Plan Review Details - Permit 08040698
Plan Review Stops For Permit 08040698
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-05-05 Cont ID  
Sent By rmcdouga Date 2008-05-05 Time 10:18 Rev Time 0.00
Received By rmcdouga Date 2008-05-05 Time 07:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-06-11 Cont ID  
Sent By btrobaug Date 2008-06-11 Time 11:07 Rev Time 0.00
Received By btrobaug Date 2008-06-11 Time 11:01 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-06-06 Cont ID  
Sent By btrobaug Date 2008-06-06 Time 08:45 Rev Time 0.00
Received By btrobaug Date 2008-06-05 Time 09:03 Sent To PC
Notes
2008-06-06 08:44:47 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER
 1AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
  
 1} AN ELECTRICAL PERMIT IS REQUIRED FOR THE SCOPE OF
 WORK PURPOSED. 105.1 FBC AS AMENDED.THE ELECTRICAL
 CONTRACTOR WHOSE NAME APPEARS ON THE APPLICATION
 SUBMITTED IS NOTCURRENTLY REGISTERED WITH THE CITY OF
 WEST PALM BEACH.
  
 2} SECTION 106
 CONSTRUCTION DOCUMENTS
 106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION DOCUMENTS,
 SPECIAL INSPECTION AND STRUCTURAL OBSERVATION PROGRAMS,
 AND OTHER DATA SHALL BE SUBMITTED IN ONE TWO OR MORE
 SETS WITH EACH APPLICATION FOR A PERMIT. THE
 CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A DESIGN
 PROFESSIONAL WHERE REQUIRED BY THE STATUTES. WHERE
 SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS
 AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS
 TO BE PREPARED BY A DESIGN PROFESSIONAL. NO ELECTRICAL
 PLANS WHERE SUBMITTED FOR REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-05-14 Cont ID  
Sent By btrobaug Date 2008-05-14 Time 14:35 Rev Time 0.00
Received By btrobaug Date 2008-05-13 Time 15:39 Sent To PC
Notes
2008-05-14 09:48:11 
  
  
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE COMPLIANCE WITH ARTICLE 800.44(B), ABOVE
 ROOFS COMMUNICATIONS WIRES AND CABLES SHALL HAVE A
 VERTICAL CLEARANCE OF NOT LESS THAN 2.5 M (8 FT) FROM
 ALL POINTS OF ROOFS ABOVE WHICH THEY PASS.
 * THIS COMMENT WAS MADE TO FOREWARN THE CONTRACTOR THAT
 THIS COULD BE AN ISSUE. IT WILL NOW BE RESOLVED AT
 INSPECTION.
  
 2} 210.52 (A) GENERAL PROVISIONS IN EVERY KITCHEN,
 FAMILY ROOM, DINING ROOM, LIVING ROOM, PARLOR, LIBRARY,
 DEN, SUNROOM, BEDROOM, RECREATION ROOM, OR SIMILAR ROOM
 OR AREA OF DWELLING UNITS, RECEPTACLE OUTLETS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE GENERAL PROVISIONS
 SPECIFIED IN 210.52(A)(1) THROUGH (A)(3).
  
 AAMA/NPEA/NSA 2100-02 VOLUNTARY SPECIFICATIONS FOR
 SUNROOMS IN THE RESIDENTIAL BUILDING CODE REFERENCES
 R301.2.1.1.2
  
 R301.2.1.1.2 SUNROOMS.
 SUNROOMS SHALL COMPLY WITH AAMA/NPEA/NSA 2100 WITH THE
 STRUCTURAL REQUIREMENTS AND TESTING PROVISIONS OF
 CHAPTER 5 MODIFIED TO INCORPORATE ASCE 7. NOTE THE TERM
 "STRUCTURAL REQUIREMENTS". THIS ARTICLE DOES NOT
 SUPERSEDE THE 2005 NEC ARTICLE SITED ABOVE.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-05-02 Cont ID  
Sent By btrobaug Date 2008-05-02 Time 16:11 Rev Time 0.00
Received By btrobaug Date 2008-05-02 Time 15:58 Sent To B
Notes
2008-05-02 16:10:58 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE COMPLIANCE WITH ARTICLE 800.44(B), ABOVE
 ROOFS COMMUNICATIONS WIRES AND CABLES SHALL HAVE A
 VERTICAL CLEARANCE OF NOT LESS THAN 2.5 M (8 FT) FROM
 ALL POINTS OF ROOFS ABOVE WHICH THEY PASS.
  
 2} 210.52 (A) GENERAL PROVISIONS IN EVERY KITCHEN,
 FAMILY ROOM, DINING ROOM, LIVING ROOM, PARLOR, LIBRARY,
 DEN, SUNROOM, BEDROOM, RECREATION ROOM, OR SIMILAR ROOM
 OR AREA OF DWELLING UNITS, RECEPTACLE OUTLETS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE GENERAL PROVISIONS
 SPECIFIED IN 210.52(A)(1) THROUGH (A)(3).
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-29 Cont ID  
Sent By adarroug Date 2008-05-29 Time 11:05 Rev Time 0.00
Received By adarroug Date 2008-05-29 Time 11:05 Sent To E
Notes
2008-05-29 11:06:18TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-08 Cont ID  
Sent By adarroug Date 2008-05-08 Time 15:04 Rev Time 0.00
Received By adarroug Date 2008-05-08 Time 15:04 Sent To E
Notes
2008-05-08 15:05:08TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-05 Cont ID  
Sent By rmcdouga Date 2008-05-05 Time 13:22 Rev Time 0.00
Received By rmcdouga Date 2008-04-25 Time 12:03 Sent To  
Notes
2008-04-25 12:04:05TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2008-04-29 Cont ID  
Sent By choops Date 2008-04-29 Time 15:17 Rev Time 0.00
Received By choops Date 2008-04-29 Time 15:17 Sent To E
Notes
2008-04-29 15:18:05***APPROVED***