Plan Review Details - Permit 08040035
Plan Review Stops For Permit 08040035 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2008-04-10 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-04-10 |
Time |
13:30 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-04-10 |
Time |
13:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-04-10 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-04-10 |
Time |
13:36 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-04-02 |
Time |
09:40 |
Sent To |
PC |
|
Notes |
2008-04-02 09:44:08 | TO "BOB"#3 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2008-04-07 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-04-07 |
Time |
14:02 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2008-04-07 |
Time |
14:02 |
Sent To |
|
|
Notes |
2008-04-07 14:10:36 | ****************PROVISO**************** | | (A) SHEET 4 PLUMBING NOTE #16: AIR CHAMBERS ARE NOT | | APPROVED BY FBC-2004. | | PER FBC PLUMBING SECTION 604.9 WATER HAMMER. A | | WATER-HAMMER ARRESTOR SHALL BE INSTALLED WHERE | | QUICK-CLOSING VALVES ARE UTILIZED. | | | | (B) SHEET 5 WATER ISOMETRIC RISER: THERMAL EXPANSION | | CONTROL REQUIRED FOR THE WATER HEATER. | | 607.3.2 BACKFLOW PREVENTION DEVICE OR CHECK VALVE. | | WHERE A BACKFLOW PREVENTION DEVICE, CHECK VALVE OR | | OTHER DEVICE IS INSTALLED ON A WATER SUPPLY SYSTEM | | UTILIZING STORAGE WATER HEATING EQUIPMENT SUCH THAT | | THERMAL EXPANSION CAUSES AN INCREASE IN PRESSURE, A | | DEVICE FOR CONTROLLING PRESSURE SHALL BE INSTALLED. | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2008-04-02 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2008-04-02 |
Time |
10:36 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2008-04-02 |
Time |
10:36 |
Sent To |
|
|
Notes |
2008-04-02 10:37:29 | *ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE | | VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE | | IMPROVEMENT VALUE. |
|
|
|