Plan Review Details - Permit 08030728
Plan Review Stops For Permit 08030728
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-01-28 Cont ID  
Sent By rmcdouga Date 2009-01-28 Time 10:47 Rev Time 0.00
Received By rmcdouga Date 2009-01-28 Time 10:47 Sent To  
Notes
2009-01-28 10:49:15CONTRACTOR SUBMITTED PRODUCT APPROVALS FOR STORM PANELS
 AS REQUESTED IN WINDOW REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-01-21 Cont ID  
Sent By rmcdouga Date 2009-01-21 Time 11:03 Rev Time 0.00
Received By rmcdouga Date 2009-01-21 Time 11:02 Sent To  
Notes
2009-01-21 11:12:32STORM SHUTTERS ARE DENIED.
  
 THE REVISION TO CHANGE CHANGE FROM IMPACT TO NON-IMPACT
 WINDOWS IS OK. HOWEVER, THE PRODUCT APPROVALS THAT WERE
 SUBMITTED FOR THE STORM PANELS IS INCOMPLETE AND IS FOR
 THE 2001 CODE VERSION. SUBMIT STORM PANEL PRODUCT
 APPROVALS FOR THE 2004 FBC WITH INSTALLATION
 INSTRUCTIONS. SPECIFY ON THE INSTALLATION INSTRUCTIONS
 THE MOUNTING TYPE (IE. DIRECT MOUNT, H TRACK, ETC.),
 THE FASTENER TYPE AND FASTENER SPACING THAT WILL BE
 USED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-12-31 Cont ID  
Sent By rmcdouga Date 2008-12-31 Time 10:03 Rev Time 0.00
Received By rmcdouga Date 2008-12-31 Time 10:03 Sent To  
Notes
2008-12-31 10:06:07REVISED INSULATION TO ICYNENE SPRAY FOAM INSULATION.
 SUBMITTED ICC EVALUATION REPORT AND SIGNED AND SEALED
 LETTER AND DRAWING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-07-16 Cont ID  
Sent By rmcdouga Date 2008-07-16 Time 14:09 Rev Time 0.00
Received By rmcdouga Date 2008-07-16 Time 14:09 Sent To  
Notes
2008-07-16 13:35:10BUILDING PROVISO
  
 SPECIFY THE FASTENING OPTION AND DESIGN PRESSURE FOR
 THE GAF MODIFIED ROOFING SYSTEM FROM NOA 03-0501.02
 THAT WILL BE INSTALLED AND SUBMIT RAS 117 CALCULATIONS
 FOR THE ENHANCED FASTENING AT THE PERIMETER AND CORNER
 AREAS OF THE FLAT ROOF. WHEN THE ROOFING PERMIT IS
 APPLIED FOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-06-17 Cont ID  
Sent By rmcdouga Date 2008-06-17 Time 15:55 Rev Time 0.00
Received By rmcdouga Date 2008-06-17 Time 15:55 Sent To  
Notes
2008-06-17 15:56:552004 FBC W/2007 REVISIONS
 LEVEL 3 ALTERATIONS TO DETACHED GARAGE
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 2) THE SIGNED AND SEALED SOIL REPORT THAT WAS SUBMITTED
 IS INCOMPLETE. THE SIGNED AND SEALED CALCULATIONS AND
 LETTER SPECIFYING THE BEARING CAPACITY OF THE SOIL FROM
 CUTCHER & ASSOCIATES, INC. ARE MISSING. PLEASE SUBMIT
 TWO SIGNED AND SEALED COPIES. FBC 106.1.2 * CITY
 AMENDMENTS.
  
 3) THE NEW PLANS ARE REQUIRED TO BE REVIEWED AND
 STAMPED BY THE CITY HISTORIC PLANNERS.
  
 4) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE FLAT
 ROOF COVERING. SPECIFY THE APPROVED ASSEMBLY, THE
 FASTENING OPTION AND DESIGN PRESSURE THAT WILL BE
 INSTALLED. SUBMIT RAS 117 CALCULATIONS FOR ENHANCED
 FASTENING. FBC 106.1.2 * CITY AMENDMENTS.
  
 5) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 EXTERIOR SWING DOOR IS EXPIRED. SUBMIT TWO CURRENT
 PRODUCT APPROVALS FOR THE DOOR.
  
 6) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-28 Cont ID  
Sent By rmcdouga Date 2008-04-28 Time 17:36 Rev Time 0.00
Received By rmcdouga Date 2008-04-28 Time 17:36 Sent To  
Notes
2008-04-28 17:14:262004 FBC W/2007 REVISIONS
 LEVEL 3 ALTERATIONS TO DETACHED GARAGE
  
 DENIED BY BUILDING 2004 FBC 106.1.2* CITY AMENDMENTS.
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 2) A SIGNED, SEALED AND DATED COPY OF THE SOIL REPORT
 IS REQUIRED. SEE FS 471.
  
 3) SHOW COMPLIANCE WITH FBC R SECTION 704 INSPECTION
 FOR TERMITES IN ORDER TO PROVIDE FOR INSPECTION FOR
 TERMITE INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL
 COVERINGS AND FINAL EARTH GRADE ON THE EXTERIOR OF A
 BUILDING SHALL NOT BE LESS THAN 6 INCHES (152 MM).
  
 4) SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED
 GRADE .
 CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND
 ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT
 ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY
 VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM)
 ELSEWHERE.
  
 5)SHOW COMPLIANCE WITH R320.7 PROTECTION AGAINST
 DECAY AND TERMITES. CONDENSATE LINES AND ROOF
 DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT (305 MM)
 AWAY FROM THE STRUCTURE SIDEWALL, WHETHER BY
 UNDERGROUND PIPING, TAIL EXTENSIONS OR SPLASH BLOCKS.
 GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON ALL BUILDINGS
 WITH EAVES OF LESS THAN 6 INCHES (152 MM) HORIZONTAL
 PROJECTION EXCEPT FOR GABLE END RAKES OR ON A ROOF
 ABOVE ANOTHER ROOF.
  
 6)SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WIT H 1 /
 8 INCH (3.2 MM) MINIMUM TO ? INCH (6.4 MM) MAXIMUM
 OPENINGS.
  
 7) THE OPENING PRESSURES FOR THE EXTERIOR DOORS LOCATED
 IN WALL ZONE 5 ARE TOO LOW. PLEASE REVISE. SEE TABLE R
 301.2(2).
  
 8) THE WALL SECTIONS SPECIFY R-19 INSULATION IN THE
 EXTERIOR WALLS. THE WALLS ARE SPECIFIED AS 2 X 4 WHICH
 CAN ONLY ACCOMODATE R-11 INSULATION. PLEASE REVISE.
  
 9) TRUSS NOTE (9) ON SHEET A4 NEEDS TO BE REVISED TO
 COMPLY WITH SECTION R803.2.3.1 OF 2006 REVISIONS TO
 2004 FBC RESIDENTIAL CODE. WOOD STRUCTURAL PANEL
 SHEATHING SHALL BE FASTENED TO ROOF FRAMING WITH 8D
 RING-SHANK NAILS AT 6 INCHES ON CENTER AT EDGES AND 6
 INCHES ON CENTER AT INTERMEDIATE FRAMING. WHERE ROOF
 FRAMING WITH A SPECIFIC GRAVITY, 0.42 < G < 0.49 IS
 USED, SPACING OF RING-SHANK FASTENERS SHALL BE 4 INCHES
 ON CENTER IN NAILING ZONE 3 FOR 130 MPH OR GREATER
 DESIGN WIND SPEEDS IN ACCORDANCE WITH FIGURE R803.2.3.1
 .
  
 10) ON SHEET A4 MASONRY NOTES 5 AND 6 SPECIFY THE WRONG
 EDITIONS OF ACI 530, ASCE5, ASCE6, TMS402 AND TMS602.
 THE 2002 EDITION OF THESE STANDARDS ARE REFERENCED IN
 THE 2004 FBC. SEE CHAPTER 43 OF THE 2004 FBC
 RESIDENTIAL.
  
 11) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR WINDOWS,
 DOORS, OVERHEAD GARAGE DOORS, ROOF COVERING, CONNECTORS
 AND STORM PANELS AS REQUIRED BY DCA RULE 9B-72.
  
 12) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 13) NOTE: THE FLOOR PLAN SPECIFIES AN EGRESS WINDOW AND
 A TEMPERED GLASS WINDOW. BASED ON THE PLANS THAT WERE
 SUBMITTED, THESE WINDOWS ARE NOT REQUIRED TO BE EITHER.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-06-11 Cont ID  
Sent By btrobaug Date 2008-06-11 Time 12:38 Rev Time 0.00
Received By btrobaug Date 2008-06-11 Time 12:30 Sent To P
Notes
2008-06-11 12:38:59 
  
 TO SHORT TIME JOHN'S DESK./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-04-25 Cont ID  
Sent By btrobaug Date 2008-04-25 Time 14:36 Rev Time 0.00
Received By btrobaug Date 2008-04-25 Time 13:48 Sent To Z
Notes
2008-04-25 14:36:30 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC CHAPTER 1AS AMENDED.
  
 INDICATE COMPLIANCE WITH THE FOLLOWING ON THE PLAN.
 1} 230.70 GENERAL.
 MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN
 A BUILDING OR OTHER STRUCTURE FROM THE SERVICE-ENTRANCE
 CONDUCTORS.
  
 2} 225.32 LOCATION.
 THE DISCONNECTING MEANS SHALL BE INSTALLED EITHER
 INSIDE OR OUTSIDE OF THE BUILDING OR STRUCTURE SERVED
 OR WHERE THE CONDUCTORS PASS THROUGH THE BUILDING OR
 STRUCTURE. THE DISCONNECTING MEANS SHALL BE AT A
 READILY ACCESSIBLE LOCATION NEAREST THE POINT OF
 ENTRANCE OF THE CONDUCTOR
  
 3} 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S)
 OR BRANCH CIRCUIT(S)
 (A) GROUNDING ELECTRODE BUILDING(S) OR STRUCTURE(S)
 SUPPLIED BY FEEDER(S) OR BRANCH CIRCUIT(S) SHALL HAVE A
 GROUNDING ELECTRODE OR GROUNDING ELECTRODE SYSTEM
 INSTALLED IN ACCORDANCE WITH 250.50. THE GROUNDING
 ELECTRODE CONDUCTOR(S) SHALL BE CONNECTED IN ACCORDANCE
 WITH 250.32(B) OR (C). WHERE THERE IS NO EXISTING
 GROUNDING ELECTRODE, THE GROUNDING ELECTRODE(S)
 REQUIRED IN 250.50 SHALL BE INSTALLED.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-01-20 Cont ID  
Sent By adarroug Date 2009-01-20 Time 14:24 Rev Time 0.00
Received By adarroug Date 2009-01-20 Time 14:24 Sent To B
Notes
2009-01-20 14:24:46TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-12-19 Cont ID  
Sent By adarroug Date 2008-12-19 Time 10:05 Rev Time 0.00
Received By adarroug Date 2008-12-19 Time 10:05 Sent To B
Notes
2008-12-19 10:06:02TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-07-10 Cont ID  
Sent By adarroug Date 2008-07-10 Time 16:57 Rev Time 0.00
Received By adarroug Date 2008-07-10 Time 16:57 Sent To P
Notes
2008-07-10 16:58:13TO "MPERSON" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-07-09 Cont ID  
Sent By adarroug Date 2008-07-09 Time 09:31 Rev Time 0.00
Received By adarroug Date 2008-07-09 Time 09:31 Sent To Z
Notes
2008-07-09 09:31:54TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-12 Cont ID  
Sent By adarroug Date 2008-06-12 Time 10:12 Rev Time 0.00
Received By adarroug Date 2008-06-12 Time 10:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-05 Cont ID  
Sent By adarroug Date 2008-06-05 Time 09:06 Rev Time 0.00
Received By adarroug Date 2008-06-05 Time 09:06 Sent To Z
Notes
2008-06-05 09:06:24TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-28 Cont ID  
Sent By rmcdouga Date 2008-04-28 Time 17:36 Rev Time 0.00
Received By rmcdouga Date 2008-04-25 Time 09:18 Sent To  
Notes
2008-04-25 09:24:26TO "SFR" "E"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-12-02 Cont ID  
Sent By rregueir Date 2008-12-02 Time 16:15 Rev Time 0.00
Received By rregueir Date 2008-12-02 Time 16:14 Sent To PC
Notes
2008-12-02 16:15:39MECH PERMIT #08110536

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-04-28 Cont ID  
Sent By tgordon Date 2008-04-28 Time 10:59 Rev Time 0.15
Received By tgordon Date 2008-04-28 Time 10:59 Sent To P
Notes
2008-04-28 11:00:37NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-07-11 Cont ID  
Sent By mperson Date 2008-07-11 Time 14:55 Rev Time 0.00
Received By mperson Date 2008-07-11 Time 14:55 Sent To B
Notes
2008-07-11 14:58:51NOTE: NO PLUMBING ON PLANS, HOWEVER THE SCUPPER AND
 DOWNSPOUT COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED.

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-06-16 Cont ID  
Sent By jleech Date 2008-06-16 Time 08:50 Rev Time 0.00
Received By jleech Date 2008-06-16 Time 08:25 Sent To B
Notes
2008-06-16 08:55:01DENIED;
 1. SECONDARY ( EMERGENCY)ROOF DRAINS ARE REQUIRED.
 SEE FBC-PLUMBING SECTION 1107.1 , 1107.2 AND 1107.3.
 SHOW ON PLANS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-04-28 Cont ID  
Sent By jleech Date 2008-04-28 Time 12:34 Rev Time 0.00
Received By jleech Date 2008-04-28 Time 12:32 Sent To B
Notes
2008-04-28 12:44:27DENIED;
 NO PLUMBING WORK SHOWN ON PLANS, BUT PLUMBING
 CONTRACTOR IS SIGNED ON, THE PERMIT APLICATION,AS A
 SUBCONTRACTOR. THERE IS PLUMBING NOTES ON PAGE A-4.
 PLEASE SHOW PLUMBING WORK TO BE DONE ON PLANS WITH A
 SANITARY RISER DIAGRAM AND FIXTURES ON DRAWINGS. IF NO
 PLUMBING WORK WILL BE DONE THEN REMOVE PLUMBING NOTES
 FROM PLANS AND DELETE THE PLUMBING PERMIT NUMBER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2008-07-10 Cont ID  
Sent By mcruz Date 2008-07-10 Time 15:14 Rev Time 0.00
Received By mcruz Date 2008-07-10 Time 15:13 Sent To P
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2008-06-10 Cont ID  
Sent By choops Date 2008-06-10 Time 08:54 Rev Time 0.00
Received By choops Date 2008-06-10 Time 08:54 Sent To E
Notes
2008-06-10 08:56:45***FAILED - RESUB #1***
  
  
 1)PLANS SHALL BE STAMPED/APPROVED BY THE CITY'S
 HISTORIC PRESERVATION DEPARTMENT.
  
  
 NOTE:THE PROVIDED VARIANCE (#3158) FINAL ORDER HAS
 EXPIRED, HOWEVER, THE DETERMINATION WAS MADE BY THE
 PLANNING DEPARTMENT DIRECTOR THAT NO RENEWAL OF THIS
 VARIANCE WAS NEEDED.
  
 NOTE:THE EXTERIOR WALLS ARE NONCONFORMING WITH
 RESPECT TO THE SIDE AND REAR SETBACKS, ANY WORK THAT IS
 BEING DONE TO THESE AREAS SHALL NOT INCREASE THESE
 NONCONFORMITIES OR CREATE ANY NEW NONCONFORMITIES.THE
 PARAPET/CEILING OF THE STRUCTURE IS ALLOWED TO BE
 RAISED APPROXIMATELY 3'6".
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status P Date 2008-04-28 Cont ID  
Sent By choops Date 2008-04-28 Time 09:55 Rev Time 0.00
Received By choops Date 2008-04-28 Time 09:55 Sent To M
Notes
2008-04-28 09:59:40***APPROVED - NO VARIANCE REQUIRED PER C. WU***
  
  
  
  
 SENT TO "M" - SF RACK