Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2008-08-11 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2008-08-11 |
Time |
15:56 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2008-08-11 |
Time |
15:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2008-04-29 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2008-04-29 |
Time |
10:03 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2008-04-29 |
Time |
10:03 |
Sent To |
M |
|
Notes |
2008-04-29 10:03:40 | 2004 FBC W/2007 REVISIONS | | LEVEL 2 ALTERATION | | | | DENIED BY BUILDING | | | | 1) SUBMIT TWO COPIES OF FLOOR PLANS SPECIFYING THE | | TYPE, SIZE AND LOCATION OF THE WINDOWS BEING REPLACED. | | INDICATE ANY OPENINGS WITH MULTIPLE WINDOWS MULLED | | TOGETHER. FBC 106.1.1* CITY AMENDMENTS | | | | 2) PROVIDE TWO COPIES OF A FLOOR PLAN SHOWING THE | | LOCATIONS WHERE THE STUCCO WILL BE INSTALLED. FBC | | 106.1.1* CITY AMENDMENTS | | | | 3) SUBMIT TWO COPIES OF CURRENT PRODUCT APPROVALS FOR | | THE WINDOWS, STRUCTURAL MULLIONS, AND STORM PANELS AS | | REQUIRED BY DCA RULE 9B-72. THE PRODUCT APPROVALS | | SUBMITTED FOR THE WINDOWS ARE EXPIRED. | | | | 4) SUBMIT TWO COPIES OF A KEY PLAN AND AN INSTALLATION | | SCHEDULE FOR THE STORM PANELS. SPECIFY THE MOUNT TYPE, | | THE ANCHOR TYPE, ANCHOR SPACING, EDGE DISTANCE, | | SEPARATION DISTANCE, SPANS, ETC. SEE THE ATTACHED | | SAMPLE SCHEDULE. FBC 106.1.2* CITY AMENDMENTS | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
N |
Date |
2008-08-05 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-08-05 |
Time |
09:41 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-08-05 |
Time |
09:25 |
Sent To |
M |
|
Notes |
2008-08-05 09:43:28 | | | | | A/C PERMIT UNDER 0807077, NO ELECTRICAL THIS | | APPLICATION./WRT. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2008-04-28 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-04-28 |
Time |
11:15 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-04-28 |
Time |
11:04 |
Sent To |
B |
|
Notes |
2008-04-28 11:15:12 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER | | 1AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | 1} | | | | 1} TWO COPIES OF PLANS MUST BE SUBMITTED FOR REVIEW PER | | 106.1 FBC AS AMENDED. | | | | 2} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. | | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER | | 440.14,RECEPTACLE PER 210.63. | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER | | 106.1.3.FBC. | | | | 4} INCLUDE THE ADDRESS OF THE PROJECT ON THE PLANS PER | | 106.1.1 FBC AS AMENDED. | | | | 5} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1 | | RESIDENTIAL FLORIDA BUILDING CODE.LOCATE SAME ON | | PLANS. | | | | 6} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN | | THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE | | INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS | | DESIGNED. | | | | AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS | | AMENDED. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2008-07-29 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-07-29 |
Time |
15:24 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-07-29 |
Time |
15:24 |
Sent To |
Z |
|
Notes |
2008-07-29 15:24:25 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-04-29 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2008-04-29 |
Time |
10:03 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2008-04-24 |
Time |
14:12 |
Sent To |
|
|
Notes |
2008-04-24 14:13:06 | TO "Z" BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
N |
Date |
2008-08-05 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-08-05 |
Time |
10:57 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2008-08-05 |
Time |
10:57 |
Sent To |
B |
|
Notes |
2008-08-05 10:59:00 | MECHANICAL PERMIT #08070771 WAS ISSUED FOR THE A/C | | WORK. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2008-04-29 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-04-29 |
Time |
16:14 |
Rev Time |
0.20 |
Received By |
tgordon |
Date |
2008-04-29 |
Time |
16:14 |
Sent To |
|
|
Notes |
2008-04-29 16:17:23 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) A MECHANICAL (A/C) PERMIT WILL BE REQUIRED FOR THE | | CHANGE-OUT OF THE AIR CONDITIONING SYSTEM. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2008-08-03 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2008-08-03 |
Time |
11:15 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2008-08-03 |
Time |
11:15 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2008-04-28 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2008-04-28 |
Time |
08:46 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2008-04-28 |
Time |
08:46 |
Sent To |
E |
|
Notes |
2008-04-28 08:49:09 | ***FAILED*** | | | | | | 1)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY SHOWING | | THE DEMOLITION WORK AND ANY OTHER PROPOSED EXTERIOR | | WORK WITH SETBACK DIMENSIONS TO ALL PROPERTY LINES. | | | | 2)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C | | EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION | | 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT | | PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK. | | | | | | NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY | | GENERATE ADDITIONAL COMMENTS. | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | ZONING TECHNICIAN (561)805-6720 |
|
|