Plan Review Details - Permit 08030648
Plan Review Stops For Permit 08030648
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-07 Cont ID  
Sent By mjacobs Date 2008-04-07 Time 12:46 Rev Time 0.00
Received By mjacobs Date 2008-04-07 Time 09:16 Sent To  
Notes
2008-04-07 12:46:06BUILDING PLAN REVIEW
 PERMIT: 08030648
 ADD: 1335 OKEECHOBEE BLVD
 CONT: E.W. KELSON BUILDERS INC.
 TEL: (561)793-5876
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 3)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 4)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO
 INCLUDE STRUCTURAL, ELECTRIC, PLUMING, MECHANICAL,
 INTERIOR FINISH, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS AND OVERHEAD AND PROFIT. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT AND MEANS COST
 ANALYSIS SERVICES PER FBC 108.3*
  
 5)PROVIDE A FIRE SPRINKLER HEAD PLAN SHOWING THE
 LOCATION OF THE SPRINKLER IN RELATION TO THE WALLS AND
 OFFICES. FBC 106.3.1.1(5)
  
 6)11-4.13.6
 MINIMUM MANEUVERING CLEARANCES AT DOORS THAT ARE NOT
 AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN IN FIGURE
 25. THE FLOOR OR GROUND AREA WITHIN THE REQUIRED
 CLEARANCES SHALL BE LEVEL AND CLEAR. THE MINIMUM
 CLEARANCE AT THE PULL SIDE SHALL BE 18 INCHES.
 7)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION;
 PROVIDE INFORMATION BASED ON INTERIOR FINISH
 REQUIREMENTS BASED ON OCCUPANCY.
  
 8)PROVIDE A FINISH SCHEDULE FOR ALL THE ROOMS AND
 INDICATE THE WALLS AND FLOOR FINISHES FOR EACH ROOM.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-04-02 Cont ID  
Sent By dpalmer Date 2008-04-02 Time 15:20 Rev Time 0.00
Received By dpalmer Date 2008-04-02 Time 15:20 Sent To  
Notes
2008-04-02 15:20:37** DENIED**
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED
 ON ELECTRICAL AS WELL AS ARCHITECTURAL SHEETS. SOME OF
 THESE ARE ALREADY LISTED HOWEVER SOME CHANGES ARE
 NEEDED.
 2004 FBC W/2007 REVISIONS.
 2002 NFPA-72 (IF FIRE ALARM SYSTEM IS PRESENT)
 PLANS DO CALL FOR FA SYSTEM.
  
 2) NOTE: PLEASE SEE FBC CHAPTER 13, 13-400.3.A,
 13-400.3.B, 13-400.3.C, 13-101.1.2 AND .1.3.
 PLEASE SEE 13-415.2 FOR LIGHTING PERFORMANCE
 CALCULATIONS.13-415.2.ABC.1.1, .1.2 AND .1.3.
 FIRST ITEM IS THE METHOD SUBMITTED FOR ENERGY
 CALCULATIONS IS THAT OF METHOD *A* WHICH IS FOR WHOLE
 BUILDING COMPLIANCE. THIS IS NOT A WHOLE BUILDING; THIS
 METHOD *A* IS NOT AN OPTION.
 PLEASE ALSO SEE THAT IN ANY CASE THE VERSION MUST BE
 THE ADOPTED VERSION PER THE FBC. THE VERSION 2.11
 SUBMITTED WAS UNDER THE OLDER 2004 CODE. THE VERSION
 CHANGED ON DEC 8TH, 2006 WHICH IS ALMOST ONE AND HALF
 YEARS AGO.
 PLEASE SEE THE PLANS DO NOT CORRELATE WITH THE INPUT
 DATA REPORT.
 FOR EXAMPLE:
 PLEASE SEE THE INTERIOR LIGHTING WHICH STATES ONLY ONE
 FIXTURE TYPE WHICH IS 26W EACH HOWEVER THE PLANS
 CONTAINS NUMEROUS OTHER FIXTURES WHICH ARE NOT PART OF
 THE IDR. HOW IS THIS POSSIBLE? PLEASE BE SURE ALL ON
 PLANS COORDINATES WITH THE CALCULATIONS.
 FOR EXAMPLE:
 PLEASE SEE THE LIGHTING CALCULATIONS ON PLANS WHICH
 CONTAIN MANY MORE FIXTURES. EXTERIOR IS BLANK ON THE
 IDR?
 PLEASE SEE THE PRINTING OF THE OWNER AGENT AS A COMPANY
 IS NOT ACCEPTABLE. THIS REQUIRES A SIGNATURE FROM THE
 OWNER AGENT.
  
 2) NOTE: PLEASE SEE 13-413.1.ABC.2, .2.1 AND .2.2 AND
 PLACE NOTES ON PLANS ACCORDINGLY.
  
 3) NOTE: PLEASE GIVE THE MAXIMUM TIMES ON THE OCCUPANCY
 DEVICES. 13-415.1.ABC.1.1, .1.2.
  
 4) NOTE: PLEASE COMPLETE ALL LOCATIONS FOR DEVICES PER
 THE PROPOSED FA SYSTEM PER FBC ADA REQUIREMENTS
 11-4.28.1,.2 AND .3(4). MINIMUM LOCATIONS AND MINIMUM
 LEVELS FOR DEVICES ARE NEEDED.
  
 5) NOTE: PLEASE SEE NOTE #1 ABOVE WITH RESPECT TO
 LIGHTING ON PLANS AND ALSO COMPLETE INFORMATION FOR
 ITEMS WHICH ARE SHOWN AS J-BOXES IN CALCULATIONS FOR
 PERFORMANCE LEVELS. 13-415.2.
  
 6) NOTE: PLANS/PANEL SCHEDULE INDICATES A SMOKE ALARM
 CIRCUIT. WHAT IS THIS? SEE NFPA-72 DEFINITIONS AND
 NOTES ABOVE WITH RESPECT TO ANY MINIMUM DESIGNS
 REQUIRED.
 PLEASE ALSO COORDINATE THE LOAD ON PANEL WITH THAT OF
 THE LOAD SHOWN ON LOAD CALCULATIONS FOR THIS SAME
 CIRCUIT.
  
 7) NOTE: PLEASE VERIFY ROOF-TOP GFI PER 210.8B, 210.63.
  
 PLANS INDICATE A GFI LOCATED ABOVE THE CEILING OF
 BATHROOM FOR THE AHU, HOWEVER THIS IS NOTED ON PANEL
 SCHEDULE AS ROOF-TOP?
  
 8) NOTE: PLEASE ALSO SUBMIT DETAIL/INFORMATION FOR THE
 REQUIRED DISCONNECT FOR THE CU. 440.11.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-04-08 Cont ID  
Sent By mawillia Date 2008-04-08 Time 10:50 Rev Time 0.00
Received By mawillia Date 2008-04-08 Time 09:18 Sent To  
Notes
2008-04-08 10:34:46*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3.PLEASE INDICATE IF THE BUILDING IS TO BE OCCUPIED
 DURING THE SCOPE OF WORK.IF SO, MEANS OF EGRESS AND
 AND REQUIRED FIRE PROTECTION FEATURES ARE TO BE IN
 PLACE AND CONTINUOUSLY MAINTAINED.
  
 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 5.AMEND FIRE EXTINGUISHER VERBAGE TO READ 2A10BC
 INSTEAD OF WHAT IS INDICATED IN GENERAL NOTES #5 ON
 SHEET A1.0
  
 6.THE CODE SUMMARY INFORMATION ON SHEET A1.0 STATES
 THAT THERE IS ONLY ONE FLOOR, HOWEVER, A SECOND FLOOR
 IS SHOWN ON SHEET E2.PLEASE EXPLAIN.
  
 7.PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS FOR
 THE PROPOSED SCOPE OF WORK.SHOW THE LOCATION OF THE
 FIRE ALARM DEVICES FOR THE PROPOSED SCOPE OF WORK.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER, INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-08 Cont ID  
Sent By mawillia Date 2008-04-08 Time 09:19 Rev Time 0.00
Received By mawillia Date 2008-03-28 Time 10:21 Sent To  
Notes
2008-03-28 10:26:07TO "BOB"#2

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-04-03 Cont ID  
Sent By tgordon Date 2008-04-03 Time 13:33 Rev Time 0.45
Received By tgordon Date 2008-04-03 Time 13:32 Sent To  
Notes
2008-04-03 13:51:58PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE ENERGY CALCULATIONS FOR THIS PROJECT CAN NOT USE
 FORM 400A, SEE 2004 FBC 13-101.1.3.
  
 2) WHEN DOING THE ENERGY CALCULATIONS DO NOT USE THE
 COMPUTER PROGRAM VERSION 2.11 YOU WILL NEED TO USE 2.5,
 SEE 2004 FBC 13-400.3.A, 13-400.3.B, 13-400.3.C, AND
 TABLE 13-400.3.ABC.3.
  
 3) PLEASE SUBMITCOOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-407.1.ABC.1.
  
 4) IF THE A/C CONDENSER STANDS ON THE ROOF ARE EXISTING
 PLEASE STATE SO ON THE MECHANICAL PLAN. IF NEW PLEASE
 SUBMIT PRODUCT APPROVAL OR AN NOA FOR PER-ENGINEERED
 CONDENSER STANDS, SEE FS 553.842(1) AND FAC RULE 9B-72,
 9B-72.005, AND FAC 9B-72.010(31)(G).
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 *** PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND
 SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B.
 AMEND. 106.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2008-04-01 Cont ID  
Sent By eschneid Date 2008-04-01 Time 09:19 Rev Time 0.00
Received By eschneid Date 2008-04-01 Time 09:19 Sent To  
Notes
2008-04-01 09:19:42NO MEZZANINE WORK.