Plan Review Details - Permit 08040240
Plan Review Stops For Permit 08040240
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-02-11 Cont ID  
Sent By mwennerg Date 2009-02-11 Time 09:36 Rev Time 0.00
Received By mwennerg Date 2009-02-11 Time 09:36 Sent To  
Notes
2009-02-11 09:37:56REVISION DATED 1/20/09 FOR THE ADDITION OF LIVING UNIT
 SMOKE DETECTORS THAT WILL INITIATE A NOTIFICATION AT
 THE FIRE ALARM PANEL ONLY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-04-25 Cont ID  
Sent By mwennerg Date 2008-04-25 Time 10:56 Rev Time 0.00
Received By mwennerg Date 2008-04-25 Time 10:56 Sent To  
Notes
2008-04-25 11:06:54UL CERTIFICATION FOR CENTRAL STATION SERVICE MAY BE
 REQUIRED AT LATER TIME SHOULD FIRE SPRINKLER EQUIPMENT
 BE INSTALLED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-04-17 Cont ID  
Sent By mwennerg Date 2008-04-17 Time 12:47 Rev Time 0.00
Received By mwennerg Date 2008-04-17 Time 12:47 Sent To  
Notes
2008-04-17 13:22:04***DENIED***
  
 1) THE MANUFACTURER SPECIFICATION SHEETS IDENTIFY
 ACCESS CONTROL EQUIPMENT. THE DRAWINGS DO NOT APPEAR TO
 ILLUSTRATE EQUIPMENT. PLEASE CLARIFY AND PROVIDE
 INFORMATION IF APPLICABLE. IF EQUIPMENT IS PART OF THE
 SCOPE OF WORK, SEPARATE SHOP DRAWINGS AND PERMIT IS
 REQUIRED.
  
 2) PLEASE PROVIDE THE ACTUAL LANGUAGE WITH REGARD TO
 THE VOICE EVACUATION SYSTEM.
  
 3) IS THERE ANY EXISTING SMOKE MANAGEMENT SYSTEM IN
 THIS BUILDING?
  
 4) FIRE ALARM SHALL BE UL CERTIFICATED FOR CENTRAL
 STATION SERVICE. THE CERTIFICATE OR COPY OF SUCH WILL
 BE REQUIRED AT THE TIME OF TO THE FINAL INSPECTION.
  
 5) THE WORD SURVIVABILITY IS USED IN THIS SUBMITTAL.
 PLEASE VERIFY IF THE FIRE ALARM SYSTEM MEETS THE
 SURVIVABILITY REQUIREMENTS OF NFPA 72.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-01-30 Cont ID  
Sent By adarroug Date 2009-01-30 Time 12:17 Rev Time 0.00
Received By adarroug Date 2009-01-30 Time 12:17 Sent To FIRE
Notes
2009-01-30 12:17:26TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-18 Cont ID  
Sent By adarroug Date 2008-04-18 Time 11:40 Rev Time 0.00
Received By adarroug Date 2008-04-18 Time 11:40 Sent To FIRE
Notes
2008-04-18 11:40:31TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-17 Cont ID  
Sent By mwennerg Date 2008-04-17 Time 13:22 Rev Time 0.00
Received By mwennerg Date 2008-04-10 Time 09:10 Sent To  
Notes
2008-04-10 09:10:40TO "F" BOX