Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-26 Cont ID  
Sent By rmcdouga Date 2008-03-26 Time 12:48 Rev Time 0.00
Received By rmcdouga Date 2008-03-26 Time 13:43 Sent To  
Notes
2008-03-26 11:52:172004 FBC W/2007 REVISIONS
 REROOF R-3
  
 DENIED BY BUILDING
  
 1)CIRCLE THE ATTACHMENT METHOD THAT WILL BE USED TO
 INSTALL THE ROOF TILES ON THE PRODUCT APPROVAL. SPECIFY
 LARGE OR MEDIUM PADDY IF USING POLYPRO.
  
 2) SUBMIT DOCUMENTATION INDICATING HOW THE REQUIREMENTS
 OF RULE 9B-3.0475 FOR HURRICANE MITIGATION RETROFITS
 WILL BE MET. THE VALUATION FOR AD VALOREM TAXATION FOR
 THE STRUCTURE IS MORE THAN $300,000, THEREFORE, THE
 ROOF TO WALL CONNECTIONS ARE REQUIRED TO BE IMPROVED AS
 REQUIRED BY SECTION 201.3 OF THE MITIGATION GUIDELINES
 UP TO 15 PER CENT OF THE COST OF RE-ROOFING.
  
 NOTE: THE RETROFIT FOR WALL CONNECTIONS WILL REQUIRE A
 RESIDENTIAL, BUILDING OR GENERAL CONTRACTOR PER FS
 489.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]