2008-04-02 14:12:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1.PLAN CHECK ONLY.THIS REVIEW WILL REMAIN IN F | | STATUS UNTIL A PERMIT IS APPLIED FOR. | | | | 2.PROVIDE A SOILS INVESTIGATION REPORT, TWO ORIGINALS | | (WITH ORIGINAL "WET" SIGNATURES), FBC1802.2. | | | | 3.DECLARE GOVERNING CODE INCLUDING 2007 | | REVISIONS/AMENDMENTS. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2008-08-12 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-08-12 |
Time |
11:47 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-08-12 |
Time |
11:47 |
Sent To |
|
|
Notes |
2008-08-12 11:48:07 | | | **REDLINED PLANS** | | | | 1) NOTE: THE EXISTING RISER INDICATES AN EQUIPMENT | | GROUNDING CONDUCTOR BEFORE THE FIRST MEANS OF | | DISCONNECT WHICH IS NOT PERMITTED PER 250.6,250.24. | | THIS WOULD CREATE OBJECTIONABLE CURRENTS. | | | | 2) NOTE: ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED | | THE BASE FLOOD ELEVATION (BFE). | | | | IF THERE ARE NAY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2008-03-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-03-20 |
Time |
10:58 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-03-20 |
Time |
10:57 |
Sent To |
|
|
Notes |
2008-03-20 10:58:28 | ** DENIEDREVIEW ** | | | | | | | | 1) NOTE: PLEASE SEE THAT PLANS HAVE ONLY BEEN SUBMITTED | | FOR PLAN REVIEW ONLY. ONCE ALL COMMENTS HAVE BEEN | | ADDRESSED REVIEW WILL REMAIN IN FAILED STATUS UNTIL | | PERMIT IS APPLIED FOR. | | | | 2) NOTE: PLEASE INDICATE THE FOLLOWING RELEVANT CODE ON | | ELECTRICAL. | | 2005 NFPA-70 | | | | 3) NOTE: PLEASE SUBMIT INFORMATION ON CONDUIT(S) AND | | CONDUCTORS BEING INSTALLED AND THE SIZE OF THE EXISTING | | SERVICE. | | 230.70, 240.4, 310.16. | | FBC 106.3.5.1.2, 106.1.2 | | | | 4) NOTE: FEES WERE NOT PAID AS OF THIS REVIEW. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | DELAYS. | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2008-03-21 |
|
|
Cont ID |
|
Sent By |
rchokshi |
Date |
2008-03-21 |
Time |
08:59 |
Rev Time |
0.00 |
Received By |
rchokshi |
Date |
2008-03-21 |
Time |
08:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2008-08-07 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-08-07 |
Time |
16:07 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-08-07 |
Time |
16:06 |
Sent To |
|
|
Notes |
2008-08-07 16:07:22 | TO "COMM" BD#15--EXPEDITED-- |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-04-02 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-04-02 |
Time |
14:12 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-03-19 |
Time |
16:09 |
Sent To |
|
|
Notes |
2008-03-19 16:10:13 | TO "COMM" BD#61--EXPEDITED-- |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2008-08-18 |
|
|
Cont ID |
|
Sent By |
bpowell |
Date |
2008-08-18 |
Time |
17:04 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-08-20 |
Time |
17:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2008-08-20 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-08-20 |
Time |
17:36 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-04-01 |
Time |
10:14 |
Sent To |
|
|
Notes |
2008-04-01 10:20:05 | 1.PLEASE PROVIDE AT LEAST TWO (2) COPIES OF A SURVEY | | FOR THE PROPERTY WITH THE PERMIT PACK. | | | | 2.PLEASE INCLUDE PARCEL LINES ON THE SITE PLAN. | | | | 3.PLEASE INDICATE A MEASURE OF SCALE FOR THE PLANS. | | NONE OF THE PLANS ARE DRAWN TO SCALE. | | | | 4.PLEASE PROVIDE ELEVATIONS FOR THE FACILITY. | | | | FOR QUESTIONS OR COMMENTS PLEASE CONTACT: BOBBY POWELL | | JR., PLANNER, CITY OF WEST PALM BEACH, (561) 822-1435, | | [email protected] | | | | | | |
|
|