Plan Review Details - Permit 08040386
Plan Review Stops For Permit 08040386
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-04-25 Cont ID  
Sent By jgomez Date 2008-04-25 Time 07:59 Rev Time 0.00
Received By jgomez Date 2008-04-25 Time 07:32 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-16 Cont ID  
Sent By jgomez Date 2008-04-16 Time 18:57 Rev Time 0.00
Received By jgomez Date 2008-04-16 Time 18:55 Sent To PC
Notes
2008-04-16 18:58:42RESIDENTIAL (R3) SHUTTERSINSTALLATION, BUILDING
 REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1-REVISE SHUTTER SPAN SHOWNON COLUMN #6 OF
 INSTALLATION SCHEDULE.SIZE SHOWN IS THE SAME SIZE AS
 THE OPENING SIZE.THIS DOESN'T WORK IF THE EDGE
 DISTANCE (TOP AND BOTTOM) IS 3.5" AS SHOWN ON
 INSTALLATION SCHEDULE COLUMN#8. REVISE AS REQUIRED.
  
 2-ANCHOR SPECIFIED ON COLUMN #10 OF INSTALLATION
 SCHEDULE IS A1/4 - 1 1/4 ELCO/BUILDEX HEX HEAD MAXI
 SET TAPCON.SEE PAGE 14 OF 26 OF STORM SHUTTERSFOR
 SPECIFIC TYPE OF TAPCON TO BE USED AND SPECIFIC MINIMUM
 EMBEDMENT REQUIRED FOR CONCRETE AND FOR CONCRETE BLOCK.
 REVISE AS REQUIRED.
  
 3- CLARIFY WHAT DOES PC/CB ON COLUMN #11 OF
 INSTALLATION SCHEDULE STANDS FOR.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-16 Cont ID  
Sent By jgomez Date 2008-04-16 Time 18:58 Rev Time 0.00
Received By jgomez Date 2008-04-16 Time 18:55 Sent To  
Notes
***NONE***