Plan Review Details - Permit 08030488
Plan Review Stops For Permit 08030488 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2009-09-22 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-09-22 |
Time |
15:09 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-09-22 |
Time |
14:38 |
Sent To |
|
|
Notes |
2009-09-22 14:43:05 | *****REVISION #6, APPROVED***** | | | | | | REVISED PLAN SHEETS FA1-4.0, FA1-6.0, FA2-1.0, FA2-1.2, | | FA2-1.3, AND FA2-1.4 WERE STAMPED, INITIALED, AND | | DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
N |
Date |
2008-04-08 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-04-08 |
Time |
13:07 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-04-08 |
Time |
11:04 |
Sent To |
|
|
Notes |
2008-04-08 11:40:12 | *****PLANS STAMPED***** | | | | | | PLANS WERE APPROVED WITH PROVISO BY FIRE MARSHAL MIKE | | CARSILLO.PLAN SHEETS FA1-1.0, FA1-2.0, FA1-3.0, | | FA1-4.0, FA1-5.0, AND FA1-6.0 WERE STAMPED, INITIALED, | | AND DATED;READY FOR PERMIT ISSUANCE. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2008-04-07 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2008-04-07 |
Time |
14:13 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2008-04-07 |
Time |
12:58 |
Sent To |
|
|
Notes |
2008-04-07 14:13:04 | 1. THE ENTIRE FIRE ALARM SYSTEM SHALL BE MONITORED BY A | | UL LISTED CENTRAL STATION APPROVED FOR CENTRAL STATION | | SERVICE. | | | | 2. AS NOTED ON THE PLANS, SMOKE DETECTORS SHALL BE | | INSTALLED A MINIMUM OF THREE FEET FROM AIR CONDITIONER | | DIFFUSERS. | | | | 3. SMOKE DETECTION EQUIPMENT WILL BE NEEDED AT THE TOP | | OF THE ATRIUM ABOVE THE MONUMENTAL STAIR. A RECENT | | FIELD VISIT INDICATED THAT THE SMOKE DETECTORS LOCATED | | ON THE PERIMETER OF THE ATRIUM WOULD NOT ACTIVATE | | THEREFORE SMOKE DETECTION EQUIPMENT WILL BE NEEDED AT | | THE TOP. | | | | 4. TOTAL COMPLETE SMOKE DETECTION COVERAGE AS INDICATED | | IN CHAPTER 5, INITIATING DEVICES WITHIN NFPA 72, THE | | NATIONAL FIRE ALARM CODE "TOTAL COVERAGE SHALL INCLUDE | | ALL ROOMS, HALLS, STORAGE AREAS, BASEMENTS, ATTICS, | | LOFTS, SPACES ABOVE SUSPENDED CEILINGS AND OTHER | | SUBDIVISIONS AND ACCESSIBLE SPACES AS WELL AS THE | | INSIDE OF ALL CLOSETS, ELEVATOR SHAFTS, ENCLOSED | | STAIRWAYS, DUMBWAITER SHAFTS AND CHUTES". | | | | 5. SMOKE DETECTORS THAT ARE INSTALLED SHALL BE | | INSTALLED IN ACCORDANCE WITH NFPA 72, THE NATIONAL FIRE | | ALARM CODE AND THE MANUFACTURER'S SPECIFICATIONS. | | | | 6. ANY FIRE ALARM DEVICE THAT IS SUBJECT TO MOISTURE | | INTRUSION SHALL BE INSTALLED IN A WEATHERPROOF MANNER | | TO PREVENT DAMAGE. | | | | 7. THE ENTIRE FIRE ALARM SYSTEM IS SUBJECT TO FIELD | | INSPECTION AND APPROVAL. | | | | APPROVED PROVISO: | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | 804-4709 PHONE | | 804-4774 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-04-08 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-04-08 |
Time |
13:07 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-03-21 |
Time |
08:30 |
Sent To |
|
|
Notes |
2008-03-21 08:30:39 | TO "F" BOX |
|
|
|