Plan Review Details - Permit 08040176
Plan Review Stops For Permit 08040176
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2008-04-24 Cont ID  
Sent By lursu Date 2008-04-24 Time 08:28 Rev Time 0.00
Received By lursu Date 2008-04-24 Time 08:28 Sent To  
Notes
2008-04-24 08:29:39SITE ADDRESS ASSIGNED AT THE STARTING POINT OF THE
 PROJECT AS 100 S FLAGLER DR ,WEST PALM BEACH, FL 33401
  
 QUESTIONS/COMMENTS:
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-05-08 Cont ID  
Sent By shill Date 2008-05-08 Time 17:43 Rev Time  
Received By shill Date 2008-05-08 Time 17:22 Sent To  
Notes
2008-05-08 17:44:20**PROVISO** PROVIDE REVIEW BY E.O.R. CH2M HILL
 SUBMIT REVISION OR LETTER, PIER DESIGNED AT 100PSF PER
 KEITH KNIGHT, PE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-24 Cont ID  
Sent By shill Date 2008-04-24 Time 08:30 Rev Time 0.00
Received By shill Date 2008-04-24 Time 07:53 Sent To  
Notes
2008-04-24 08:13:29****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FAC61G15-23.002.EITHER SIGN, SEAL, AND DATE THE SOIL
 BORING INFORMATION (CURRENTLY MARKED "FOR INFORMATION
 ONLY") OR REMOVE THEM FROM THE SET AND PROVIDE THE
 ORIGINAL SOIL BORING REPORT.
  
 2.PLEASE PROVIDE MORE INFORMATION REGARDING THE
 EXPECTED USE AND ANTICIPATED LIVE LOAD, FBC TABLE
 1607.1.THE CODE DOES NOT SPECIFICALLY HAVE A DESIGN
 CRITERIA FOR THIS USE, BUT IT SEEMS TO ACT AS A
 CORRIDOR, WHICH WOULD REQUIRE 100PSF (RATHER THAN 60PSF
 AS STATED ON G2).
  
 3.DECLARE GOVERNING CODE INCLUDING 2007
 REVISIONS/SUPPLEMENTS.
  
 4.DECLARE WIND DESIGN CRITERIA FBC1603.1.4.
  
 5.SHEET S3 STATES THAT HANDRAILS WILL BE DONE BY
 OTHERS (THEREFORE NOT INCLUDED ON THIS PERMIT).PLEASE
 SEE FBC1001.1, DESIGN OF MEANS OF EGRESS COMPONENTS
 SHALL BE CONTROLLED BY FBC CHAPTER 10 (GUARDRAIL,
 HANDRAIL).PROVIDE DESIGN CRITERIA FOR THE
 GUARDS/HANDRAIL, FBC1607.7, FBC1012, .NOTE THAT THE
 GUARD/HANDRAIL AS GRAPHICALLY DEPICTED DO NOT APPEAR
 CODE COMPLIANT.IF THIS IS TO BE INCLUDED ON A
 SEPARATE PERMIT, PLEASE NOTE THAT THE PERMIT WILL BE
 ISSUED WITH THE PROVISO THAT GUARD/HANDRAIL WILL COMPLY
 WITH THE STATED CODE SECTIONS.IF THIS IS NOT
 DESIGNER'S INTENT, PLEASE CONTACT ME TO DISCUSS OR
 REVISE THE PLAN ACCORDINGLY.
  
 6.SEE S1 AND S2; FOR THE FIXED PORTIONS OF GANGWAYS
 AS APPLICABLE (SLOPE >1:20), SHOW HANDRAIL EXTENSION
 DIMENSIONS FBC11-4.8.5.
  
 7. THIS IMPROVEMENT IS GOVERNED BY ADA TITLE II.
 PLEASE CONFIRM THAT DESIGNER HAS READ THIS DOCUMENT;
 HTTP://WWW.ACCESS-BOARD.GOV/RECREATION/GUIDES/BOATING.H
 TM.
  
 8. THE NORTH CLEMATIS WALKWAY DOES NOT SHOW GRADE.
 INFORMATION REGARDING ACCESSIBLE ROUTE CAN BE PROVIDED
 EITHER NOW OR ON A FUTURE PERMIT (PROVISO ITEM).

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2008-05-07 Cont ID  
Sent By rchokshi Date 2008-05-07 Time 13:14 Rev Time 0.00
Received By rchokshi Date 2008-05-07 Time 13:14 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-04-10 Cont ID  
Sent By rchokshi Date 2008-04-10 Time 14:38 Rev Time 0.00
Received By rchokshi Date 2008-04-10 Time 14:19 Sent To  
Notes
2008-04-10 14:36:19FAILED FOR FOLLOWING REASONS:
  
 1 PLEASE PROVIDE A COPY OF SFWMD PERMIT,, IF APPLICABLE
 TO THIS JOB OR SOME LETTER THAT YOU DO NOT NEED A
 PERMIT.
  
 2. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS, PLANSSHOULD SHOW THE POLLUTION PREVENTION
 METHOD AROUND PIERS PER FDEP BEFORE, DURING, AND AFTER
 CONSTRUCTIONS.
  
 PLEASE CONTINUE TO RESUBMIT ARMY CORP ENG PERMIT COPY &
 DEP PERMIT COPY UNTIL YOU GET PERMIT FROM US.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-05-12 Cont ID  
Sent By mcarsill Date 2008-05-12 Time 15:19 Rev Time 0.00
Received By mcarsill Date 2008-05-12 Time 15:19 Sent To  
Notes
2008-05-12 15:22:48PREVIOUS PLAN REVIEW NOTES IS APPLICABLE TO THE THE
 FLOATING DOCK INSTALLATION. FIXED PIER AND PILES AND
 PILE CAPS ONLY ARE PER THIS DRAWING. CONSULTATION
 OCCURRED WITH CONSTRUCTION SERVICES REGARDING THIS
 REVIEW.
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-05-12 Cont ID  
Sent By mcarsill Date 2008-05-12 Time 08:24 Rev Time 0.00
Received By mcarsill Date 2008-05-12 Time 08:05 Sent To  
Notes
2008-05-12 08:23:57THIS REVIEW WAS PERFORMED ON PLANS FOR TITLED "CITY
 COMMONS AND WATERFORNT DOCKS, NORTH CLEMATIS DOCK
 UTILITIES.
  
 1. IT DOES NOT APPEAR THAT THE PREVIOUS FIRE RESCUE
 PLANS REVIEW NOTES WERE ADDRESSED BY THESE DRAWINGS.
 PLEASE DISPLAY NEAREST FIRE HYDRANT.
  
 2. THE PORTABLE FIRE EXTINGUISHERS INDICATED ON THE
 PLANS NEED TO BE PROPERLY SERVICED TAGGED.
  
 3. THE REQUIRED SMOKING RESTRICTIONS AS INDICATED IN
 NFPA 303 IS NOT ADDRESSED BY THESE PLANS.
  
 4. THE REQUIRED STANDPIPE SYSTEM SHALL MEET THE
 REQUIREMENTS OF NFPA 303, THE STANDARD FOR MARINAS AND
 BOATYARDS. THE WET CLASS I STANDPIPE SYSTEM SHALL MEET
 THE REQUIREMENTS OF NFPA 14, THE STANDARD FOR THE
 INSTALLATION OF STANDPIPE, PRIVATE HYDRANT, AND HOSE
 SYSTEMS. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 INSTALLATION OF THE STANDPIPE SYSTEM. THE STANDPIPE
 SYSTEM WHEN INSTALLED SHALL BE PRESSURE TESTED ALONG
 WITH THE PROPOSED FIRE DEPARTMENT CONNECTION (FDC) TO
 ENSURE TIGHTNESS. THE HOSE VALVES SHALL BE EQUIPPED
 WITH 2 1/2 TO 1 1/2 REDUCERS. THE HOSE VALVES AND
 PIOING SHALL BE PROPERLY RESTRAINED.
  
 5. ALL ELECTRICAL SYSTEMS AND DEVICES SHALL COMPLY WITH
 NFPA 70, THE NATIONAL ELECRICAL CODE AND NFPA 303, THE
 STANDARD FOR MARINAS AND BOATYARDS.
  
 6. PLEASE INDICATE THE PORPOSED MEANS OF TRANSMITTING
 OF AN EMERGENCY AT THIS LOCATION. NFPA 303, REQUIRES
 THAT A MEANS TO REPORT AN EMERGENCY SHALL BE PROVIDED
 AND IF THIS MEANS IS A TELEPHONE IT SHALL NOT REQUIRE A
 COIN TO OPERATE.
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-04-25 Cont ID  
Sent By mwennerg Date 2008-04-25 Time 14:37 Rev Time 0.00
Received By mwennerg Date 2008-04-25 Time 14:37 Sent To  
Notes
2008-04-25 14:57:14***DENIED***
  
 1) IN ADDITION TO OTHER APPLICABLE CODES AND
 GOVERNMENTAL APPROVAL, WORK SHALL COMPLY WITH NFPA 303,
 STANDARD FOR MARINAS AND BOATYARDS AND ALL ASSOCIATED
 PIERS, DOCKS AND FLOATS.
  
 2) PLEASE INDICATE THE MAXIMUM HOSE LAY DISTANCE FROM
 THE FIRE APPARATUS. FIRE STANDPIPE SYSTEM SHALL BE
 REQUIRED IF THE DISTANCE EXCEEDS 150 FEET. IF THE SCOPE
 OF THIS WORK DOES NOT APPLY, PLEASE NOTE THIS
 REQUIREMENT FOR FUTURE REFERENCE WITH REGARD TO THE
 PROPOSED PIER AND GANGWAY, AND FLOATING DOCKS.
  
 3) PLEASE ILLUSTRATE THE CLOSEST FIRE HYDRANTS TO THIS
 PROJECT.
  
 4) PLEASE SEE BUILDING REVIEW COMMENT REGARDING GUARDS
 AND HANDRAILS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-06 Cont ID  
Sent By adarroug Date 2008-05-06 Time 10:52 Rev Time 0.00
Received By adarroug Date 2008-05-06 Time 10:52 Sent To  
Notes
2008-05-06 10:56:03TO "COMM" BD#41--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-25 Cont ID  
Sent By mwennerg Date 2008-04-25 Time 15:18 Rev Time 0.00
Received By mwennerg Date 2008-04-08 Time 10:48 Sent To  
Notes
2008-04-08 10:48:33TO "COMM" BD#11

Review Stop Z ZONING
Rev No 1 Status N Date 2008-04-21 Cont ID  
Sent By mflis Date 2008-04-21 Time 08:36 Rev Time 0.00
Received By mflis Date 2008-04-21 Time 08:36 Sent To  
Notes
2008-04-21 08:41:03ZONING REVIEW: N/A
  
 COMMENTS:
  
 1) COVER SHEET INDICATEDS "PRELIMINARY DRAWINGS. THESE
 DRAWINGS ARE NOT IN FINAL FORM..." CONFIRM THAT THESE
 ARE FINAL DRAWINGS FOR SUBMITTAL.
  
 2) CONFIRM HEIGHT OF SEAWALL AT EACH LANDING
 CONNECTION. NORTH CLEMATIS CONNECTION SEEMS TO INDICATE
 THE SEAWALL WILL NOT BE CUT DOWN. IS THIS CORRECT?
 SOUTH CLEMATIS CONNECTION INDICATES TOP OF SEAWALL TO
 BE 5'-0". PLEASE CONFIRM HEIGHTS FOR BOTH CONNECTIONS
 ARE CORRECT.
  
 3) ALL HANDRAILS AND GUARDRAILS PLANS AND DETAILS
 SHOULD BE SUBMITTED FOR REVIEW BY THE CITY. (THIS
 PERMIT INDICATES THEY WILL BE SUBMITTED BY OTHERS -
 CONFIRM THIS IS CORRECT).
  
 MATT FLIS - 822-1445