID  
Sent By btrobaug Date 2009-10-13 Time 14:55 Rev Time 0.00
Received By btrobaug Date 2009-10-13 Time 13:31 Sent To PC
Notes
2009-10-13 14:58:52 
  
 ADD CARD READER CIRCUIT./WRT.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-10-14 Cont ID  
Sent By btrobaug Date 2008-10-14 Time 08:47 Rev Time 0.00
Received By btrobaug Date 2008-10-08 Time 08:04 Sent To  
Notes
2008-10-08 08:07:36 
  
 SENT TO CAPTAIN WENNERGREN AS THIS REVISION AFFECTS THE
 SPRINKLER SYSTEM./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-06-11 Cont ID  
Sent By btrobaug Date 2008-06-11 Time 14:25 Rev Time 0.00
Received By btrobaug Date 2008-06-11 Time 13:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-05-02 Cont ID  
Sent By btrobaug Date 2008-05-02 Time 11:11 Rev Time 0.00
Received By btrobaug Date 2008-05-01 Time 15:41 Sent To  
Notes
2008-05-01 17:26:45 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC.
  
 2} THE FEEDERS (#1) INDICATED FOR THE 1000 AMP
 DISCONNECT "EM" ARE NOT COMPLIANT WITH 310.16, @3/0 CU.
 SAME FOR FEEDER ON THE 800 AMP BREAKER FROM THE
 GENERATOR.
  
 3} THE #10 FEEDERS ON THE SECONDARY SIDE OF TRANSFORMER
 T-18 DO NOT COMPLY WITH 310.16 AND 450.4(A), TABLE
 450.3(B)@ 125%.
  
 4} MCC-CH INDICATES IT HAS 600 AMP MAINS AND ALSO
 INDICATES MLO. CORRELATE SAME.
  
 5} PANEL EM HAS A 400 AMP BREAKER FEEDING MCC-CH, SEE
 COMMENT #4.
  
 6} INDICATE A BRANCH CIRCUIT AND PANEL DESIGNATION PER
 620.24 BRANCH CIRCUIT FOR HOISTWAY PIT LIGHTING AND
 RECEPTACLE(S).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-10-10 Cont ID  
Sent By mwennerg Date 2008-10-10 Time 15:02 Rev Time 0.00
Received By mwennerg Date 2008-10-10 Time 15:02 Sent To E
Notes
2008-10-10 15:03:21REVISION #2 AND #3 DATED 8/15/08.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-06-12 Cont ID  
Sent By mwennerg Date 2008-06-12 Time 15:39 Rev Time 0.00
Received By mwennerg Date 2008-06-12 Time 15:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-05-09 Cont ID  
Sent By mwennerg Date 2008-05-09 Time 14:29 Rev Time 0.00
Received By mwennerg Date 2008-05-09 Time 14:29 Sent To  
Notes
2008-05-09 14:42:15***DENIED***
  
 1) PLEASE SEE ELECTRICAL COMMENT #1 AND COMPLY.
  
 2) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003
 EDITION.
  
 3) WORK TO COMPLY WITH ASME A17.1, SAFETY CODE FOR
 ELEVATORS AND ESCALATORS.
  
 4) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
 5) EMERGENCY WARNING SIGNS ARE REQUIRED IN ELEVATOR
 LOBBY.
  
 6) PLEASE PROVIDE SECTION OF NFPA 72 THAT DOES NOT
 REQUIRE SHAFT HEAT DETECTOR TO BE TIED INTO FIRE
 ALARM.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-10-06 Cont ID  
Sent By lmartine Date 2009-10-05 Time 09:56 Rev Time 0.00
Received By lmartine Date 2009-10-05 Time 09:55 Sent To  
Notes
2009-10-06 09:56:19GAVE TO BILL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-09-30 Cont ID  
Sent By adarroug Date 2008-09-30 Time 09:40 Rev Time 0.00
Received By adarroug Date 2008-09-30 Time 09:40 Sent To E
Notes
2008-09-30 09:40:28TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-05 Cont ID  
Sent By adarroug Date 2008-06-05 Time 09:25 Rev Time 0.00
Received By adarroug Date 2008-06-05 Time 09:25 Sent To  
Notes
2008-06-05 09:27:52TO "BOB"#14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-05 Cont ID  
Sent By adarroug Date 2008-05-09 Time 09:24 Rev Time 0.00
Received By adarroug Date 2008-04-30 Time 11:30 Sent To  
Notes
2008-04-30 11:32:08TO "BOB"#6

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2008-06-06 Cont ID  
Sent By tgordon Date 2008-06-06 Time 11:36 Rev Time 0.20
Received By tgordon Date 2008-06-06 Time 11:36 Sent To  
Notes
2008-06-06 11:38:02NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.
  
 ALL MECHANICAL CONDITIONS ARE EXISTING.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-05-02 Cont ID  
Sent By tgordon Date 2008-05-02 Time 13:33 Rev Time 0.45
Received By tgordon Date 2008-05-02 Time 13:33 Sent To  
Notes
2008-05-02 13:38:35PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SHOW ON PLANS COMPLIANCE WITH 2004 FBC
 3003.1.4 VENTING.
 WHERE STANDBY POWER IS CONNECTED TO ELEVATORS, THE
 MACHINE ROOM VENTILATION OR AIR CONDITIONING SHALL BE
 CONNECTED TO THE STANDBY POWER SOURCE.
  
 ** IF THIS REQUIRERMENT IS EXISTING PLEASE STATE SO ON
 PLAN, IF NOT EXISTING PLEASE PROVIDE REQUIRED
 INFORMATION.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-05-01 Cont ID  
Sent By choops Date 2008-05-01 Time 10:18 Rev Time 0.00
Received By choops Date 2008-05-01 Time 10:18 Sent To  
Notes
2008-05-01 10:18:59*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.