Plan Review Details - Permit 08040031
Plan Review Stops For Permit 08040031
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-04-14 Cont ID  
Sent By shill Date 2008-04-14 Time 09:37 Rev Time 0.00
Received By shill Date 2008-04-14 Time 09:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-08 Cont ID  
Sent By shill Date 2008-04-08 Time 09:45 Rev Time 0.00
Received By shill Date 2008-04-08 Time 09:45 Sent To  
Notes
2008-04-08 09:49:34****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1)FOR THE FLAT ROOF, SELECT THE APPROVED ASSEMBLY YOU
 ARE USING.ALSO INDICATE WHICH FASTENER YOU ARE USING
 IF THE OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS.
  
 A POST-IT NOTE WAS PLACED ON PAGE 20, SYSTEM TYPE E2.
 THIS SYSTEM HAS A DESIGN PRESSURE LIMITATION OF -60;
 THEREFORE YOU WOULD NEED ENHANCED FASTENING FOR ZONE 3.
 ONLY THE SYSTEM ON PAGE 22, SYSTEM E4, DOES NOT REQUIRE
 ENHANCED FASTENING AND ENGINEERING AS THE DESIGN
 PRESSURE FOR THIS SYSTEM IS -112.5.
  
 2.)SEE PRODUCT LIMITATION #7.IF ENHANCED FASTENING
 IS REQUIRED, CALCULATIONS PREPARED BY AN ARCHITECT,
 ENGINEER, OR REGISTERED ROOF CONSULTANT REQUIRED FOR
 ENHANCED FASTENING.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-01 Cont ID  
Sent By shill Date 2008-04-01 Time 16:33 Rev Time 0.00
Received By shill Date 2008-04-01 Time 16:33 Sent To  
Notes
2008-04-01 16:39:46****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.THE NOA SUBMITTED CONTAINS A TYPO.THERE MAY BE
 ANOTHER MORE CURRENT NOA AVAILABLE, OR ENGINEERING MAY
 BE AVAILABLE FROM THE MANUFACTURER.
  
 2.THE ENHANCED FASTENING IS TO BE ROUNDED DOWN TO THE
 NEAREST INCH, SEE RAS117.THE ENGINEERING SPECIFIES
 4.5 INCHES.
  
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2008-04-01 Cont ID  
Sent By ssherman Date 2008-04-01 Time 15:30 Rev Time 0.00
Received By ssherman Date 2008-04-01 Time 15:30 Sent To  
Notes
2008-04-01 15:30:24HISTORICAL APPROVAL PER JILLIAN PAPA