Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-07-03 Cont ID  
Sent By rmcdouga Date 2008-07-03 Time 09:26 Rev Time 0.00
Received By rmcdouga Date 2008-07-03 Time 09:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-25 Cont ID  
Sent By rmcdouga Date 2008-04-25 Time 07:40 Rev Time 0.00
Received By rmcdouga Date 2008-04-25 Time 07:08 Sent To  
Notes
2008-04-25 08:22:392004 FBC W/2007 REVISIONS
 INSTALL ACCORDION SHUTTERS
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C. THE
 DESIGN PRESSURE CALCULATIONS THAT WERE SUBMITTED ARE
 FOR EXPOSURE B, PLEASE CORRECT. SEE FBC R301.2.1.4
 WHICH REVISED THE DEFINITION OF EXPOSURE C TO INCLUDE
 BUILDINGS ADJACENT TO OPEN AREAS OF EXPOSURE TYPE C
 TERRAIN IN ANY QUADRANT FOR A DISTANCE OF MORE THAN 600
 FEET. PLEASE REVISE CALCULATIONS.
  
 2) ON SHEET 5 OF THE DRAWINGS WALL MOUNT SECTION F IS
 CIRCLED. THE CONNECTION TYPE FOR THIS MOUNT IS C2 AT
 THE TOP AND BOTTOM. ON THE ANCHOR SCHEDULE ON SHEET 7,
 THE ANCHOR SPACING THAT IS CIRCLED IS FOR C3 CONNECTION
 TYPE. PLEASE CORRECT.
  
 3) THE HEIGHT OF ONE OPENING IS SPECIFIED AS 77"WHICH
 IS A SPAN MORE THAN 6'-0". ON SHEET 7 THE FASTENER
 SPACING THAT WAS CIRCLED IS IN THE COLUMN FOR SPANS NOT
 EXCEEDING 6'-0". PLEASE CORRECT.
  
 4) UNLESS THE ANCHORS ARE BEING INSTALLED INTO A
 MINIMUM OF 3,000 PSI CONCRETE, THE TABLE FOR HOLLOW
 CONCRET BLOCK SHOULD BE USED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]