Plan Review Details - Permit 08040560
Plan Review Stops For Permit 08040560
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-05-30 Cont ID  
Sent By mjacobs Date 2008-05-30 Time 14:48 Rev Time 0.00
Received By mjacobs Date 2008-05-30 Time 14:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-05-20 Cont ID  
Sent By mjacobs Date 2008-05-20 Time 08:16 Rev Time 0.00
Received By mjacobs Date 2008-05-19 Time 14:47 Sent To  
Notes
2008-05-20 08:08:57BUILDING PLAN REVIEW 2ND
 PERMIT: 08040560
 ADD: 1501 S. FLAGLER DR. #7H
 CONT: JEFFREY GOMERSALL BLDG CONTR.
 TEL: (561)718-1866
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 5-19-08
 REVIEW: 2ND
 ACTION: DENIED
  
 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) OK
  
 **NOTED; FBC EXISTING LEVEL 2 ALTERATION INCLUDE THE
 RECONFIGURATION OF SPACE, THE ADDITION OR ELIMINATION
 OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSION
 OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL
 EQUIPMENT. THE NEW WALL AND THE NEW DOOR WILL BE
 INCLUDED IN THE SECTION AS LEVEL 2 ALTERATION.**
 3)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 4)OK
 9)OK
  
 **NOTED, HOWEVER, THE CONSTRUCTION TYPE, USE AND
 OCCUPANCY AND THE FLOOD ZONE INFORMATION ON THE PLANS
 ARE INCORRECT. THIS BUILDING IS A HI-RISE; THEREFORE
 CONSTRUCTION TYPE VB WILL NOT MEET THE REQUIREMENTS OF
 A HI-RISE BUILDING. GROUP R3 IS ONE AND TWO FAMILY
 DWELLINGS. THE CORRECT FLOOD ZONE IS A5; THERE IS NO
 FLOOD ZONE IN THE CITY OF WEST PALM BEACH DESIGNATED AS
 ?NEAR COASTAL?.**
 10)INDICATE THE TYPE OF CONSTRUCTION OF THE BUILDING
 PER 2004 FBC CHAPTER 6 AND TABLE 601. THIS INFORMATION
 IS REQUIRED FOR PLAN REVIEW TO DETERMINE THE TYPE OF
 MATERIALS WHICH ARE ALLOWED IN THE BUILDING.
  
 11)OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-05-01 Cont ID  
Sent By mjacobs Date 2008-05-01 Time 12:24 Rev Time 0.00
Received By mjacobs Date 2008-05-01 Time 10:54 Sent To  
Notes
2008-05-01 12:24:09BUILDING PLAN REVIEW
 PERMIT: 08040560
 ADD: 1501 S. FLAGLER DR. #7H
 CONT: JEFFREY GOMERSALL BLDG CONTR.
 TEL: (561)718-1866
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 5-1-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) PLANS SUBMITTED FOR PERMIT AFTER JULY 1ST, 2007
 SHALL BE REVIEWED TO THE 2004 FBC BUILDING WITH THE
 2007 SUPPLEMENTS.
  
 3)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 4)(CONDO CONSTRUCTION/RENOVATION)
 PER FLORIDA STATUTES, 481.229 EXEMPTIONS FROM
 ARCHITECTURAL LICENSURE ONLY APPLY TO 1FAMILY AND
 2FAMILY RESIDENCES (R3) NOT MULTI-FAMILY (R2) OR
 BUILDINGS OVER $25,000, THEREFORE, DRAWINGS ARE
 REQUIRED TO BE DRAWN BY A LICENSED DESIGN
 PROFESSIONAL.
  
 5)A DESIGN PROFESSIONAL THAT IS REGISTERED TO
 PRACTICE UNDER CHAPTER 481 OR 471 OF THE FLORIDA
 STATUTES SHALLAFFIX THEIR OFFICIAL SEAL, SIGNATURE
 AND DATE TO SAID DRAWINGS AND SPECIFICATION PER 106.1
 FBC 2004, THE EXEMPTION FROM LICENSURE UNDER 481.229
 FLORIDA STATUTES DOES NOT EXEMPT THE DESIGNER
 RESPONSIBLE FOR THE DRAWINGS FROM SIGNING AND DATING
 SAID DRAWINGS.
  
 6) PER R301. THE FOLLOWING DESIGN CRITERIA IS REQUIRED
 ON THE CONSTRUCTION DOCUMENTS SUBMITTED FOR PERMIT,
 BUILDINGS AND STRUCTURES, AND ALL PARTS THEREOF, SHALL
 BE CONSTRUCTED TO SAFELY SUPPORT ALL LOADS, INCLUDING
 DEAD LOADS, LIVE LOADS, ROOF LOADS, FLOOR LOADS AND
 WIND LOADS AS PRESCRIBED BY THIS CODE. THE CONSTRUCTION
 OF BUILDINGS AND STRUCTURES SHALL RESULT IN A SYSTEM
 THAT PROVIDES A COMPLETE LOAD PATH CAPABLE OF
 TRANSFERRING ALL LOADS FROM THE POINT OF ORIGIN THROUGH
 THE LOAD-RESISTING ELEMENTS TO THE FOUNDATION.
  
 7) INDICATE THE TYPE OF CONSTRUCTION OF THE BUILDING
 PER 2004 FBC CHAPTER 6 AND TABLE 601. THIS INFORMATION
 IS REQUIRED FOR PLAN REVIEW TO DETERMINE THE TYPE OF
 MATERIALS WHICH ARE ALLOWED IN THE BUILDING.
  
 8) FBC 106.1.1CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISION OF
 THE CODE AND RELEVANT LAWS. WHICH AREA OF THE PROJECT
 WILL RECEIVE THE WOOD FLOORS? A FRAMING DETAIL IS
 REQUIRED SHOWING THE STUD SPACING ALL MATERIALS TO
 CONSTRUCT THE NEW AND INFILL WALLS.
  
 9)WILL BOTH BATHROOMS BE DEMOED AND REBUILT WITH ALL
 NEW MATERIALS OR ONLY PORTIONS OF THE BATHROOM WILL BE
 DEMOED? STATE AND SHOW CLEARLY THE WORK TO BE DONE IN
 EACH BATHROOM INCLUDING THE BACKER BOARD AT THE SHOWER
 AND WET AREAS.
  
 NOTE:OWNER NEEDS TO PROVIDE PROOF OF OWNER-SHIP. A
 DIFFERENT OWNER IS SHOWN THE PROPERTY APPRAISER
 WEB-SITE. A CBC CONTRACTOR CANNOT DO ANY STRUCTURAL
 WORK INCLUDING FLOOR/CEILING PENETRATIONS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-05-23 Cont ID  
Sent By btrobaug Date 2008-05-23 Time 11:04 Rev Time 0.00
Received By btrobaug Date 2008-05-23 Time 10:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-05-15 Cont ID  
Sent By btrobaug Date 2008-05-15 Time 14:53 Rev Time 0.00
Received By btrobaug Date 2008-05-15 Time 14:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-04-25 Cont ID  
Sent By btrobaug Date 2008-04-25 Time 14:51 Rev Time 0.00
Received By btrobaug Date 2008-04-25 Time 14:41 Sent To  
Notes
2008-04-25 14:51:01 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC CHAPTER 1AS AMENDED AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 1} ELECTRICAL PLANS INDICATING THE SCOPE OF WORK MUST
 BE SUBMITTED WITH THE APPLICATION. 106.1 FBC AS
 AMENDED.
  
 2} THE DESIGN PROFESSIONAL OR OWNER MUST ELECT THE
 LEVEL OF ALTERATION PURSUANT TO SECTIONS 303, 304 AND
 305 OF THE EXISTING BUILDING CODE. PLEASE DECLARE SAME
 ON THE PLAN.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-05-29 Cont ID  
Sent By mawillia Date 2008-05-29 Time 12:52 Rev Time 0.00
Received By mawillia Date 2008-05-29 Time 12:47 Sent To  
Notes
2008-05-29 12:52:48*****APPROVED*****
  
  
 SINGLE PLAN SHEET A.0 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-05-20 Cont ID  
Sent By mwennerg Date 2008-05-20 Time 09:42 Rev Time 0.00
Received By mwennerg Date 2008-05-20 Time 09:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-04-28 Cont ID  
Sent By mwennerg Date 2008-04-28 Time 15:06 Rev Time 0.00
Received By mwennerg Date 2008-04-28 Time 15:06 Sent To  
Notes
2008-04-28 15:08:53***DENIED***
  
 1) PLANS DON'T CLEARLY ILLUSTRATE THE SCOPE OF WORK.
  
 2) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 3) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-22 Cont ID  
Sent By adarroug Date 2008-05-22 Time 16:11 Rev Time 0.00
Received By adarroug Date 2008-05-22 Time 16:11 Sent To  
Notes
2008-05-22 16:11:59TO "BOB"#11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-14 Cont ID  
Sent By adarroug Date 2008-05-14 Time 16:29 Rev Time 0.00
Received By adarroug Date 2008-05-14 Time 16:29 Sent To  
Notes
2008-05-14 16:29:35TO "BOB"#12--PLANS WERE MISPLACED AND LOCATED IN
 SAMANTHA'S IN-BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-05-01 Time   Rev Time 0.00
Received By adarroug Date 2008-04-22 Time 09:19 Sent To  
Notes
2008-04-22 09:19:17TO "BOB"#11

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-05-23 Cont ID  
Sent By tgordon Date 2008-05-23 Time 13:30 Rev Time 0.20
Received By tgordon Date 2008-05-23 Time 13:30 Sent To  
Notes
2008-05-23 13:30:52REPLACING EXISTING BATHROOM EXHAUST FANS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-05-21 Cont ID  
Sent By tgordon Date 2008-05-21 Time 09:56 Rev Time 0.20
Received By tgordon Date 2008-05-21 Time 09:56 Sent To  
Notes
2008-05-21 09:57:39REPLACING EXISTING BATHROOM EXHAUST FANS.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-06-02 Cont ID  
Sent By mperson Date 2008-06-02 Time 11:11 Rev Time 0.00
Received By mperson Date 2008-06-02 Time 11:11 Sent To PC
Notes
2008-06-02 11:32:12NOTE: LIKE FOR LIKE FIXTURE.

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-05-15 Cont ID  
Sent By mperson Date 2008-05-15 Time 15:38 Rev Time 0.00
Received By mperson Date 2008-05-15 Time 15:38 Sent To  
Notes
2008-05-15 15:39:13NOTE: LIKE FOR LIKE FIXTURE CHANGE OUT, NO CHANGES IN
 LAYOUT.

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-04-24 Cont ID  
Sent By mperson Date 2008-04-24 Time 14:30 Rev Time 0.00
Received By mperson Date 2008-04-24 Time 14:30 Sent To  
Notes
2008-04-24 14:39:39PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE SUBMITTED PLANS FAIL TO CLEARLY INDICATE THE
 SCOPE OF THE PLUMBING WORK. PLEASE CLEARLY INDICATE
 EXACTLY WHAT PLUMBING FIXTURES ARE BEING DEMOED ON THE
 EXISTING FLOOR PLAN AND WHAT PLUMBING FIXTURES ARE NEW
 ON THE PROPOSED NEW FLOOR PLAN. PER (W.P.B. AS AMENDED)
 SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS
 AND FBC PLUMBING SECTION 401.1 SCOPE.
  
 2. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-04-24 Cont ID  
Sent By choops Date 2008-04-24 Time 10:55 Rev Time 0.00
Received By choops Date 2008-04-24 Time 10:55 Sent To  
Notes
2008-04-24 10:55:31*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.