2008-04-02 15:20:37 | ** DENIED** |
| |
| 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED |
| ON ELECTRICAL AS WELL AS ARCHITECTURAL SHEETS. SOME OF |
| THESE ARE ALREADY LISTED HOWEVER SOME CHANGES ARE |
| NEEDED. |
| 2004 FBC W/2007 REVISIONS. |
| 2002 NFPA-72 (IF FIRE ALARM SYSTEM IS PRESENT) |
| PLANS DO CALL FOR FA SYSTEM. |
| |
| 2) NOTE: PLEASE SEE FBC CHAPTER 13, 13-400.3.A, |
| 13-400.3.B, 13-400.3.C, 13-101.1.2 AND .1.3. |
| PLEASE SEE 13-415.2 FOR LIGHTING PERFORMANCE |
| CALCULATIONS.13-415.2.ABC.1.1, .1.2 AND .1.3. |
| FIRST ITEM IS THE METHOD SUBMITTED FOR ENERGY |
| CALCULATIONS IS THAT OF METHOD *A* WHICH IS FOR WHOLE |
| BUILDING COMPLIANCE. THIS IS NOT A WHOLE BUILDING; THIS |
| METHOD *A* IS NOT AN OPTION. |
| PLEASE ALSO SEE THAT IN ANY CASE THE VERSION MUST BE |
| THE ADOPTED VERSION PER THE FBC. THE VERSION 2.11 |
| SUBMITTED WAS UNDER THE OLDER 2004 CODE. THE VERSION |
| CHANGED ON DEC 8TH, 2006 WHICH IS ALMOST ONE AND HALF |
| YEARS AGO. |
| PLEASE SEE THE PLANS DO NOT CORRELATE WITH THE INPUT |
| DATA REPORT. |
| FOR EXAMPLE: |
| PLEASE SEE THE INTERIOR LIGHTING WHICH STATES ONLY ONE |
| FIXTURE TYPE WHICH IS 26W EACH HOWEVER THE PLANS |
| CONTAINS NUMEROUS OTHER FIXTURES WHICH ARE NOT PART OF |
| THE IDR. HOW IS THIS POSSIBLE? PLEASE BE SURE ALL ON |
| PLANS COORDINATES WITH THE CALCULATIONS. |
| FOR EXAMPLE: |
| PLEASE SEE THE LIGHTING CALCULATIONS ON PLANS WHICH |
| CONTAIN MANY MORE FIXTURES. EXTERIOR IS BLANK ON THE |
| IDR? |
| PLEASE SEE THE PRINTING OF THE OWNER AGENT AS A COMPANY |
| IS NOT ACCEPTABLE. THIS REQUIRES A SIGNATURE FROM THE |
| OWNER AGENT. |
| |
| 2) NOTE: PLEASE SEE 13-413.1.ABC.2, .2.1 AND .2.2 AND |
| PLACE NOTES ON PLANS ACCORDINGLY. |
| |
| 3) NOTE: PLEASE GIVE THE MAXIMUM TIMES ON THE OCCUPANCY |
| DEVICES. 13-415.1.ABC.1.1, .1.2. |
| |
| 4) NOTE: PLEASE COMPLETE ALL LOCATIONS FOR DEVICES PER |
| THE PROPOSED FA SYSTEM PER FBC ADA REQUIREMENTS |
| 11-4.28.1,.2 AND .3(4). MINIMUM LOCATIONS AND MINIMUM |
| LEVELS FOR DEVICES ARE NEEDED. |
| |
| 5) NOTE: PLEASE SEE NOTE #1 ABOVE WITH RESPECT TO |
| LIGHTING ON PLANS AND ALSO COMPLETE INFORMATION FOR |
| ITEMS WHICH ARE SHOWN AS J-BOXES IN CALCULATIONS FOR |
| PERFORMANCE LEVELS. 13-415.2. |
| |
| 6) NOTE: PLANS/PANEL SCHEDULE INDICATES A SMOKE ALARM |
| CIRCUIT. WHAT IS THIS? SEE NFPA-72 DEFINITIONS AND |
| NOTES ABOVE WITH RESPECT TO ANY MINIMUM DESIGNS |
| REQUIRED. |
| PLEASE ALSO COORDINATE THE LOAD ON PANEL WITH THAT OF |
| THE LOAD SHOWN ON LOAD CALCULATIONS FOR THIS SAME |
| CIRCUIT. |
| |
| 7) NOTE: PLEASE VERIFY ROOF-TOP GFI PER 210.8B, 210.63. |
| |
| PLANS INDICATE A GFI LOCATED ABOVE THE CEILING OF |
| BATHROOM FOR THE AHU, HOWEVER THIS IS NOTED ON PANEL |
| SCHEDULE AS ROOF-TOP? |
| |
| 8) NOTE: PLEASE ALSO SUBMIT DETAIL/INFORMATION FOR THE |
| REQUIRED DISCONNECT FOR THE CU. 440.11. |
| |
| |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |