Plan Review Details - Permit 08030447
Plan Review Stops For Permit 08030447
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-08-20 Cont ID  
Sent By shill Date 2008-08-20 Time 17:37 Rev Time 0.00
Received By shill Date 2008-08-20 Time 17:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-02 Cont ID  
Sent By shill Date 2008-04-02 Time 14:10 Rev Time 0.00
Received By shill Date 2008-04-02 Time 14:10 Sent To  
Notes
2008-04-02 14:12:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.PLAN CHECK ONLY.THIS REVIEW WILL REMAIN IN F
 STATUS UNTIL A PERMIT IS APPLIED FOR.
  
 2.PROVIDE A SOILS INVESTIGATION REPORT, TWO ORIGINALS
 (WITH ORIGINAL "WET" SIGNATURES), FBC1802.2.
  
 3.DECLARE GOVERNING CODE INCLUDING 2007
 REVISIONS/AMENDMENTS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-08-12 Cont ID  
Sent By dpalmer Date 2008-08-12 Time 11:47 Rev Time 0.00
Received By dpalmer Date 2008-08-12 Time 11:47 Sent To  
Notes
2008-08-12 11:48:07 
 **REDLINED PLANS**
  
 1) NOTE: THE EXISTING RISER INDICATES AN EQUIPMENT
 GROUNDING CONDUCTOR BEFORE THE FIRST MEANS OF
 DISCONNECT WHICH IS NOT PERMITTED PER 250.6,250.24.
 THIS WOULD CREATE OBJECTIONABLE CURRENTS.
  
 2) NOTE: ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED
 THE BASE FLOOD ELEVATION (BFE).
  
 IF THERE ARE NAY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-20 Cont ID  
Sent By dpalmer Date 2008-03-20 Time 10:58 Rev Time 0.00
Received By dpalmer Date 2008-03-20 Time 10:57 Sent To  
Notes
2008-03-20 10:58:28** DENIEDREVIEW **
  
  
  
 1) NOTE: PLEASE SEE THAT PLANS HAVE ONLY BEEN SUBMITTED
 FOR PLAN REVIEW ONLY. ONCE ALL COMMENTS HAVE BEEN
 ADDRESSED REVIEW WILL REMAIN IN FAILED STATUS UNTIL
 PERMIT IS APPLIED FOR.
  
 2) NOTE: PLEASE INDICATE THE FOLLOWING RELEVANT CODE ON
 ELECTRICAL.
 2005 NFPA-70
  
 3) NOTE: PLEASE SUBMIT INFORMATION ON CONDUIT(S) AND
 CONDUCTORS BEING INSTALLED AND THE SIZE OF THE EXISTING
 SERVICE.
 230.70, 240.4, 310.16.
 FBC 106.3.5.1.2, 106.1.2
  
 4) NOTE: FEES WERE NOT PAID AS OF THIS REVIEW.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2008-03-21 Cont ID  
Sent By rchokshi Date 2008-03-21 Time 08:59 Rev Time 0.00
Received By rchokshi Date 2008-03-21 Time 08:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-07 Cont ID  
Sent By shill Date 2008-08-07 Time 16:07 Rev Time 0.00
Received By shill Date 2008-08-07 Time 16:06 Sent To  
Notes
2008-08-07 16:07:22TO "COMM" BD#15--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-02 Cont ID  
Sent By shill Date 2008-04-02 Time 14:12 Rev Time 0.00
Received By shill Date 2008-03-19 Time 16:09 Sent To  
Notes
2008-03-19 16:10:13TO "COMM" BD#61--EXPEDITED--

Review Stop Z ZONING
Rev No 2 Status P Date 2008-08-18 Cont ID  
Sent By bpowell Date 2008-08-18 Time 17:04 Rev Time 0.00
Received By shill Date 2008-08-20 Time 17:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2008-08-20 Cont ID  
Sent By shill Date 2008-08-20 Time 17:36 Rev Time 0.00
Received By shill Date 2008-04-01 Time 10:14 Sent To  
Notes
2008-04-01 10:20:051.PLEASE PROVIDE AT LEAST TWO (2) COPIES OF A SURVEY
 FOR THE PROPERTY WITH THE PERMIT PACK.
  
 2.PLEASE INCLUDE PARCEL LINES ON THE SITE PLAN.
  
 3.PLEASE INDICATE A MEASURE OF SCALE FOR THE PLANS.
 NONE OF THE PLANS ARE DRAWN TO SCALE.
  
 4.PLEASE PROVIDE ELEVATIONS FOR THE FACILITY.
  
 FOR QUESTIONS OR COMMENTS PLEASE CONTACT: BOBBY POWELL
 JR., PLANNER, CITY OF WEST PALM BEACH, (561) 822-1435,
 [email protected]
  
  
  