Plan Review Details - Permit 08040672
Plan Review Stops For Permit 08040672
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-17 Cont ID  
Sent By adarroug Date 2008-06-17 Time 16:20 Rev Time 0.00
Received By adarroug Date 2008-06-17 Time 16:20 Sent To M
Notes
2008-06-17 16:21:16TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-16 Cont ID  
Sent By adarroug Date 2008-06-16 Time 15:54 Rev Time 0.00
Received By adarroug Date 2008-06-16 Time 15:54 Sent To M
Notes
2008-06-16 15:54:22TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-25 Cont ID  
Sent By tgordon Date 2008-04-25 Time 09:48 Rev Time 0.00
Received By tgordon Date 2008-04-24 Time 14:33 Sent To  
Notes
2008-04-24 14:33:41TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-06-18 Cont ID  
Sent By tgordon Date 2008-06-18 Time 13:41 Rev Time 0.45
Received By tgordon Date 2008-06-18 Time 13:41 Sent To  
Notes
2008-06-18 14:00:37SPACE PAK HIGH VELOCITY SYSTEM
  
 *** PROVISO ***
 1) IF PLASTIC REGISTERS, GRILLES OR DIFFUSERS ARE USED
 THEN PROVIDE UL TESTING REPORT.
 PER 2004 FBC/R M1601.16 DUCT REGISTERS, GRILLES AND
 DIFFUSERS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS, AND SHALL
 HAVE A FLAME SPREAD RATING NOT OVER 25 WITHOUT EVIDENCE
 OF CONTINUED PROGRESSIVE COMBUSTION AND A
 SMOKE-DEVELOPED RATING NOT OVER 50 WHEN TESTED IN
 ACCORDANCE WITH ASTM E 84. BALANCING DAMPERS OR OTHER
 MEANS OF SUPPLY AIR ADJUSTMENT SHALL BE PROVIDED IN THE
 BRANCH DUCTS OR AT EACH INDIVIDUAL DUCT REGISTER,
 GRILLE OR DIFFUSER.
  
 2) HAVE DETAILED MANUFACTURER'S SPECIFICATION'S AND
 INSTALLATION INSTRUCTIONS FOR A/C SYSTEM AND
 PRE-ENGINEERED DUCT SYSTEM ON JOB SITE FOR CITY
 INSPECTORS. PER 2004 FBC/R M1401.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-06-17 Cont ID  
Sent By tgordon Date 2008-06-17 Time 10:22 Rev Time 0.45
Received By tgordon Date 2008-06-17 Time 10:22 Sent To  
Notes
2008-06-17 10:35:14PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE PLAN SUBMITTED SHOWS THE SUPPLY DUCTS AS 4" THIS
 IS A PER ENGINEERED SYSTEM AND THE MANUFACTURE STATES
 THE SUPPLY TUBING (DUCTS) NEED TO BE 2' (SEE ATTACHED
 MANUFACTURE SPEC. SHEET) PLEASE CORRECT, PER 2004 FBC/R
 M1401.1.
  
 2) THE PLAN SHOWS A 28X20 RETURN AIR GRILL IN A CLOSET
 (SEE YELLOW HIGH LIGHT ON PLAN) PLEASE EXPLAIN OR
 CORRECT, PER 2004 FBC/R M1602.2 (3).
  
 3) PLAN SHOWS NO RETURN AIR GRILL IN THE HALL FOR
 COMMON RETURN, ONLY A MIXING BOX ABOVE, PLEASE EXPLAIN
 OR CORRECT, PER 2004 FBC/R M1602.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-04-25 Cont ID  
Sent By tgordon Date 2008-04-25 Time 09:03 Rev Time 0.45
Received By tgordon Date 2008-04-25 Time 09:03 Sent To  
Notes
2008-04-25 09:26:14PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) PLEASE SUBMIT MANUAL D CALCULATIONS FOR RESIDENTIAL
 DUCT DESIGN, PER 2004 FBC/R M1601.1.
  
 2) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE
 AIR DIFFUSERS SHOWING THEIR FLAME SPREAD RATING AND
 SMOKE-DEVELOPED RATING. PER 2004 FBC/R M1601.16
 REGISTERS, GRILLES AND DIFFUSERS.
 DUCT REGISTERS, GRILLES AND DIFFUSERS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS, AND SHALL HAVE A FLAME
 SPREAD RATING NOT OVER 25 WITHOUT EVIDENCE OF CONTINUED
 PROGRESSIVE COMBUSTION AND A SMOKE-DEVELOPED RATING NOT
 OVER 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84.
 BALANCING DAMPERS OR OTHER MEANS OF SUPPLY AIR
 ADJUSTMENT SHALL BE PROVIDED IN THE BRANCH DUCTS OR AT
 EACH INDIVIDUAL DUCT REGISTER, GRILLE OR DIFFUSER.
  
 3) PLEASE SHOW THE CFM'S AT ALL SUPPLY AIR DIFFUSERS,
 PER WPB AMEND. 106.3.5.4 (10).
  
 4) PLEASE SHOW THE SEER OF THE A/C SYSTEM IN THE
 EQUIPMENT SCHEDULE ON THE PLAN.
  
 5) A/C SYSTEM MODEL NUMBERS LISTED ON THE A/C EQUIPMENT
 SCHEDULE COULD NOT BE FOUND ON THE ARI DIRECTORY
 WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI CERTIFICATE,
 SEE 2004 FBC 13-407.1.ABC.3.1.1 OR 13-607.1.ABC.3.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]