Plan Review Details - Permit 08040592
Plan Review Stops For Permit 08040592
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-05-01 Cont ID  
Sent By mperson Date 2008-05-01 Time 10:45 Rev Time 0.00
Received By mperson Date 2008-05-01 Time 10:45 Sent To PC
Notes
2008-05-01 10:47:37****************PROVISO****************
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 3,750 CUBIC FEET REQUIRED.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-04-23 Cont ID  
Sent By mperson Date 2008-04-23 Time 15:54 Rev Time 0.00
Received By mperson Date 2008-04-23 Time 15:53 Sent To PC
Notes
2008-04-23 16:46:22GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PROVIDE CORRESPONDING LENGTHS TO ALL CUT SECTIONS
 OF PIPE. REFERENCE THE RED CIRCLED YELLOW HIGH LIGHTED
 CUT SECTIONS INDICATING NON-COMPLIANCE. NOTE: LONGEST
 LENGTH AND PIPE SIZING OF THE SYSTEM MAY CHANGE. PER
 FBC FUEL GAS SECTION 401.1 SCOPE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. PER FBC FUEL GAS
 SECTION 401.1 SCOPE.
  
 3. PER TABLE 402.4(20) THE UNDER GROUND PE PIPING TO
 THE POOL HEATER IS UNDER SIZED. AT A LONGEST LENGTH OF
 90' IT SHOULD BE 1-1/2". PLEASE CORRECT AND RESUBMIT.
  
 4. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-30 Cont ID  
Sent By adarroug Date 2008-04-30 Time 11:50 Rev Time 0.00
Received By adarroug Date 2008-04-30 Time 11:50 Sent To G
Notes
2008-04-30 11:50:44TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-23 Cont ID  
Sent By mperson Date 2008-04-23 Time 16:46 Rev Time 0.00
Received By mperson Date 2008-04-22 Time 16:29 Sent To  
Notes
***NONE***