2008-05-01 15:12:25 | ** DENIEDREVIEW ** |
| |
| **** IMPORTANT**** |
| PLEASE SEE COMMENTS BELOW: AS THERE IS INFORMATION, |
| DOCUMENTS, PLANS ETC WHICH ARE NOT SUBMITTED SOME ITEMS |
| FOR CODE COMPLIANCE CAN NOT BE REVIEWED AT THIS TIME. |
| PLEASE SEE THE LIST OF COMMENT BELOW BASED ON PLANS AND |
| DOCUMENTS WHICH WERE SUBMITTED. IT IS IMPORTANT TO |
| UNDERSTAND THAT DUE TO MUCH NEED FOR CHANGES FOR CODE |
| COMPLIANCE AND ITEMS WHICH CAN NOT BE REVIEWED THERE |
| MAY VERY WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW |
| WHICH CAN NOT BE MADE AT THIS TIME. |
| |
| 1) NOTE: PLEASE SEE THE PLANS SUBMITTED SHALL CONTAIN |
| THE LATEST ADOPTED CODES UNDER THE FLORIDA BUILDING |
| CODE ALONG WITH STATUTORY ADOPTED CODES. PLEASE SEE THE |
| FOLLOWING SHALL BE STATED ON PLANS. SOME CODES BELOW |
| ARE BEING REQUESTED TO BE STATED AND SHOWN ON |
| ELECTRICAL AS WELL AS COVER SHEETS. |
| 2004 FBC W/2007 |
| 2003 NFPA-101 |
| 2002 NFPA-72 |
| 2003 NFPA-20 |
| 2005 NFPA-70 |
| |
| PLEASE KNOW SOME SHEETS REFERENCE A FIRE PUMP AS NOTED |
| ON E6.05 SEE NOTES WITH RESPECT TO ANY FIRE PUMP. |
| PLEASE SEE THERE ARE SEVERAL SHEETS IN WHICH CODES ARE |
| BEING REFLECTED FROM THE 1999 NFPA-70 (NEC). |
| FOR EXAMPLE: |
| PLEASE SEE E0.03 AND 0.04, NOTES FOR GROUNDING IS |
| STATING 250.26 FOR SEPARATELY DERIVED SYSTEMS. THIS |
| CHANGED IN THE 2002 AND 2005 NEC. |
| PLEASE SEE THESE SAME SHEETS FOR NOTES ON WIRING WHICH |
| REFLECTS 370.20/21 HOWEVER THIS IS NO LONGER IN EFFECT |
| FOR EQUIPMENT AS STATED. THE 2002 AND 2005 WERE BOTH |
| CHANGED AND THE SECTIONS 370 OF THE NEWER CODES |
| ACTUALLY REFLECT THE CABLEBUS. |
| ** THE IS ONLY A COUPLE OF EXAMPLES AND IS NOT AN |
| EXHAUSTED LIST OF LOCATIONS. THIS IS GIVEN AS A BENEFIT |
| ONLY AND IS IN NO WAY ALL POSSIBLE LOCATIONS. |
| |
| |
| 2) NOTE: PLEASE BE SURE THE ADDRESS TO THE LOCATION OF |
| THIS PROJECT IS LISTED ON ALL TITLE BLOCKS ON ALL |
| SHEETS. |
| PLEASE SEE FAC 61G1-16.004, 61G15-23.002, FBC ADMIN |
| SECTION 106.5. |
| |
| 3) NOTE: PLEASE SEE THE COLOR CODING SHOWN ON E0.03 |
| SHALL BE BROWN, PURPLE AND YELLOW FOR 277/480V |
| SYSTEMS. |
| ORANGE AS STATED IN NEC 110.15 IS ONLY FOR A |
| *HIGH-LEG*. THE 277/480V IS NOT A HIGH-LEG. |
| PLEASE KNOW AS THE NEC DOES NOT PROVIDED COLOR CODING |
| FOR THIS PARTICULAR SYSTEM THE CITY OF WEST PALM BEACH |
| ALONG WITH ALL OF PALM BEACH COUNTY HAD TECHNICAL |
| AMENDMENTS WHICH WERE IN EFFECT FOR MORE THAN 30 YEARS. |
| EVEN THOUGH THIS TECHNICAL AMENDMENT IS NO LONGER IN |
| EFFECT IN KEEPING WITH COORDINATION, SAFETY AND |
| CONTINUITY OF OTHER WIRING WHICH ALREADY EXISTS IN THIS |
| AHJ PLEASE ADJUST. |
| 90.4 |
| |
| 4) NOTE: PLEASE SEE E6.05 WHICH SHOWS GROUNDING DETAIL |
| WHICH MENTIONS TO FIRE PUMP YET NO FIRE PUMP, |
| ELECTRICAL FOR FIRE PUMP ETC WAS LOCATED ON ANY OTHER |
| SHEET(S). |
| IF A FIRE PUMP IS INDEED GOING TO BE INSTALLED PLEASE |
| SUBMIT ALL INFORMATION INCLUDING MANUFACTURES SPECS/CUT |
| SHEETS FOR SUCH SYSTEM/UNIT. |
| PLEASE SEE 695 OF NFPA-70 AND ALL OF 2003 NFPA-20. |
| |
| 5) NOTE: PLANS ARE SPECIFICALLY CALLING FOR A *LIFE |
| SAFETY* AND *EMERGENCY* TRANSFER SWITCHES YET THE PLANS |
| DO NOT SHOW ANY GENERATOR. |
| THERE IS NO ELECTRICAL ON THE EMERGENCY SIDE ON EITHER |
| OF THE TRANSFER SWITCHES. IF THIS IS A TRUE LIFE SAFETY |
| REQUIRED SYSTEM UNDER 700 OR 701, THEN THE GENERATOR |
| AND ALL OTHER REQUIRED SHALL BE IN THE DESIGN FOR |
| MINIMUM CODE COMPLIANCE UNDER NFPA-101, 20, 110, 70 |
| ETC. |
| PLEASE KNOW AS NO INFORMATION, SPECS, MANUFACTURES CUT |
| SHEETS, ETC WAS SUBMITTED NO REVIEW OF *MINIMUM* CODE |
| COMPLIANCE CAN BE DONE AT THIS TIME. IF THERE IS A |
| LEGALLY REQUIRED SYSTEM OR LIFE SAFETY SYSTEM, PLEASE |
| IDENTIFY AND INCLUDE ALL FOR MINIMUM CODE COMPLIANCE. |
| IF LOADS ARE ONLY GOING TO BE OPTION STAND-BY THEN |
| PLEASE ADJUST ALL PLANS ETC FOR CODE COMPLIANCE. PLEASE |
| CAREFULLY REVIEW NEC 700,701 AND 702 FOR ACTUAL LOADS. |
| *** IMPORTANT** |
| PLEASE KNOW IF A GENERATOR IS GOING TO BE INSTALLED THE |
| PLANS FOR ALL OTHER TRADES SHALL BE REVISED TO INCLUDE |
| ANY SUCH UNIT. |
| PLEASE BE SURE TO INCLUDE ELEVATIONS ON |
| SITE/BUILDING/STRUCTURAL SHEETS. |
| PLEASE BE SURE TO INCLUDE ON SITE PLANS FOR |
| CIVIL/ZONING REVIEWS. |
| PLEASE BE SURE TO INCLUDE SCREENING AS REQUIRED BY |
| ZONING. |
| PLEASE BE SURE TO INCLUDE STRUCTURAL SLAB DETAILS FOR |
| UNIT, TIE DOWNS ETC. |
| PLEASE BE SURE TO INCLUDE SIZE OF FUEL TANK AS |
| DEPENDING ON SIZE THERE MAY BE NEEDS FOR REVIEW AND |
| STAMP BY DERM. |
| |
| THE ITEMS LISTED ABOVE ARE NOT AN EXHAUSTED LIST AS |
| THERE WILL BE COMMENTS FROM OTHER TRADES. THESE NOTES |
| WILL BE FORWARDED TO OTHER TRADES. |
| PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR |
| BOTH TRANSFER SWITCHES. 90.7, 110.3, 700, 701, OR 702. |
| FBC 106.3.5.1.2, 106.1.2 |
| |
| 6) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED. |
| PLEASE KNOW AS THE BUILDING IS NOT BEING DONE AS A |
| WHOLE BUILDING AND STILL INCLUDED SHELL SPACES METHOD |
| *A* MAY NOT BE USED. |
| PLEASE SEE 13-400.3.B, 13-400.3.C, 13-101.1.3, |
| 13-101.1.6 ETC. |
| PLEASE KNOW EVEN AS METHOD *A* WAS SUBMITTED IN THE |
| INFORMATION SHOWN ON THE INPUT DATA REPORT AND |
| CALCULATIONS DOES NOT CORRELATE WITH PLANS. |
| PLEASE KNOW THE INPUT DATA REPORT WILL BE NOTED AS IDR |
| FOR REMAINDER OF THIS COMMENT. |
| PLEASE KNOW THAT ALL INFORMATION ON PLANS SHALL |
| COORDINATE WITH THE IDR. ALL COMPONENTS OF THE BUILDING |
| FOR ENERGY EFFICIENCIES SHALL BE INCLUDED. SOME |
| EXAMPLES WILL BE GIVEN BELOW FOR ITEMS WHICH ARE |
| MISSING |
| FOR EXAMPLE: |
| PLEASE SEE THE IDR WHICH ONLY SHOWS A TOTAL OF FOUR |
| LIGHT FIXTURES. HOW IS THIS POSSIBLE WHEN THE IDR |
| CLEARLY REQUIRES THE TYPES OF LUMINAIRES, THE NUMBER OF |
| *EACH* OF THOSE LUMINAIRES, THE WATTAGE ON EACH OF |
| THOSE LUMINAIRIES ETC. |
| BASED ON THE IDR SUBMITTED THIS DOES NOT MEET THE |
| *MINIMUM* REQUIRED. |
| FOR EXAMPLE: |
| PLEASE ONCE AGAIN SEE THE IDR WHICH SHOWS ONLY 16-42 |
| WATT FIXTURES. HOW IS THIS POSSIBLE WHEN THE PLANS |
| CLEARLY SHOW THE *Q* FIXTURE ALONE BEING 75W. PLEASE |
| KNOW THAT *ALL* EXTERIOR LIGHTING IS REQUIRED BY CODE |
| TO BE FIGURED INTO THE IDR FOR EXTERIOR CALCULATIONS |
| AND ALLOWANCES. |
| THE FIXTURES ON THE FIXTURE LEGEND ALSO INCLUDE OTHER |
| EXTERIOR LIGHTS HOW THESE ARE NOT SHOWN. |
| |
| ** THIS IS ONLY TWO EXAMPLES. ONE FOR INTERIOR AND ONE |
| FOR EXTERIOR AND THIS IS NOT AN EXHAUSTED LIST. THESE |
| EXAMPLES ARE GIVEN AS A BENEFIT ONLY AND ARE NO WAY ALL |
| ITEMS ON THE IDR WHICH DO NOT COORDINATE WITH THE |
| SUBMITTED PLANS. |
| ** PLEASE SEE COMMENTS FROM OTHER TRADES AS THERE ARE |
| OTHER BUILDING COMPONENTS WHICH DO NOT COORDINATE. |
| PLEASE SEE SECTIONS NOTED ABOVE ALONG WITH 13-415.2, |
| 13-415.2.ABC.1.1, .1.1, AND .1.3. (ETC) |
| |
| ** AS THERE ARE SEVERAL ITEMS NOT YET COMPLETE ON PLANS |
| THERE MAY VERY WELL BE ADDITIONAL COMMENTS ON THE |
| FOLLOWING REVIEW. |
| |
| 7) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND |
| .1.4. |
| PLEASE SUBMIT MORE INFORMATION ON PLANS FOR LIGHTING |
| CONTROLS. THERE IS A NOTE ON E0.01 WHICH STATES ALL |
| LIGHTING SHALL MEET CHAPTER 13, HOWEVER QUOTING THE |
| CODE IN LIEU OF ACTUAL MINIMUM DESIGN IS NOT |
| PERMITTED. |
| PLEASE SEE AS NO SITE PARKING LOT LIGHTING WAS SHOWN ON |
| PLANS COMPLIANCE WITH .1.4 AS NOTED ABOVE CAN NOT |
| VERIFIED. ONCE PLANS ARE COMPLETE FOR ALL LIGHTING |
| REVIEW OF ALL SYSTEMS ETC WILL BE REVIEWED. |
| PLEASE SEE SOME EXAMPLES WILL BE GIVEN BELOW HOWEVER |
| THESE ARE IN NO WAY AN EXHAUSTED LIST. |
| FOR EXAMPLE: |
| PLEASE SEE SEVERAL OUTSIDE OFFICES WHICH APPEAR TO SHOW |
| A STANDARD LIGHT SWITCH. HOW DOES THIS DEVICE WORK AS |
| AN OVER RIDE OR WITH THE SYSTEM AS PROPOSED? |
| FOR EXAMPLE: |
| PLEASE SEE SECTIONS OF CODES NOTED AS EACH FLOOR IS |
| REQUIRED TO CONTAIN A SEPARATE SYSTEM IF LIGHTING |
| CONTROL PANELS ARE TO BE INSTALLED. |
| FOR EXAMPLE: |
| PLANS NOTE THAT ALL LIGHTING SHALL BE TURNED OFF AND |
| CODE DOES REQUIRE THIS. PLEASE VERIFY LIGHTING CONTROLS |
| IN STAIRS AND OTHER LOCATIONS WHICH DO NOT APPEAR TO |
| SHOW ANY CONTROLS. |
| PLEASE SEE LIFE SAFETY CODE 101, 7.8.1.2.2 AND FBC |
| 1016.1 FOR REQUIRED FAIL SAFE ON FOR EGRESS LIGHTING. |
| FOR EXAMPLE: |
| PLEASE KNOW THERE IS NOTHING IN THE CODE WHICH PERMITS |
| NIGHT LIGHTS. THIS AHJ WILL PERMIT SOME NIGHT LIGHTS |
| FOR SECURITY AS LONG AS LEVEL DOES NOT EXCEED 1 FT |
| CANDLE AVG ON EGRESS PATHS. |
| FOR EXAMPLE: |
| PLEASE SEE NO OUTSIDE LIGHTING AND CONTROLS SHOWN FOR |
| OTHER FIXTURES. SOME FIXTURES ON BUILDING ARE NOTED AS |
| ON PHOTO-SENSOR HOW NOT ALL. THERE IS A LIGHTING |
| CONTACTOR DETAIL HOWEVER NO ALL LIGHTING LISTED. |
| |
| AS NOTED THIS IS NOT AN EXHAUSTED LIST AND IS GIVEN AS |
| A BENEFIT ONLY. |
| |
| 8) NOTE: PLEASE SUBMIT COMPLETED LOAD CALCULATIONS FOR |
| PANELS AND SERVICE. |
| NEC 220, 220.12, 220.14, 220.42, 220.44 ETC |
| PLEASE SEE THAT ALL CONTINUOUS LOADS SHALL BE SHOWN AT |
| 125%. 215.3, 230.42 |
| |
| 9) NOTE: PLEASE SEE THAT THE LOCATION OF THE MAIN FOR |
| THE BUILDING IS NOT ACCEPTABLE TO THIS AHJ. THE |
| LOCATION OF THE MAIN IS NOT LOCATED AT THE NEAREST |
| POINT OF ENTRANCE IN AN EMERGENCY. FIRE DEPARTMENT |
| PERSONNEL MUST HAVE A QUICK AND READY ACCESS TO THE |
| MAIN LOCATION WITHOUT A SUBSTANTIAL TRAVEL DISTANCE |
| THROUGH A BUILDING WHICH MAY BE ON FIRE. |
| PLEASE RELOCATED ACCESS, ADD ACCESS, ADD MAIN ETC. THIS |
| MAY BE GONE OVER WITH THIS AHJ. |
| 230.70,71, 72, 76, 79 ETC |
| |
| 10) NOTE: PLEASE SEE 110.26C2 AS THE DOOR SWING ON THE |
| MAIN ELECTRICAL ROOM SHALL NOT SWING IN. |
| THE DOOR IS REQUIRED TO SWING OUT AND IS REQUIRED TO |
| CONTAIN PANIC HARDWARE ETC. |
| PLEASE KNOW THE ROOM, EQUIPMENT; DOOR ETC WILL ALL |
| DEPEND ON DESIGN TO COMPLY WITH NOTE #9 ABOVE. IN ANY |
| CASE 1200AMP EQUIPMENT WILL BE REQUIRED TO CONTAIN |
| DOOR(S) WITH OUT-SWING. |
| |
| 11) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR |
| EGRESS STAIRS UNDER NORMAL AND EMERGENCY CONDITIONS. |
| PLEASE SE NFPA-101 7.8.1.3, 7.9.2.2 |
| FAC 61G15-33.004 |
| |
| 12) NOTE: PLANS CONTAIN A NOTE ON RISER FOR GF |
| PROTECTION OF MAIN HOWEVER PLEASE BE SURE TO INCLUDE |
| SPECIFIC INFORMATION ON THE MDP/MAIN. |
| 240.13, 230.95. |
| PLEASE KNOW IF THERE ARE ANY REQUIRED LIFE SAFETY |
| SYSTEMS, SELECTIVE COORDINATION PER 240.13. |
| |
| 13) NOTE: PLEASE SEE RISER WHICH SHOWS 800AMP OVER |
| CURRENT PROTECTION ON PANEL 1-HEQ WHICH IS A 400AMP |
| PANEL. HOW IS THIS POSSIBLE? |
| 110.9, 90.4, 240.4 ETC |
| |
| 14) NOTE: PLEASE SEE RISER AND PANEL SCHEDULES AS ALL |
| OF THESE PANELS ON THE SECONDARY SIDE OF THE |
| TRANSFORMERS REQUIRE MAINS. |
| THERE ARE SEVERAL CODE SECTIONS AND SOME EXAMPLES OF |
| WHICH PANELS ARE GIVEN BELOW. |
| 1L1, |
| 1LEQ, |
| 1LLS. ETC |
| PLEASE SEE 240.21, 240.4, 310.16, 408.36 ETC |
| THIS IS NOT AN EXHAUSTED EXAMPLE. |
| |
| 15) NOTE: PLEASE SEE THAT ALL CONDUCTORS ON THE |
| SECONDARY SIDE OF TRANSFORMER SHALL TERMINATE IN OVER |
| CURRENT PROTECTION AS NOTED ABOVE IN NOTE #14. THESE |
| CONDUCTORS SHALL ALSO BE RATED FOR THAT OCP. |
| FOR EXAMPLE: |
| PLEASE SEE THE CONDUCTORS GOING INTO *1L1* WHICH ARE |
| SHOWN AS 500MCM. THESE CONDUCTORS PER 110.14, 110.3, |
| AND 310.16 ARE ONLY RATED FOR 380AMPS. |
| IN THIS PARTICULAR SCENARIO YOU MAY NOT GO TO THE NEXT |
| SIZE UP WHEN THE OCP LISTED PER 240.6 DOES NOT |
| COORDINATE WITH THE CONDUCTOR RATING. |
| MUST MEET OR EXCEED OCP ON THE SECONDARY SIDE. (MIN |
| 600MCM) |
| |
| 16) NOTE: PLEASE BE SURE TO COMPLETE NOTES ON PLANS PER |
| 13-413.1.ABC.2.1 AND .2.2. |
| THE NOTES ON ELECTRICAL SHEET COVER PAGE DOES PARTIALLY |
| LIST THIS HOWEVER NOT ALL. |
| PLEASE KNOW THIS WAS CONFIRMED WITH DCA/FBC AS THE |
| EXACT WORDING AS LISTED IN THE CODE WAS THE INTENT TO |
| HAVE LISTED ON PLANS. |
| |
| 17) NOTE: PLEASE SEE PANELS *1L1 AND 1L12* ON RISER |
| APPEARS TO BE SHOWN AS A TWO SECTION PANEL HOWEVER PER |
| THE PANEL SCHEDULE THESE ARE TWO SEPARATE PANELS AND |
| EACH PANEL DOES NOT CONTAIN THE SAME PANEL RATING. ONE |
| IS LISTED AS 400AMP AND THE OTHER AS 225AMP. PLEASE |
| COORDINATE AND ADJUST. |
| 110.3,90.7 ETC |
| FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND |
| COORDINATION. |
| |
| 18) NOTE: PLEASE SUBMIT COMPLETE PLANS FOR NEW OR |
| EXISTING SITE LIGHTS. |
| PLANS MENTION THIS HOWEVER AT THIS TIME THESE CAN NOT |
| BE CONFIRMED. |
| PLEASE SEE NOTES ABOVE WITH RESPECT TO LIGHTS, |
| CALCULATIONS ETC. |
| FBC 106.3.5.1.2 |
| |
| 19) NOTE: PLEASE SEE SITE ELECTRICAL PLANS SPECIFICALLY |
| CALL FOR A GROUND RING AND TO SEE DETAIL ON E6.05 YET |
| E6.05 DOES NOT SHOW ANY GROUND RING AS PART OF THE |
| GROUNDING ELECTRODE SYSTEM DETAIL. |
| PLEASE VERIFY ?? |
| 250.50 |
| FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND |
| COORDINATION. |
| |
| 20) NOTE: PLEASE VERIFY SERVER ROOM. IS THIS AN IT ROOM |
| AS DEFINED IN NFPA-75, NFPA-70? |
| PLEASE SEE 645.1 AND .4. |
| PLANS SHOW RATED WALLS, FIRE DAMPERS, A/C , FM 200 |
| SYSTEM ETC HOWEVER NO SHUT OFF PER 645.10 WAS LOCATED |
| ON PLANS. |
| PLEASE KNOW THERE ARE SEVERAL UNANSWERED QUESTIONS WITH |
| RESPECT TO THIS ROOM. |
| |
| 21) NOTE: PLEASE SEE NFPA-70 620.23 FOR REQUIRED |
| DEDICATED CIRCUITS IN MACHINE ROOM. |
| FOR EXAMPLE: |
| PLEASE SEE THE LIGHTING CIRCUIT FEEDING THIS ROOM |
| CURRENTLY ALSO FEEDS SEVERAL OTHER LIGHTING FIXTURES |
| OUTSIDE OF THIS ROOM WHICH IS NOT PERMITTED BY CODE. |
| PLEASE KNOW THIS IS NOT A NEW CODE. PLEASE ADJUST |
| PLANS. |
| |
| 22) NOTE: PLEASE SEE 620.24 WHICH REQUIRE DEDICATED |
| CIRCUITS FOR PIT/HOIST-WAY LIGHTS AND RECEPTACLES. |
| PLEASE SEE PLANS AS THE CIRCUIT WHICH FEEDS THE PIT GFI |
| WHICH IS *1L1-30* ALSO FEEDS MECHANICAL ROOM |
| RECEPTACLES, RECEPTION AREA ETC. |
| PLEASE ADJUST; THIS IS NOT A NEW CODE. |
| |
| 23) NOTE: PLEASE SEE THE ELEVATOR MACHINE ROOM PER FBC |
| 3006.2 IS REQUIRED TO CONTAIN SEPARATE CONDITIONING. |
| PLEASE SEE COMMENTS FROM MECHANICAL REVIEWER AS THIS |
| WILL AFFECT ELECTRICAL PLANS AS NOTED. |
| ** THIS IS BEING GIVEN FOR INFORMATION ONLY. |
| |
| 24) NOTE: PLEASE SEE CONDUCTORS ON RISER FOR |
| TRANSFORMER *1TN* WHICH SHOWS 200AMP OCP ON MDP ON 1/0 |
| CONDUCTORS WHICH ARE ONLY RATED FOR 150AMPS PER |
| 310.16. |
| PLEASE CORRECT AND ADJUST. |
| THIS IS NOT WHAT IS SHOWN ON MDP SCHEDULE. MDP SCHEDULE |
| INDICATES 150AMP BREAKER AND NOT 200AMP. |
| FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION. |
| |
| 25) NOTE: PLEASE BE SURE TO COMPLETE THE CERTIFICATION |
| SHEETS ON THE SUBMITTED ENERGY CALCULATIONS. |
| THE COVER SHEET WAS SIGNED, DATED AND SEALED HOWEVER |
| THIS SHOULD BE ON THE CERTIFICATION SHEETS. |
| PLEASE ALSO SEE OTHER INFORMATION REQUIRE ON THESE SAME |
| SHEETS SUCH AS OWNER/AGENT SIGNATURE IS REQUIRED. FBC |
| 13-103.1.1.1, FAC 61G15-23.002 |
| |
| 26) NOTE: PLEASE BE SURE TO STATE ALL MAXIMUM TIMES ON |
| OVER RIDE DEVICES. PLEASE SEE THE LOCATIONS OF EACH |
| OVER RIDE SHALL BE LOCATED SO THE OCCUPANT CAN VISUALLY |
| SEE THE LIGHTING IN WHICH THEY ARE CONTROLLING. THERE |
| ARE EXCEPTIONS ON THE CODE HOWEVER NO INFORMATION COULD |
| BE LOCATED ON PLANS ON HOW *PILOTS/INDICATORS LIGHTS* |
| WILL BE USED OR INSTALLED. |
| PLEASE SEE 13-415.1.ABC.1.1, .1.2. |
| |
| 27) NOTE: PLEASE SEE SYMBOL LEGEND MENTIONS THE USE OF |
| WHAT APPEARS TO BE A SPRING WOUND TIMER FOR SOME |
| LOCATIONS. |
| PLEASE SEE FBC 11-4.27.4 WHICH DOES NOT PERMIT THE USE |
| OF THESE DEVICES. |
| THIS MAY ALSO BE LIMITED TO SOME LOCATIONS AS PERMITTED |
| BY CODE. |
| |
| 28) NOTE: PLEASE SUBMIT AND PROVIDE AN ENLARGED |
| ELECTRICAL ROOM PLAN TO SCALE FOR THE MAIN ELECTRICAL |
| ROOM. |
| BASED ON THE EQUIPMENT SHOWN AND MINIMUM CLEARANCES |
| REQUIRED IN 110.26 THERE IS CONCERN OVER THE SIZE OF |
| THE ROOM AND EQUIPMENT AS SHOWN. |
| PLEASE SEE MANUFACTURES MINIMUM CLEARANCE FOR |
| TRANSFORMER, VENTILATION ETC. |
| PLEASE SEE 110.26, 450.9, 450.13, 450.21 ETC. |
| |
| 29) NOTE: PLEASE SEE SHEET E1.03 WHICH APPEARS TO USE A |
| SQUARE BOX WITH A C INSIDE AS ONE OF THE SYMBOLS LOCATE |
| AT DOOR. THIS SYMBOL ON E0.02 MENTIONS THIS IS A |
| LIGHTING CONTACTOR. WHAT IS THIS? |
| FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND |
| COORDINATION. |
| |
| 30) NOTE: PLEASE SEE SYMBOLS ON THE SHEET E1.03 AS |
| THERE ARE DEVICES WHICH APPEAR TO PARTIAL FIRE |
| DEVICES. |
| FOR EXAMPLE: |
| PLEASE SEE STAIR #2 WHICH SHOWS A PARTIAL FIRE DEVICE. |
| THIS IS ONE EXAMPLE: |
| |
| 31) NOTE: PLEASE INCLUDE MAXIMUM HEIGHT FOR ALL DEVICES |
| PER ADA 11-4.27. |
| PLEASE PLACE NOTE ON PLANS TO INCLUDE. |
| |
| 32) NOTE: PLEASE CLARIFY THE *SPECIAL OUTLET* IN THE |
| BREAK-ROOM KITCHEN AREA. 1L12, 8, 10,12. |
| FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND |
| COORDINATION. |
| |
| 33) NOTE: PLEASE PLACE NOTES ON PLANS FOR THE FOLLOWING |
| PER FBC SECTION 2704.1 WHICH REQUIRES BONDING OF METAL |
| FRAMING MEMBERS. |
| METAL FRAMING MEMBERS SHALL BE BONDED TO THE EQUIPMENT |
| GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY ENERGIZE |
| THE FRAMING AND BE SIZED IN ACCORDANCE WITH THE |
| NATIONAL ELECTRIC CODE, TABLE 250.122. FOR THE PURPOSE |
| OF THIS SECTION, A GROUNDED METAL OUTLET BOX ATTACHED |
| TO THE FRAMING SHALL BE PERMITTED. |
| |
| 34) NOTE: PLEASE KNOW DUE TO THE EXTENT OF THE COMMENTS |
| ABOVE, ONE ROLL OF PLANS ARE BEING RETAINED BY THIS |
| OFFICE ALONG WITH ONE SET OF ENERGY CALCULATION |
| SUBMITTED. |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |