Plan Review Details - Permit 08030506
Plan Review Stops For Permit 08030506
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-04-29 Cont ID  
Sent By shill Date 2008-04-29 Time 08:02 Rev Time 0.00
Received By shill Date 2008-04-29 Time 08:02 Sent To  
Notes
2008-04-29 08:08:04****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.FBC1503.1, FLASHING TO BE INSTALLED TO PREVENT
 MOISTURE ENTERING THE WALL AND ROOF.THE THROUGH WALL
 FLASHING DETAIL DOES NOT COMPLY WITH THIS CODE SECTION.
 FROM THE INFORMATION PROVIDED, WATER APPEARS TO BE
 ENTERING THE BUILDING AND THE ROOFING CONTRACTOR IS
 MAKING AN ATTEMPT TO DIVERT THE WATER FROM THE INSIDE
 OF THE WALL TO THE OUTSIDE OF THE BUILDING.THIS
 SHOULD BE ACCOMPLISHED BY STOPPING THE WATER AT THE
 SOURCE(S) OF THE WATER INTRUSION, NOT AFTER IT HAS
 ENTERED A WOOD FRAME NON PT WALL WHICH WAS NEVER
 DESIGNED FOR WATER.OTHER COMMENTS RELATED TO
 DESIGN/PLANS OF THIS THROUGH WALL DETAIL DO NOT NEED TO
 BE ADDRESSED UNLESS CONTRACTOR FOLLOWS THE PROCESS TO
 GET THIS DETAIL APPROVED BY OTHERS.THIS HAS ALREADY
 BEEN REVIEWED AND DENIED BY THE PLANS EXAMINER AND
 ROBERT BROWN, LICENSE & PERMIT SERVICES MANAGER/ABO.
  
 2.FBC1503.3, CONTRACTOR SUBMITTED A DETAIL WHICH
 STATES THAT THE METAL IS OPTIONAL.HOWEVER, THE DETAIL
 DOES NOT SHOW WATERPROOFING MATERIAL THE FULL WIDTH OF
 THE PARAPET WALL.PLEASE INCLUDE A DETAIL WHICH
 COMPLIES WITH THIS REQUIREMENT.
  
 3.THE DETAIL IS NOT DEPICTED GRAPHICALLY IN A
 STANDARDIZED MANNER.IT APPEARS THAT THE
 "CROSS-SECTION" IS A COMBINATION OF A PERSPECTIVE AND A
 PLAN.PLEASE SEE FBC*106, ARCHITECTURAL QUALITY PLANS
 REQUIRED.
  
 4.THE SCOPE OF PROPOSED WORK IS NOT CLEAR.IT SHOWS
 ONE SECTION OF WALL, TWO STUDS.DOES THIS MEAN THAT
 YOU PROPOSE THIS INSTALLATION AT ONE LOCATION OR
 MULTIPLE LOCATIONS?PROVIDE AN OVERALL ROOF PLAN
 SHOWING LOCATION(S) OF DETAIL.
  
 5.IT IS NOT CLEAR HOW THE FLASHING AGAINST THE
 INTERIOR WALL WILL BE (OR WAS) ACCOMPLISHED.HOW CAN
 THE TOP OF THE FLASHING BE WATERPROOFED TO PREVENT
 WATER FROM GOING BEHIND THE FLASHING?WOULDN'T THIS
 REQUIRE REMOVAL OF THE EXTERIOR WALL SHEATHING AND
 STUCCO TO GET PROPER ACCESS TO THE TOP OF THE FLASHING?
 THIS WOULD BE BEYOND THE SCOPE OF A ROOFING
 CONTRACTOR'S LICENSE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-03-27 Cont ID  
Sent By jgomez Date 2008-03-27 Time 18:38 Rev Time 0.00
Received By jgomez Date 2008-03-27 Time 18:38 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-24 Cont ID  
Sent By shill Date 2008-03-24 Time 15:10 Rev Time 0.00
Received By shill Date 2008-03-24 Time 15:10 Sent To  
Notes
2008-03-24 15:18:42****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
 _XX_1.)EFFECTIVE OCTOBER 1, 2007, SECONDARY WATER
 BARRIER REQUIRED FS553.844(5)(A). PROVIDE
 INFORMATION (PRODUCT APPROVAL OR SPECIFICATIONS) TO
 SHOW HOW YOU WILL COMPLY WITH THIS REQUIREMENT.
 INFORMATION IS AVAILABLE AT WWW.BOAF.NET, HURRICANE
 MITIGATION.
  
 ____2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY;
 MEAN ROOF HEIGHT, ROOF PITCH, ROOF DECK TYPE, AREA OF
 EACH ROOF TYPE
  
 ____3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG
  
 _XX_4.)FOR THE FLAT ROOF, INDICATE WHICH FASTENER
 YOU ARE USING IF AS THE OPTIONS HAVE DIFFERENT PRESSURE
 LIMITATIONS.NOTE THAT THE FIELD FASTENING RANGES FROM
 TWO FIELD ROWS TO FOUR FIELD ROWS.
  
 _XX_5.)FOR THE FLAT ROOF ENHANCED FASTENING YOU
 HAVE PROVIDED A SAMPLE FROM PALM BEACH COUNTY.NOTE
 THAT IF YOU ARE USING A FASTENER WITH A
 PATTERN/PRESSURE OTHER THAN THAT IN THE EXAMPLE, THIS
 FASTENING PATTERN MAY NOT MEET WIND LOAD REQUIREMENTS.
 THIS CANNOT BE DETERMINED UNTIL A FASTENER AND PATTERN
 IS SELECTED FROM THE NOA, SEE ITEM 4 (INFORMATIONAL
 ONLY).
  
 ____ 6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH
 METHOD OF ATTACHMENT YOU ARE USING.IF YOU SELECT FOAM
 ADHESIVE, PRODUCT APPROVALS REQUIRED FAC9B72.
  
 ____ 7.)SEE PRODUCT LIMITATION #7.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-25 Cont ID  
Sent By adarroug Date 2008-03-25 Time 13:26 Rev Time 0.00
Received By adarroug Date 2008-03-25 Time 13:26 Sent To B
Notes
2008-03-25 13:27:14TO "SHILL" DESK/RESUB