Plan Review Details - Permit 08040701
Plan Review Stops For Permit 08040701
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-07-11 Cont ID  
Sent By mjacobs Date 2008-07-11 Time 07:39 Rev Time 0.00
Received By mjacobs Date 2008-07-11 Time 06:58 Sent To  
Notes
2008-07-11 07:16:04PROVISOR: THE GLAZING IN THE TWO WINDOWS SHALL BE
 SAFETY GLAZING PER SECTION 2406.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-06-23 Cont ID  
Sent By mjacobs Date 2008-06-23 Time 12:53 Rev Time 0.00
Received By mjacobs Date 2008-06-23 Time 12:00 Sent To PC
Notes
2008-06-23 12:53:53 
  
 PROVISOR: THE GLAZING IN THE TWO WINDOWS SHALL BE
 SAFETY GLAZING PER SECTION 2406.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-05-08 Cont ID  
Sent By mjacobs Date 2008-05-08 Time 10:13 Rev Time 0.00
Received By mjacobs Date 2008-05-07 Time 07:16 Sent To  
Notes
2008-05-08 10:13:04BUILDING PLAN REVIEW
 PERMIT: 08040701
 ADD: 3810 GEORGIA AVE #101
 CONT: HEDRICH BROTHERS CONSTRUCTION CO. INC
 TEL: (561)689-8808
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 3)2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE. STATE THE LEVEL OF ALTERATION ON THE
 DRAWINGS.
  
 4) FBC 505.2 THE DRAWINGS NEED TO INDICATE THE SQUARE
 FOOT AREA OF THE MEZZANINE WHICH SHALL NOT EXCEED
 ONE-THIRD OF THE AREA OF THE ROOM WHERE IT IS LOCATED.
  
 5)FBC 505.1 THE HEIGHT OF CEILINGS BELOW AND ABOVE A
 MEZZANINE SHALL NOT BE LESS THAN 7 FEET. PROVIDE AN
 ELEVATION DRAWING OF THE FRONT VIEW OF COMPLYING WITH
 THIS SECTION.
  
 6)IF THERE IS A SPRINKLER SYSTEM INSTALLED AT THIS
 STRUCTURE, A CEILING PLAN SHALL BE SUBMITTED SHOWING
 THE SPRINKLER HEAD LAYOUT THROUGH OUT THE BUILDING FBC
 106.3.5.1.1(5)
  
 7)SHEET A.1 INDICATES THAT THE EXISTING 3? 0 X 6?-8?
 SHALL BE RELOCATED BUT THE DRAWINGS FAIL TO SHOW THE
 OLD LOCATION OF THE DOOR. THE DRAWINGS ALSO SHOW TWO
 DIFFERENT SIZE OF STEEL COLUMN: THE KEY LEGEND SHOWS A
 6 X 6 AND DETAIL 2 ON SHEET A.1 SHOWS A 4X4 COLUMN.
 CLARIFY.
  
 8)FBC TABLE 1607.1 THE MINIMUM DISTRIBUTED AND
 CONCENTRATED LIVE LOAD FOR LIGHT STORAGE IS 125PSF NOT
 40PSF. THE EXISTING WOOD CEILING FLOOR JOIST IS NOT
 ADEQUATE FOR LIGHT STORAGE PER TABLE 1607.1. SEE FBC
 SECTION 1607 FOR MORE INFORMATION.
  
 9)110.4.2 STORAGE & FACTORY- INDUSTRIAL OCCUPANCIES.
 IT SHALL BE THE RESPONSIBILITY OF THE OWNER, AGENT,
 PROPRIETOR OR OCCUPANT OF GROUP S AND GROUP F
 OCCUPANCIES, OR ANY OCCUPANCY WHERE EXCESSIVE FLOOR
 LOADING IS LIKELY TO OCCUR, TO EMPLOY A COMPETENT
 ARCHITECT OR ENGINEER IN COMPUTING THE SAFE FLOOR LOAD
 CAPACITY. ALL SUCH COMPUTATIONS SHALL BE ACCOMPANIED BY
 AN AFFIDAVIT FROM THE ARCHITECT OR ENGINEER STATING THE
 SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR IN POUNDS PER
 SQ FT. THE
 COMPUTATIONS & AFFIDAVIT SHALL BE FILED AS A PERMANENT
 RECORD OF THE BLDG DEPT.
  
 10)110.4.3. SIGNS REQUIRED. IN EVERY BUILDING OR PART
 OF A BUILDING USED FOR STORAGE, INDUSTRIAL OR HAZARDOUS
 PURPOSES, THE SAFE FLOOR LOADS, AS REVIEWED BY THE
 BUILDING OFFICIAL ON THE PLAN, SHALL BE MARKED ON
 PLATES OF APPROVED DE SIGN WHICH SHALL BE SUPPLIED &
 SECURELY AFFIXED BY THE OWNER OF THE BUILDING IN A
 CONSPICUOUS PLACE IN EACH STORY TO WHICH THEY RELATE.
 SUCH PLATES SHALL NOT BE REMOVED OR DEFACED, & IF LOST,
 REMOVED THE OWNER OF THE BUILDING SHALL REPLACE THEM.
  
 11)INDICATE CLEARLY THE ATTACHMENT METHOD FOR THE
 GUARDRAIL TO THE FLOOR AND WALL SHOWING ALL FASTENERS.
 SHOW ON THE PLANS WHERE THE NEW 4 INCH NON-BEARING WALL
 WILL BE CONSTRUCTED. WHAT IS THE DIAGONAL PIECE SHOWN
 BELOW THE STAIR PLATFORM? IS THIS PIECE ATTACHED TO THE
 EXTERIOR WALL?
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2008-05-09 Cont ID  
Sent By btrobaug Date 2008-05-09 Time 08:37 Rev Time 0.00
Received By btrobaug Date 2008-05-09 Time 08:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-07-14 Cont ID  
Sent By mawillia Date 2008-07-14 Time 16:28 Rev Time 0.00
Received By mawillia Date 2008-07-14 Time 16:20 Sent To  
Notes
2008-07-14 16:28:26*****APPROVED*****
  
  
 NEW PLAN SHEET A.1 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-06-19 Cont ID  
Sent By mawillia Date 2008-06-19 Time 13:21 Rev Time 0.00
Received By mawillia Date 2008-06-19 Time 13:10 Sent To  
Notes
2008-06-19 13:16:20*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLAN SHEET A.1 STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-05-09 Cont ID  
Sent By mwennerg Date 2008-05-09 Time 10:09 Rev Time 0.00
Received By mwennerg Date 2008-05-09 Time 10:09 Sent To  
Notes
2008-05-09 10:14:14***DENIED***
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003
 EDITION.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 3) MINIMUM 2A-10B,C RATED FIRE EXTINGUISHERS TO BE
 PROVIDED AND MOUNTED AT LOCATIONS TO SATISFY THE 75'
 TRAVEL DISTANCE REQUIREMENT.
  
 4) PLEASE ILLUSTRATE NEW AND OR EXISTING EXIT LIGHTS
 AND EMERGENCY LIGHTING FACILITIES.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-09-05 Cont ID  
Sent By adarroug Date 2008-09-05 Time 14:13 Rev Time 0.00
Received By adarroug Date 2008-09-05 Time 14:13 Sent To P
Notes
2008-09-05 14:14:03TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-07-02 Cont ID  
Sent By adarroug Date 2008-07-02 Time 15:08 Rev Time 0.00
Received By adarroug Date 2008-07-02 Time 15:08 Sent To  
Notes
2008-07-02 15:10:08TO "BOB"#2

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-10 Cont ID  
Sent By adarroug Date 2008-06-10 Time 11:43 Rev Time 0.00
Received By adarroug Date 2008-06-10 Time 11:43 Sent To  
Notes
2008-06-10 11:43:56TO "BOB"#8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-09 Cont ID  
Sent By mwennerg Date 2008-05-09 Time 10:15 Rev Time 0.00
Received By mwennerg Date 2008-04-25 Time 12:10 Sent To  
Notes
2008-04-25 12:28:09TO "BOB"#12

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-05-08 Cont ID  
Sent By tgordon Date 2008-05-08 Time 11:42 Rev Time 0.25
Received By tgordon Date 2008-05-08 Time 11:42 Sent To  
Notes
2008-05-08 11:45:22** NOTICE **
  
 1) A MECHANICAL (A/C) PERMIT WILL BE REQUIRED TO
 RELOCATE THE EXISTING AIR HANDLER TO THE MEZZANINE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-09-05 Cont ID  
Sent By mperson Date 2008-09-05 Time 16:38 Rev Time 0.00
Received By mperson Date 2008-09-05 Time 16:38 Sent To PC
Notes
2008-09-05 16:41:45REVISION: "OK" NEW 11" X 17" SK.1 SANITARY RISER
 DIAGRAM ADDRESSING PLUMBING PROVISO. *MRPERSON.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-07-03 Cont ID  
Sent By mperson Date 2008-07-03 Time 13:06 Rev Time 0.00
Received By mperson Date 2008-07-03 Time 13:06 Sent To  
Notes
2008-07-03 13:10:19******PROVISO******
 PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN THE
 INSTALLATION OR REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED. A PLUMBING
 PERMIT IS REQUIRED AND AN INSPECTION IS REQUIRED OF
 PLUMBING DEMO WORK PRIOR TO COVERING DEMO WORK WITH
 FINNISH WALLS, CIELINGS, OR POURED CONCRETE SLABS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-06-20 Cont ID  
Sent By mperson Date 2008-06-20 Time 13:24 Rev Time 0.00
Received By mperson Date 2008-06-20 Time 13:24 Sent To  
Notes
2008-06-20 14:05:30PLUMBING PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONES FOR THE PURPOSE OF CONTINUITY.
  
 1. SHEET A.1 FLOOR PLAN EXIST. TOILET #102: THE
 REMOVAL OF THE EXISTING LAVATORY AND RELOCATING THE MOP
 SINK IN ITS PLACE IS UNACCEPTABLE PER FBC-2004 PLUMBING
 SECTION 405.3.2 PUBLIC LAVATORIES.
 IN EMPLOYEE AND PUBLIC TOILET ROOMS, THE REQUIRED
 LAVATORY SHALL BE LOCATED IN THE SAME ROOM AS THE
 REQUIRED WATER CLOSET.
 NOTE: THIS DOES NOT SAY FIXTURES CAN BE SUBSTITUTED.
  
 **RESPONSE NOTED, HOWEVER THE RESUBMITTED PLANS ARE
 STILL INDICATING A WATERCLOSET IN EXIST TOILET 102 WITH
 THE RELOCATED MOP SINK. CODE CLEARLY INDICATES THE A
 LAVATORY SHALL BE LOCATED IN THE BATHROOM WITH A WATER
 CLOSET. IF IT IS THE INTENT TO HAVE A UNISEX BATHROOM
 AS DISCUSSED IN OUR PHONE CONVERSATION AND MOVE THE MOP
 SINK TO ROOM 102 THEN THE WATER CLOSET IN ROOM 102
 SHALL BE DELETED. PER SECTION 405.3.2. ALSO THE
 SUBMITTED SANITARY RISER DIAGRAM DOES NOT INDICATE THE
 EXISTING SANITARY SYSTEM. PLEASE REMEMBER THE MOP SINK
 CAN NOT DRAIN INTO A WET VENTED BATHROOM GROUP, IT MUST
 DRAIN DOWNSTREAM OF THE WET VENTED BATHROOM GROUP.
 CLEARLY INDICATE HOW THE EXISTING SANITARY IS INSTALLED
 AS WELL AS THE PROPOSED TO MEET COMPLIANCE. PER FBC-
 PLUMBING SECTION 909.1 WET VENT PERMITTED.
  
 2. "OK" COMMENT ADDRESSED.
  
 3. "OK" COMMENT ADDRESSED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-04-30 Cont ID  
Sent By mperson Date 2008-04-30 Time 13:19 Rev Time 0.00
Received By mperson Date 2008-04-30 Time 13:19 Sent To  
Notes
2008-04-30 13:50:48PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A.1 FLOOR PLAN EXIST. TOILET #102: THE
 REMOVAL OF THE EXISTING LAVATORY AND RELOCATING THE MOP
 SINK IN ITS PLACE IS UNACCEPTABLE PER FBC-2004 PLUMBING
 SECTION 405.3.2 PUBLIC LAVATORIES.
 IN EMPLOYEE AND PUBLIC TOILET ROOMS, THE REQUIRED
 LAVATORY SHALL BE LOCATED IN THE SAME ROOM AS THE
 REQUIRED WATER CLOSET.
 NOTE: THIS DOES NOT SAY FIXTURES CAN BE SUBSTITUTED.
  
 2. SHEET A.1 FLOOR PLAN DOES NOT INDICATE AN EXISTING
 DRINKING FOUNTAIN. PER FBC-2004 PLUMBING TABLE 403.1
 (S-1) MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES A
 DRINKING FOUNTAIN IS REQUIRED (1 PER 1000) AND IT SHALL
 BE ADA COMPLIANT PER FBC-2004 CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE PER THE FOLLOWING.
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELAVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS (PAPER CUP HOLDER PROVIDED) AS
 WOULD ACHIEVE THE REQUIRED ACCESSIBILITY FOR EACH GROUP
 ON EACH FLOOR).
  
 3. SHEET A.1 FLOOR PLAN DOES NOT INDICATE AN EXISTING
 EMERGENCY SHOWER AND EYEWASH STATION AND THE PLANS DO
 NOT INDICATE WHAT TYPES OF MATERIALS ARE BEING STORED.
 PLEASE CLARIFY WHAT TYPES OF MATERIALS ARE BEING STORED
 AND IF AN EMERGENCY SHOWER AND EYEWASH STATION IS
 REQUIRED. ALSO IF HAZARDOUS MATERIALS ARE BEING STORED
 PLEASE PROVIDE MATERIAL DATA SAFETY SHEETS (MSDS).
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 2 Status N Date 2008-06-12 Cont ID  
Sent By choops Date 2008-06-12 Time 14:57 Rev Time 0.00
Received By choops Date 2008-06-12 Time 14:57 Sent To  
Notes
2008-06-12 15:00:39*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-04-28 Cont ID  
Sent By choops Date 2008-04-28 Time 14:29 Rev Time 0.00
Received By choops Date 2008-04-28 Time 14:29 Sent To  
Notes
2008-04-28 14:36:09***FAILED***
  
  
 1)PLEASE PROVIDE AN APPRAISAL SHOWING THE
 IMPROVEMENT VALUE OF THE PROPERTY (STRUCTURE'S VALUE).
 PURSUANT TO SECTION 94-441(C) OF THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS:LANDSCAPING SHALL BE IN
 COMPLIANCE WITH CURRENT REGULATIONS IF VALUE OF
 PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE.
  
 AS THE PALM BEACH COUNTY PROPERTY APPRAISER DOES NOT
 LIST AN "IMPROVEMENT VALUE", AN APPRAISAL SHALL BE
 PROVIDED TO DETERMINE IF ZONING REVIEW IS APPLICABLE.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved