Plan Review Details - Permit 08030488
Plan Review Stops For Permit 08030488
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-09-22 Cont ID  
Sent By mawillia Date 2009-09-22 Time 15:09 Rev Time 0.00
Received By mawillia Date 2009-09-22 Time 14:38 Sent To  
Notes
2009-09-22 14:43:05*****REVISION #6, APPROVED*****
  
  
 REVISED PLAN SHEETS FA1-4.0, FA1-6.0, FA2-1.0, FA2-1.2,
 FA2-1.3, AND FA2-1.4 WERE STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date 2008-04-08 Cont ID  
Sent By mawillia Date 2008-04-08 Time 13:07 Rev Time 0.00
Received By mawillia Date 2008-04-08 Time 11:04 Sent To  
Notes
2008-04-08 11:40:12*****PLANS STAMPED*****
  
  
 PLANS WERE APPROVED WITH PROVISO BY FIRE MARSHAL MIKE
 CARSILLO.PLAN SHEETS FA1-1.0, FA1-2.0, FA1-3.0,
 FA1-4.0, FA1-5.0, AND FA1-6.0 WERE STAMPED, INITIALED,
 AND DATED;READY FOR PERMIT ISSUANCE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-04-07 Cont ID  
Sent By mcarsill Date 2008-04-07 Time 14:13 Rev Time 0.00
Received By mcarsill Date 2008-04-07 Time 12:58 Sent To  
Notes
2008-04-07 14:13:041. THE ENTIRE FIRE ALARM SYSTEM SHALL BE MONITORED BY A
 UL LISTED CENTRAL STATION APPROVED FOR CENTRAL STATION
 SERVICE.
  
 2. AS NOTED ON THE PLANS, SMOKE DETECTORS SHALL BE
 INSTALLED A MINIMUM OF THREE FEET FROM AIR CONDITIONER
 DIFFUSERS.
  
 3. SMOKE DETECTION EQUIPMENT WILL BE NEEDED AT THE TOP
 OF THE ATRIUM ABOVE THE MONUMENTAL STAIR. A RECENT
 FIELD VISIT INDICATED THAT THE SMOKE DETECTORS LOCATED
 ON THE PERIMETER OF THE ATRIUM WOULD NOT ACTIVATE
 THEREFORE SMOKE DETECTION EQUIPMENT WILL BE NEEDED AT
 THE TOP.
  
 4. TOTAL COMPLETE SMOKE DETECTION COVERAGE AS INDICATED
 IN CHAPTER 5, INITIATING DEVICES WITHIN NFPA 72, THE
 NATIONAL FIRE ALARM CODE "TOTAL COVERAGE SHALL INCLUDE
 ALL ROOMS, HALLS, STORAGE AREAS, BASEMENTS, ATTICS,
 LOFTS, SPACES ABOVE SUSPENDED CEILINGS AND OTHER
 SUBDIVISIONS AND ACCESSIBLE SPACES AS WELL AS THE
 INSIDE OF ALL CLOSETS, ELEVATOR SHAFTS, ENCLOSED
 STAIRWAYS, DUMBWAITER SHAFTS AND CHUTES".
  
 5. SMOKE DETECTORS THAT ARE INSTALLED SHALL BE
 INSTALLED IN ACCORDANCE WITH NFPA 72, THE NATIONAL FIRE
 ALARM CODE AND THE MANUFACTURER'S SPECIFICATIONS.
  
 6. ANY FIRE ALARM DEVICE THAT IS SUBJECT TO MOISTURE
 INTRUSION SHALL BE INSTALLED IN A WEATHERPROOF MANNER
 TO PREVENT DAMAGE.
  
 7. THE ENTIRE FIRE ALARM SYSTEM IS SUBJECT TO FIELD
 INSPECTION AND APPROVAL.
  
 APPROVED PROVISO:
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-08 Cont ID  
Sent By mawillia Date 2008-04-08 Time 13:07 Rev Time 0.00
Received By mawillia Date 2008-03-21 Time 08:30 Sent To  
Notes
2008-03-21 08:30:39TO "F" BOX