2008-04-23 16:46:22 | GAS PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. PROVIDE CORRESPONDING LENGTHS TO ALL CUT SECTIONS |
| OF PIPE. REFERENCE THE RED CIRCLED YELLOW HIGH LIGHTED |
| CUT SECTIONS INDICATING NON-COMPLIANCE. NOTE: LONGEST |
| LENGTH AND PIPE SIZING OF THE SYSTEM MAY CHANGE. PER |
| FBC FUEL GAS SECTION 401.1 SCOPE. |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. PER FBC FUEL GAS |
| SECTION 401.1 SCOPE. |
| |
| 3. PER TABLE 402.4(20) THE UNDER GROUND PE PIPING TO |
| THE POOL HEATER IS UNDER SIZED. AT A LONGEST LENGTH OF |
| 90' IT SHOULD BE 1-1/2". PLEASE CORRECT AND RESUBMIT. |
| |
| 4. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| SECTION *106.3.4.3. |
| IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR |
| ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER |
| FLORIDA STATUTES 481 AND 471 RESPECTIVELY. |
| |
| END OF COMMENTS: |
| |